Installing the Humidifier Control to Operate Manually 

 
If it is not possible to use the outdoor temperature sensor, or if the homeowner wants to 
control the humidifier manually, 

Compustat

 can be reconfigured for manual operation. 

(See Figure 9.) 
 
1.  Locate the three-pin arrangement marked “AUTO/MAN”, protruding from the con-

trol board (directly to the right of the wiring connections).  

2.  Pull upward to remove the black, two-pin connector from the auto position. Rein-

stall it in the manual position (on the center and right-hand pins).  

 NOTE: 

Do not attach sensor wire to the blue wiring connection block.  

3.  Follow Steps 8 and 9 to complete the wiring. Apply the manual-mode faceplate to 

the 

Compustat 

cover. Reattach the cover to the base and reinstall the knob.  

 

System Checkout 

 
1.  To conduct a system test, be sure that 24 VAC is applied to the 24 VAC terminals of the humidifier control.  
2. Reattach 

the 

Compustat 

cover and knob to the base. 

3.  Activate the furnace blower and confirm that the thermostat is calling for heat.  
4.  Rotate the knob on the humidifier control clockwise (

3

) to the “Test” position.  

  If everything is set up correctly, the humidifier should begin operating. In “Test” mode, 

Compustat

 will operate for 

 

approximately one minute.  

  If the humidifier does not activate properly in “Test” mode, refer to the Troubleshooting Guide, below.  

5.  Set the humidifier control.  

  If the home is occupied, set the humidifier control knob to “5”. (For manual operation, set the knob to “35%”.) 

  If the home is vacant, turn the humidifier control knob counterclockwise (

4

) to “Off”.  

6.  Tell the homeowner to refer to the 

Compustat 

Operating Instructions for direction regarding initial adjustment.  

 

Troubleshooting Guide 

(applies to automatic and manual operation, unless otherwise indicated) 

 

P

ROBLEM

 

S

OLUTION

(

S

)  

 
Humidifier does not operate

 

  Make sure the furnace blower is operating and the thermostat is calling for  

in “Test” mode

 heat. 

 

  Confirm that the outdoor temperature sensor is connected to the “Outdoor  

Temperature Sensor” terminals on the humidifier control. (For manual op-
eration, make sure the jumper pins are positioned correctly.)  

  Check the wiring diagrams (Figures 6-8) for correct installation. 

  Check the voltage at the humidifier control “24 VAC” terminals. (Voltage  

should be between 22 and 30 VAC.)   

  Check the Model A50 relay (if used) for proper installation. (The relay is to  

be wired to the “Out” circuit only!) 

• 

Make sure the control knob has not been left in the “Test” position. (In  

“Test” mode, the humidifier will not continue to operate after approximately 
one minute.)  

Humidifier operates only in 

 

  Check the resistance of the sensor by removing the leads from the humidifier  

“Test” mode

 

control terminals, and measuring the resistance across the wires with an 

 

ohmmeter. Compare the reading to the temperature/resistance chart, which 

 follows. 

 Temp. 

Resistance 

 

 

Figure 9 

Automatic 

Manual 

Содержание Compustat SEH-7100-000

Страница 1: ...a heat call is satisfied to prevent high temperatures from damaging the control Do not set the humidity so high that condensation forms on windows or walls Indoor condensation may result in damage to the home These instructions are for installation of the Skuttle Compustat humidifier control only For installation of a Skuttle humidifier refer to the instructions packaged with the humidifier STEP 1...

Страница 2: ...Compustat for Manual Operation STEP 6 Route the Sensor Wire to the Selected Location Run wire between the humidifier control and the outdoor sensor lead If the sensor is out doors snap the probe end of the sensor into the sensor shield and attach it to an exterior wall The probe must be completely covered by the shield NOTE The outdoor temperature sensor wire must not exceed 30 feet in length CAUT...

Страница 3: ...he Out terminals on the humidifier con trol Also attach a jumper wire to the Wire Connector as shown in Figures 6 and 7 Do not use a Model A50 relay NOTE See the furnace manual for operation of accessory terminals If an external transformer is used connect a Model A50 relay in series with the solenoid valve and the Out terminals on the humidifier control This will allow the humidifier to operate o...

Страница 4: ... Guide below 5 Set the humidifier control If the home is occupied set the humidifier control knob to 5 For manual operation set the knob to 35 If the home is vacant turn the humidifier control knob counterclockwise 4 to Off 6 Tell the homeowner to refer to the Compustat Operating Instructions for direction regarding initial adjustment Troubleshooting Guide applies to automatic and manual operation...

Страница 5: ...e verify that the humidifier will shut off after approxi mately one minute Check the resistance of the sensor See previous section For automatic applications Make sure the outdoor temperature sensor is mounted completely outside the house i e not recessed into the hole on the North Northeast or North west side away from direct sunlight Turn the humidifier control knob counterclockwise 4 to the Off...

Страница 6: ...101 Margaret Street Marietta OH 45750 Phone 800 848 9786 Fax 740 373 9565 Email customerservice skuttle com Web www skuttle com ...

Отзывы: