sisel ENDA ET4430 Скачать руководство пользователя страница 6

Word

0000d  (0000h)

I0

Word

000

1

 

(000

1

h)

I1

Word

000

2

d  (000

2

h)

I2

I3

Word

000

3

d  (000

3

h)

Word

000

4

d  (000

4

h)

I4

Word

000

5

d  (000

5

h)

I5

000

6

d  (000

6

h)

I6

Word

R

R

R

R

R

R

R

1.3  Memory Map for Input  Registers

Parameter

Number

      

Input

 Register 

A

dres

s

De

c

imal    (Hex)      

Data

Type

Paramet

er Description

Read

 /

 Write

Permission

Measured temperature

Analog output percentage

Measurement error codes
0 = No error, 1 = Sensor short circuit, 2 = Lower scale error,
3 = Upper scale error, 4 = Sensor connection lost, 5 = Wrong input selection.

Self tune condition codes
0 = No error, 1 = 

Initial temperature is higher than 60% setpoint value

2 = 

Calculating PID parameters

, 3 = 

Calculating power set parameters

Current (active) temperature setpoint

.

Current (active) decimal point value

 (0 = 

No decimal point

, 1 = 0.0 

Decimal point is tenths

Reserved

C0
C1
C2
C3
C4
C5
C6

C7

C8

C9

Bit

Bit

Bit

Bit

Bit

Bit

Bit

Bit

Bit

Bit

(0000)h

(0001)h

(0002)h

(0003)h

(0004)h

(0005)h

(000

6

)h

(000

7

)h

(000

8

)h

(000

9

)h

Coil 

Address

1

0

1

0

0

0

0

0

0

0

Paramet

er Description

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

A2.st.

A2.Er.

A1.St.

A1.Er.

C.tyP.

unit

C.E.c.t.

----
----
----

1.2  Memory Map for Coils

Parameter

Number

      

Data

Type

Default

Value

Parame

ter

Name

Read

 /

 Write

Permission

Alarm2 

condition

 (0 = A

ctive

  Low  ,1 =

Active

  High)

Alarm2 condition selection on probe failure

 (0 = 

Off

 , 1 = 

On

 ) 

 

Control output configuration

  ( 0 = 

Heat

 ; 1 = 

Cool 

)

Temperature unit

     (0 = °C ; 1 = °F) 

Control outputs active

 (0 = Control outputs active

, 1 = 

Only display mode

)

 

Controlling according to 2nd temperature setpoint

 (

If 

C7 = 0

 

 

is  

H0, 

 if 

C7 = 1 

is

 H1) 

 

Auto/Manual selection (0 = 

Automatic "Running mode"

,

 

1 = Manual "Running mode". 

In this mode, 

output generated according to H39 parameter.)

Control procedure in case of probe failure

 (0 = H10 

proportional control according to percentage value

,

1 = 

Error found before the setpoint control is done with the value of the proportional control

Alarm

1

 condition (0 = A

ctive

  Low  ,1 =

Active

  High)

Alarm1 condition selection on probe failure

 (0 = 

Off

 , 1 = 

On

 ) 

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

0

0

1

1

1

1

1

00

40

d   (00

28

h)

00

43

d   (00

2B

h)

00

44

d   (00

2C

h)

00

46

d   (00

2E

h)

00

45

d   (00

2D

h)

00

47

d   (00

2F

h)

00

48

d   (00

30

h)

00

49

d   (00

31

h)

00

50

d   (00

32

h)

00

51

d   (00

33

h)

00

52

d   (00

34

h)

00

41

d   (00

29

h)

00

42

d   (00

2A

h)

H41

H43

H44
H45

H47

H46

H48

H49

H50

H51

H52

H40

H42

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

d.in.C.

F.kE.C.

Co.Sc.

A.1.Sc.

A.2.Sc.

Cn.Sc.

S.t..Sc.

