VFDC-3000 Controller User Manual
I/O TABLE
J1 POWER AND COMMUNICATIONS
PIN
NAME
DESCRIPTION
1
N/C
- NO CONNECTION -
2
N/C
- NO CONNECTION -
3
0V
RETURN FOR +24 VDC SUPPLY
4
+24 VDC
19 - 28 VDC SUPPLY
5
D+
VFD COMM (RS-485) - MODBUS
6
D-
VFD COMM (RS-485) - MODBUS
7
SHIELD
8
A OUT
4-20mA LOOP, POWER SUPPLIED
9
AO COM
4-20mA LOOP RETURN
10
N/C
- NO CONNECTION -
11
GND
PROTECTIVE EARTH GROUND
12
GND
PROTECTIVE EARTH GROUND
J2 RELAY OUTPUTS
PIN
NAME
DESCRIPTION
1
RELAY 1
CONFIGURABLE RELAY 1
2
3
RELAY 2
CONFIGURABLE RELAY 2
4
5
RELAY 3
CONFIGURABLE RELAY 3
6
7
RELAY 4
CONFIGURABLE RELAY 4
8
9
RELAY 5
CONFIGURABLE RELAY 5
10
11
RELAY 6
CONFIGURABLE RELAY 6
12
J3 DIGITAL/ANALOG INPUTS
PIN
NAME
DESCRIPTION
1
COM
INPUT COMMON RETURN
2
LOW SUCTION
LOW SUCTION INPUT
3
HIGHPRESSURE
HIGH PRESSURE INPUT
4
LOW WATER
LOW WATER INPUT
5
SETPOINT 2
SETPOINT PRESSURE 2 INPUT
6
N/C
- NO CONNECTION -
7
N/C
- NO CONNECTION -
8
N/C
- NO CONNECTION -
9
N/C
- NO CONNECTION -
10
N/C
- NO CONNECTION -
11
N/C
- NO CONNECTION -
12
N/C
- NO CONNECTION -
13
SHIELD
14
NC
- NO CONNECTION -
15
PRESSURE
4 - 20mA LOOP INPUT
16
+24 VDC OUT
PRESS TRANSMITTER SUPPLY
All Digital Input functions are activated upon a
contact closure to the Input Common Return (COM)
terminal.
Note:
Pins J1-3, J1-7, J1-11, J1-12, J3-1, J3-13 and J3-14
are all internally connected and should be wired to
Protective Earth Ground at terminal J1-11 or J1-12.