Table 5. Characteristics of various fuel gases

Table 6. Gas main sizing guide

Natural

1000 Btu

1.00

Propane

2500 Btu

1.10

Type

of Gas

Heating

Valve*†

Flow

Correction

Factor

* per cubic foot
† Consult fuel supplier for actual BTU value.

10

20

30

40

50

60

70

1/4

.364

32

22

18

15

14

12

11

3/8

.493

72

49

40

34

30

27

25

1/2

.622

132

92

73

63

56

50

46

3/4

.824

278

190

152

130

115

105

96

1

1.049

520

350

285

245

215

195

180

1 1/4

1.380

1,050

730

590

500

440

400

370

1 1/2

1.610

1,600

1,100

890

760

670

610

560

2

2.067

3,050

2,100

1,650

1,450

1,270

1,150

1,050

2 1/2

2.469

4,800

3,300

2,700

2,300

2,000

1,850

1,700

3

3.068

8,500

5,900

4,700

4,100

3,600

3,250

3,000

4

4.026

17,500

12,000

9,700

8,300

7,400

6,800

6,200

80

90

100

125

150

175

200

1/4

.364

11

10

9

8

8

7

6

3/8

.493

23

22

21

18

17

15

14

1/2

.622

43

40

38

34

31

28

26

3/4

.824

90

84

79

72

64

59

55

1

1.049

170

160

150

130

120

110

100

1 1/4

1.380

350

320

305

275

250

225

210

1 1/2

1.610

530

490

460

410

380

350

320

2

2.067

990

930

870

780

710

650

610

2 1/2

2.469

1,600

1,500

1,400

1,250

1,130

1,050

980

3

3.068

2,800

2,600

2,500

2,200

2,000

1,850

1,700

4

4.026

5,800

5,400

5,100

4,500

4,100

3,800

3,500

Nominal

Iron Pipe

Size

Inches

Internal

Diameter

Inches

Equivalent

Length of Pipe, Feet

Maximum capacity of pipe in cubic
feet of gas per hour for gas pres-
sures of 0.5 psig or less and a
pressure drop of 0.3 inch water
column (based on a 0.60 specific
gravity gas).

 

Содержание GAS Modular Boilers

Страница 1: ...The unit must be electrically grounded if an external power source is used In Canada the installation must be in accordance with standards CGA B149 1 and B149 2 installation codes for gas burning appl...

Страница 2: ......

Страница 3: ...2275 78 1 82 4 4880 301 16 625 8 10 1323 32 253 16 115 16 21 2 3 GGHT 3375E 9 GG 375HEC 3375 2736 15860 2379 81 7 92 7 5490 301 16 595 8 10 1323 32 253 16 115 16 23 10 3 GGHT 3600E 9 GG 399HEC 3591 29...

Страница 4: ...4 Design Data Max ASME Working Pressure 100 psi Power Requirements 120 volts 60 HZ 34 amps per module Figure 1 Gas Caravan dimensions and typical piping hot water models...

Страница 5: ...r piping for variable circulation Figure 3 Supply and return piping locations Figure 4 Instantaneous tankless coil two temperature with recirculation Figure 5 Storage tank from tankless coil with reci...

Страница 6: ...lief valve ASME unmounted Specify 30 50 or 100 psi Control header unmounted one per system Draft hoods unmounted OPTIONAL EQUIPMENT Hot water supply and return header assemblies Control panel with aut...

Страница 7: ...opening near the floor below burner air inlet and one louvered opening near the ceiling above the highest draft regulator each opening with a minimum FREE air passage area of 1 square inch per 4000 B...

Страница 8: ...8 Figure 8 Typical layouts for gas fired systems...

Страница 9: ...uld be used where permitted for additional protection against adverse wind conditions and precipitation The National Board of Fire Underwriters recommend that the chimney should extend at least 3 feet...

Страница 10: ...ation of this pipe in a typical appli cation Table 2a depicts the proper diameter Dim C of the connector rise depending upon its total length top of the draft hoods to the breeching above GG 200C 7 7...

Страница 11: ...057 4 68 2 11 2 34 3 11 1 1 4 2 19 1 37 1 07 0 082 6 54 2 94 3 27 4 35 1 1 2 2 63 1 64 1 29 0 098 7 84 3 52 3 92 5 21 2 3 55 2 23 1 74 1 320 10 60 4 77 5 30 7 05 3 5 72 3 59 2 81 2 130 17 08 7 69 8 8...

Страница 12: ...3 068 8 500 5 900 4 700 4 100 3 600 3 250 3 000 4 4 026 17 500 12 000 9 700 8 300 7 400 6 800 6 200 80 90 100 125 150 175 200 1 4 364 11 10 9 8 8 7 6 3 8 493 23 22 21 18 17 15 14 1 2 622 43 40 38 34 3...

Страница 13: ...The view menu on the control includes error messages actual outdoor air temperature actual supply water temperature target supply water temperature and running time for each stage This control can be...

Страница 14: ...Plastic tie straps Other Options include Immersion well for supply water sensor to be installed in control header supplied with Caravan High Limit manual reset and Immersion Well to be installed in co...

Страница 15: ...15 FIELD WIRING AT MODULES...

Страница 16: ...16 SC 3 SYSTEM WIRING DIAGRAM...

Страница 17: ...17 SC 3 LADDER WIRING DIAGRAM...

Страница 18: ...18 SC 9 SPACE HEATING WIRING DIAGRAM...

Страница 19: ...19 SC 9 SPACE HEATING LADDER WIRING DIAGRAM...

Страница 20: ...20 SC 9 SPACE AND DOMESTIC HOT WATER WIRING DIAGRAM...

Страница 21: ...21 SC 9 SPACE AND DOMESTIC HOT WATER LADDER WIRING DIAGRAM...

Страница 22: ...base jacket insulation combustion chamber tankless heater exhaust and air inlet piping burner enclosure mixing elbow gas and air orifice blower assem bly air filter and electrical and mechanical comp...

Страница 23: ...CARAVAN SYSTEM RATING PLATE System rating plate format for Caravan modular boiler system System rating plates are available upon request using the form on the back cover...

Страница 24: ...N Y 11548 Phone 516 484 2600 FAX 516 484 5921 Canada Slant Fin LTD LTEE Mississauga Ontario www slantfin com Each individual Caravan module is shipped with a rating plate bearing the model serial numb...

Отзывы: