INSTALLATION AND COMMISSIONING
SKF Enlight Collect gateway
44 (84)
SKF Enlight Collect IMx-1 System
User Manual
Revision A
D. The gateway should be decommissioned, press Commission to proceed.
E.
Now choose the ‘virtual’ gateway, configured in @ptitude Observer, that this
physical gateway should be associated with. Virtual gateways will be listed
with both their name and location text visible. Virtual gateway locations that
are already commissioned will have MAC addresses associated with them
and be unavailable for selection.
F. Having now selected the associated physical and virtual gateways press
Commission to complete the process.
The configuration the gateway now has is not the measurement configuration but the
settings that facilitate data exchange with its sensors and the @ptitude Observer
software. The latter includes:
•
The gateway networking interface:
o
Ethernet (wired)
o
WiFi
•
IP configuration for the selected network interface
o
DHCP
or
o
Static: IP address, subnet mask, gateway and DNS settings
•
Wi-Fi connection setup, where Wi-Fi selected
o
Security:
WPA2
(WPA2-PSK)
o
SSID and password: password received and stored by the gateway
as an encrypted string
•
Sensor, mesh radio setup
o
Security: 128-bit AES encryption key
o
A unique, mesh network, identifier
•
Configuration for the software connection
o
@ptitude Observer
o
Connection URL
Note that default values are those shown above, in bold. Any errors encountered in
transferring the configuration are reported in-app. All credentials stored are
encrypted.
On successful completion of the commissioning activity, the gateway status is
changed to commissioned and the networking and sensor mesh radio, are activated.