DOL 535 • DOL 539
Technical Manual
33
Type of scales
Recommended calibration weight
[kg]
70 kg scale
10
Other scale
Half of the maximum weight
4.1.1 Checking the bird scale calibration
A simple way to check the bird scale calibration is in the menu
| Technical | Manual/auto | Production
| Bird scale
First test with an empty bird scale (0 kg) and then with a 5 kg calibration weight.
The results should be as shown in the table:
DOL 94-10
DOL 98S-20
Weight
Voltage
Scale
Voltage
Empty scale (0 kg) 0 +/- 50 g
0.400– 0,600 V
0 +/- 50 g
0.400– 0,600 V
5 kg weight
5000 +/- 100 g
5000– 5500 V
5000 +/- 200 g
2200– 2500 V
If these results are not obtained, the scale must be calibrated again, see the section
the scale.
4.2 Calibration of light
Calibrate the light control after installation.
When a light sensor is connected to the light source, calibration can be carried out against the measured value.
Otherwise a lux meter must be used.
Select the menu
Technical | Calibration | Production | Light
.
Activate
Manual calibration
.
Relay-controlled light
Enter the measured lux value for ON.