
INSTALLATION AND COMMISSIONING
SKF Enlight Collect gateway
40 (84)
SKF Enlight Collect IMx-1 System
User Manual
Revision A
Figure 23
Example of connector/cable assemblies
Longer cable assemblies or intermediate junction boxes may be required depending
on site layout and requirements.
3.2.2 Power requirements
The SKF Enlight Collect Gateway is designed to be powered from either PoE or an
industrial range 24 V DC supply, including 12 V battery operation. The connection
details for the DC supply are as shown in the figure and table below.
Figure 24
Incoming power supply connection
Table 1
DC in connections
DC Power In
Connector pin
Cable core colour
0 V (Power supply return)
1 and 4
White
+ 24 V (9
–36V DC)
2 and 3
Brown
Incoming power is isolated from other gateway circuitry.