37
SKOPE TME650/1000
Replacement Procedures
Service Manual
Thermostat
The thermostat is pre-set to give an internal air temperature of between 1°C
and 4°C, and in normal circumstances should not require adjustment. If
thermostat adjustment is required: to make colder - turn clockwise, to make
warmer - turn anti-clockwise.
To replace the thermostat
Figure 5: Thermostat
dial
Thermostat
1. Disconnect the chiller from the power supply.
2. Remove the evaporator box assembly lid to access the interior of the
evaporator box.
3. Withdraw the capillary from evaporator, noting original position and length
into coil.
4. Open the unit junction box (see page 36), remove and replace the
thermostat. When refitting thermostat, ensure the capillary is fitted back in the
original position.