Select an Exterior Location to Mount the Outdoor Temperature Sensor 

Placement of the outdoor temperature sensor must meet these requirements:  

• 

It must be mounted on the North, Northeast or Northwest side of the house, where 
direct sunlight will not influence the sensor.  

• 

It must be placed at least 3 feet from all exhaust vents. 

• 

It must be installed above the expected snow line (see Figure 3).  

 

CAUTION: 

Incorrect indoor humidity levels will result if these requirements are not 

met.  
 

NOTE: 

For manual operation, do not install the sensor wire.   

 

S

TEP

 5:

  

Locate an Existing Indoor/Outdoor Access Hole 

If possible, insert the sensor cable through an existing indoor/outdoor access hole for 
cable TV lines, telephone lines, A/C lines, etc.  
 

CAUTION: 

Make sure there are no active high-voltage wires in the hole.  

 

As an alternative, the sensor can be mounted in the center of a 6-inch fresh air intake duct.  

However, the sensor bulb must be no further than 30 inches from the outside wall. (See Figure 4.)  
 
The sensor can also be mounted in the center of a 6 inch pipe used for make-up air or 
combustion make-up air devices (such as a Skuttle Model 216 or Combustion Air Dif-
fuser). The sensor must be no further than 30 inches from the outside wall.  

 

NOTE: 

If it is not possible to install the outdoor temperature sensor in any of these con-

figurations, 

Compustat

 can be installed to operate manually. (See “Installing 

Compustat

 

for Manual Operation”) 
 

S

TEP

 6:

  

Route the Sensor Wire to the Selected Location 

Run wire between the humidifier control and the outdoor sensor lead. If the sensor is out-
doors, snap the probe end of the sensor into the sensor shield and attach it to an exterior wall. The probe must be completely 
covered by the shield.  
 

NOTE: 

The outdoor temperature sensor wire must not exceed 30 feet in length. 

 

CAUTION: 

Do not run outdoor temperature sensor wire alongside wires carrying high voltage 

(120 VAC or higher); 

do not run the sensor wire through conduit.  
 

S

TEP

 7:

  

Attach the Sensor Wire to the Humidifier Control  

Strip the connecting wire 1/4" and attach the two internal wires to the terminals labeled “Outdoor Temperature Sensor” on 
the humidifier control.  
 

S

TEP

 8:

  

Select a Power Source 

Select a source for 24 VAC to power the humidifier control, based on the following options:  

For furnaces with accessory terminals… 

• 

If the accessory terminals provide 24 VAC, wire them to the “24 VAC” terminals on the humidifier control.  

• 

If the accessory terminals provide 120 VAC, wire them to a 24 VAC transformer; connect the transformer to the “24 
VAC” terminals on the humidifier control.  

For other furnaces, a 24 VAC transformer must be added.  

• 

Wire into a power source other than the furnace accessory terminals. (The transformer can be powered off the 120 VAC 
line at the junction box, before it enters the furnace.)  

• 

Connect the 24-volt side of the transformer to the “24 VAC” terminals on the humidifier control.  

 
In either configuration, the voltage to the humidifier control must be between 22 and 30 VAC.  

Figure 3 

Figure 4 

Содержание Compustat SEH-7100-000

Страница 1: ...a heat call is satisfied to prevent high temperatures from damaging the control Do not set the humidity so high that condensation forms on windows or walls Indoor condensation may result in damage to the home These instructions are for installation of the Skuttle Compustat humidifier control only For installation of a Skuttle humidifier refer to the instructions packaged with the humidifier STEP 1...

Страница 2: ...Compustat for Manual Operation STEP 6 Route the Sensor Wire to the Selected Location Run wire between the humidifier control and the outdoor sensor lead If the sensor is out doors snap the probe end of the sensor into the sensor shield and attach it to an exterior wall The probe must be completely covered by the shield NOTE The outdoor temperature sensor wire must not exceed 30 feet in length CAUT...

Страница 3: ...he Out terminals on the humidifier con trol Also attach a jumper wire to the Wire Connector as shown in Figures 6 and 7 Do not use a Model A50 relay NOTE See the furnace manual for operation of accessory terminals If an external transformer is used connect a Model A50 relay in series with the solenoid valve and the Out terminals on the humidifier control This will allow the humidifier to operate o...

Страница 4: ... Guide below 5 Set the humidifier control If the home is occupied set the humidifier control knob to 5 For manual operation set the knob to 35 If the home is vacant turn the humidifier control knob counterclockwise 4 to Off 6 Tell the homeowner to refer to the Compustat Operating Instructions for direction regarding initial adjustment Troubleshooting Guide applies to automatic and manual operation...

Страница 5: ...e verify that the humidifier will shut off after approxi mately one minute Check the resistance of the sensor See previous section For automatic applications Make sure the outdoor temperature sensor is mounted completely outside the house i e not recessed into the hole on the North Northeast or North west side away from direct sunlight Turn the humidifier control knob counterclockwise 4 to the Off...

Страница 6: ...101 Margaret Street Marietta OH 45750 Phone 800 848 9786 Fax 740 373 9565 Email customerservice skuttle com Web www skuttle com ...

Отзывы: