  Memory Map for Discrete input

C/A2 Control output status (0 = OFF  ,1 = ON)

A1 Output status  (0 = OFF , 1 = ON ) 

SSR Output status  (0 = OFF  ,1 = ON)

Digital input status (0 = OFF  ,1 = ON)

Parameter

Number

      

Data

Type

Paramet

er Description

Read

 /

 Write

Permission

ENDA ET4430 PID 

TEMPERATURE

 CONTROLLER

 

    MODBUS PROTOCOL ADDRESS MAP

2

. MODBUS ERROR MESSAGES

Modbus protocol has two types error, communication error and operating error. Reason of the communication error is 
data corruption in transmission. Parity and CRC control should be done to prevent communication error. Receiver side 
checks parity and CRC of the data. If they are wrong, the message will be ignored. If format of the data is true but 
function doesn’t perform for any reason, operating error occurs. Slave realizes error and sends error message. Most 
significant bit of function is changed '1' to indicate error in error message by slave. Error code is sent in data section. 
Master realizes error type via this message.

Error Code

Description

Name

ILLEGAL

 

FUNCTION

ILLEGAL DATA ADDRESS

ILLEGAL DATA VALUE

01 

02

03

The function code received in the query is not an allowable action for the slave. If a 
Poll Program Complete command was issued, this code indicates that no program 
function preceded it.

The data address received in the query is not an allowable address for the slave.

A value contained in the query data field is not an allowable value for the slave.

Device Address

Function Code

Beginning address 
of coils. 

Number of coils (N)  

CRC DATA   

MSB 

LSB 

MSB 

LSB 

LSB  

MSB 

Structure of command message (Byte Format) 

(0A)h 

(01)h 

(04)h 

(A1)h 

(00)h 

(01)h 

(AC)h 

(63)h 

Device Address

Function Code

CRC DATA   

LSB

MSB 

Structure of response message (Byte Format) 

(0A)h 

(81)h 

(02)h 

(B0)h 

(53)h 

    Error Code

Message sample ;

As you see in command message, coil information of   (4A1)h = 1185 is required but there isn’t any coil with 1185 address. 

Therefore error code with number (02) (

Illegal Data  Address

) sends.

ModBus Error Codes

* MODBUS CONNECTION DIAGRAM

1

2

0

 O

h

m

120 Ohm

Master

Slave - 1

Up to 127 slave devices 
can be controlled.

Slave - 2

Slave - 127

A

B

A

B

A

B

A

B

Termination  should  be  accomplished  by 
attaching  120  Ohm  resistors  to  the  start 
and at the end of the communication line.

*  Applies to devices with Modbus function.

SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş.

Şerifali Mah. 

 Y.Dudullu  34775

ÜMRANİYE/İSTANBUL-TURKEY
Tel : +90 216 499 46 64 Pbx.    Fax : +90 216 365 74 01
url : www.enda.com.tr

Barbaros Cad. No:18

 

3

/

3

ET4430-Modbus-EN-01-190116

ENDA

TM

Содержание ENDA ET4430

Страница 1: ...screw terminal connections 1 5mm EN 61326 1 2013 Performance criterion B satisfied for EN 61000 4 3 standard EEPROM minimum 10 years Max 100 Ohm EN 61010 1 2010 Pollution degree 2 overvoltage category...

Страница 2: ...pplement to cables Connect the thermocouple cables to the right places at the input terminal For resistance PT100 Sensor In order to using 2 wire resistance sensors PT100 8th and 9th terminals must be...

Страница 3: ...ent Alarm A1 tp indE Deviation Alarm A1 tp dE Band Alarm A1 tp bAnd SV CONT output set value ASV Alarm output set value ASV min 300 ASV maks 300 ASV min beginning of scale ASV max end of scale ASV min...

Страница 4: ...m bAnd Band alarm bAn i Band with inhibition A2s t Status selection for Alarm2 Output If Hi is selected A2 output is above the Alarm2 set value ON If lo is selected A2 Output is above the Alarm2 set v...

Страница 5: ...rm 2 Band alarm 3 Active alarm after in band time ModBus device address Adjustable between 1 and 247 Modbus communication speed Baudrate 0 Modbus cancel 1 2400 bps 2 4800 bps 3 9600 bps 4 19200 bps 5...

Страница 6: ...d 002Dh 0047d 002Fh 0048d 0030h 0049d 0031h 0050d 0032h 0051d 0033h 0052d 0034h 0041d 0029h 0042d 002Ah H41 H43 H44 H45 H47 H46 H48 H49 H50 H51 H52 H40 H42 R W R W R W R W R W R W R W R W R W R W R W...

Страница 7: ...the query is not an allowable action for the slave If a Poll Program Complete command was issued this code indicates that no program function preceded it The data address received in the query is not...

Отзывы: