background image

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
For automatic applications… 

  Make sure the outdoor temperature sensor is mounted completely outside  

the house (i.e., not recessed into the hole) on the North, Northeast or North-
west side, away from direct sunlight.  

  Make sure the outdoor temperature sensor is mounted at least three feet  

away from all exhaust vents.  

  If the outdoor temperature sensor is mounted in the fresh air intake duct,  

make sure the probe is no further than 30 inches from an outside wall.  

 

NOTES: 

In AUTOMATIC applications, if the outdoor temperature is greater than         
+50°F (+10ºC) or less than -32°F (-35.6ºC), the humidifier control will not  
operate (except in “Test” mode).  
In both AUTOMATIC and MANUAL applications, if the relative humidity 
in the home is higher than the knob setting, 

Compustat 

will not operate the 

humidifier. Similarly, 

Compustat

 will not operate if the indoor relative    

humidity exceeds 45 percent. 

Humidifier operates constantly 

 

• 

Check the humidifier control setting. If the relative humidity in the home is  
less than the knob setting, the humidifier will operate until the humidity level 
is higher than the knob setting.  

• 

In the “Test” mode, verify that the humidifier will shut off after approxi- 
mately one minute.  

• 

Check the resistance of the sensor. (See previous section.) 

For automatic applications… 

• 

Make sure the outdoor temperature sensor is mounted completely outside  
the house (i.e., not recessed into the hole) on the North, Northeast or North-
west side, away from direct sunlight.  

• 

Turn the humidifier control knob counterclockwise (

4

) to the “Off” posi- 

tion and observe whether the humidifier turns off. If the humidifier continues 
to operate, perform the following:  

—  Check the wiring diagrams (Figures 5-8) for correct installation.  
—  Remove the wires from the humidifier control’s “Out” terminals. If the       
 

humidifier continues to operate, check the humidifier.  

Humidifier or humidifier control 

 

• 

Use a voltmeter to check for a steady 22-to-30VAC.      

“chatters” or clicks on and off

 

• 

For automatic applications, make sure the outdoor temperature sensor wiring  

rapidly

 does 

not run alongside wires carrying high voltage (120 VAC or higher).  

 

 

 

 
 

 100°F

    6,000 ohms

 38°C

 90°F

    7,500 ohms

 32°C

 80°F

    9,500 ohms

 27°C

 70°F

  11,500 ohms

 21°C

 60°F

  14,000 ohms

 16°C

 50°F

  18,000 ohms

 10°C

 40°F

  23,000 ohms

 4°C

 30°F

  28,500 ohms

 -1°C

 20°F

  37,000 ohms

 -7°C

 10°F

  46,500 ohms

 -12°C

   0°F

  61,500 ohms

 -18°C

-10°F

  78,500 ohms

 -23°C

-20°F

105,500 ohms

 -29°C

-30°F

135,000 ohms

 -34°C

Temperature/Resistance Chart 

Содержание Compustat SEH-7100-000

Страница 1: ...a heat call is satisfied to prevent high temperatures from damaging the control Do not set the humidity so high that condensation forms on windows or walls Indoor condensation may result in damage to the home These instructions are for installation of the Skuttle Compustat humidifier control only For installation of a Skuttle humidifier refer to the instructions packaged with the humidifier STEP 1...

Страница 2: ...Compustat for Manual Operation STEP 6 Route the Sensor Wire to the Selected Location Run wire between the humidifier control and the outdoor sensor lead If the sensor is out doors snap the probe end of the sensor into the sensor shield and attach it to an exterior wall The probe must be completely covered by the shield NOTE The outdoor temperature sensor wire must not exceed 30 feet in length CAUT...

Страница 3: ...he Out terminals on the humidifier con trol Also attach a jumper wire to the Wire Connector as shown in Figures 6 and 7 Do not use a Model A50 relay NOTE See the furnace manual for operation of accessory terminals If an external transformer is used connect a Model A50 relay in series with the solenoid valve and the Out terminals on the humidifier control This will allow the humidifier to operate o...

Страница 4: ... Guide below 5 Set the humidifier control If the home is occupied set the humidifier control knob to 5 For manual operation set the knob to 35 If the home is vacant turn the humidifier control knob counterclockwise 4 to Off 6 Tell the homeowner to refer to the Compustat Operating Instructions for direction regarding initial adjustment Troubleshooting Guide applies to automatic and manual operation...

Страница 5: ...e verify that the humidifier will shut off after approxi mately one minute Check the resistance of the sensor See previous section For automatic applications Make sure the outdoor temperature sensor is mounted completely outside the house i e not recessed into the hole on the North Northeast or North west side away from direct sunlight Turn the humidifier control knob counterclockwise 4 to the Off...

Страница 6: ...101 Margaret Street Marietta OH 45750 Phone 800 848 9786 Fax 740 373 9565 Email customerservice skuttle com Web www skuttle com ...

Отзывы: