15
N.B.
if within 5 sec it is not "confirmed", the days-meter comes back to the current counting value
AL2:
Indicates lamp failure. Check:
o
Lamp connection.
o
If lamp is burned by testing another lamp.
o
If lamp starter has failed by testing a new lamp.
In case of lamp replacement press and hold for less than 5 seconds the
(
◄
┘
)
button. The value of the
days-meter will start to flash. Within 5 sec press again the button to confirm the days-meter reset.
ATTENTION
: Do not replace the lamp with powered panel!
Press and hold for more than 9 seconds the
(
◄
┘
)
button to silence the alarm for 7 days (max 4 times).
Working days count down
Alarm + Buzzer
Remaining working days of the
lamp. Keep pressed for less than
5 sec. (◄┘).
The value of the days-meter will
start to flash. Within 5 sec press
again the button to confirm the
days-meter reset.
N.B.
if within 5 sec it is not
"confirmed", the days-meter
comes back to the current
counting value
Reamining lifespan of the lamp
(restarted)
365
113
AL2
AL2
113
Press and Hold > 9 sec.
(
◄
┘
)
To stop the buzzer
Fix AL2 alarm, cut power
and give power again
Alarm AL2
Event