DOL 535 • DOL 539
10
Technical Manual
3.4.2 The menu Show Connection
When you have selected all the components in the installation menu, the house controller will show you where
to connect the individual components.
See the menu
Show connection
for where exactly to connect the individual components.
When a wiring diagram in the Circuit Diagrams and Cable Plans reads "See Show connection", it refers to this
menu.
3.4.3 Manual I/O allocation
If you want to decide the I/O-allocation for one or more components yourself, you can change it manually under
the menu item
Manual I/O allocation
.
Select the menu
Technical | Installation | Manual I/O
allocation
, and press the component to be changed.
Choose between the listed terminals. Please note if a terminal
is currently allocated to another function.
Press the required terminal.
If you use a terminal that is currently used by another function,
the house controller will change the I/O allocation for this func-
tion.
Check in the menu
Show connections
that the house controller
has moved the first allocated function to another terminal.
The controller will change the I/O allocation instantly.
If the I/O allocation can be changed, the house controller will
accept it.
If the I/O allocation cannot be changed, the house controller will
reject it, and the I/O allocation will remain unchanged.
3.4.4 Shared equipment
Controllers in the same network (see
) can share equipment such as outside tempera-
ture sensor and outside humidity sensor.
The controller where the equipment is physically connected is called the ‘Master’. The other controllers are
called ‘Clients’.
A climate or production controller may be the’ Master’ of connected equipment while it is also the ‘Client’ of
equipment connected to another controller.
If the connection between the controllers is lost, an alarm appears on both the ‘Master’ and the ‘Client’
controller.
Example of shared outside temperature sensor - setup in ‘Client’ controller