Word

10

00

53

d   (00

35

h)

H53

R/W

ENDA ET4430 PID 

TEMPERATURE

 CONTROLLER

 

    MODBUS PROTOCOL ADDRESS MAP

1.1 Memory Map for Holding Registers (continue)

Digital input control parameter ( 0 = Digital input off, 1 = 2nd set value can be selected by digital input,

2 = Manual mode can be entered via digital input, 3 = Can be switched to display mode via digital input)

Control output menu, security parameter ( 0 = Menu invisible,

1 = Menu programmable, 2 = Menu only visible )

Alarm1 output menu security parameter ( 0 = Menu invisible,

1 = Menu programmable, 2 = Menu only visible )

Alarm2 output menu, security parameter

 

( 0 = Menu invisible,

1 = Menu programmable, 2 = Menu only visible )

Function key control parameter ( 0 = Function key off, 1 = 2nd Set value can be selected by function key,
2 = Manual mode can be entered by using function key, 3 = Can be switched to display mode by using function key)

Configuration menu, security parameter

 

( 0 = Menu invisible,

1 = Menu programmable, 2 = Menu only visible )
Self tune menu, security parameter

 

( 0 = Menu invisible,

1 = Self tune can be done)

d.lth

Display Brightness (can be adjusted between 1 and 20)

C

o

n

fi

g

u

ra

ti

o

n

 P

a

ra

m

e

te

rs

S

e

c

u

ri

ty

 P

a

ra

m

e

te

rs

Holding Register 

A

dres

s

De

c

imal    (Hex)      

Parameter

Number

      

Data

Type

Default

Value

Parame

ter

Name

Read

 /

 Write

Permission

1

.

4

  Memory Map for Software Revision Input Registers

Software 

Revision

61472d  (F020h)

14 

Word

Software name and update is read in ASCII format and as 14 word.

Memory Formats 

For example 

: ET4430-01       03 Feb 201

7

:

 

NOTE :
To view each word correctly by changing the byte sequences should be displayed as ASCII TEXT

 

Word

1

T E

 

Word

2

4 4

 

Word

3

0 3

 

Word

4

0 -

 

Word

5

1

 

Word

6

 

Word

7

 

Word

8

 

Word

9

3 0

 

Word

10

F

 

Word

11

b e

 

Word

12

2

 

Word

13

1 0

 

Word

14

. 7

R

SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş.

Şerifali Mah. 

 Y.Dudullu  34775

ÜMRANİYE/İSTANBUL-TURKEY
Tel : +90 216 499 46 64 Pbx.    Fax : +90 216 365 74 01
url : www.enda.com.tr

Barbaros Cad. No:18

 

2

/

3

Paramet

er Description

Reserverd

----

----

Reserverd

Reserverd

Reserverd

Reserverd

Reserverd

----

----

----

----

----

----

----

----

----

----

ET4430-Modbus-EN-01-190116

ENDA

TM

Содержание ENDA ET4430

Страница 1: ...screw terminal connections 1 5mm EN 61326 1 2013 Performance criterion B satisfied for EN 61000 4 3 standard EEPROM minimum 10 years Max 100 Ohm EN 61010 1 2010 Pollution degree 2 overvoltage category...

Страница 2: ...pplement to cables Connect the thermocouple cables to the right places at the input terminal For resistance PT100 Sensor In order to using 2 wire resistance sensors PT100 8th and 9th terminals must be...

Страница 3: ...ent Alarm A1 tp indE Deviation Alarm A1 tp dE Band Alarm A1 tp bAnd SV CONT output set value ASV Alarm output set value ASV min 300 ASV maks 300 ASV min beginning of scale ASV max end of scale ASV min...

Страница 4: ...m bAnd Band alarm bAn i Band with inhibition A2s t Status selection for Alarm2 Output If Hi is selected A2 output is above the Alarm2 set value ON If lo is selected A2 Output is above the Alarm2 set v...

Страница 5: ...rm 2 Band alarm 3 Active alarm after in band time ModBus device address Adjustable between 1 and 247 Modbus communication speed Baudrate 0 Modbus cancel 1 2400 bps 2 4800 bps 3 9600 bps 4 19200 bps 5...

Страница 6: ...d 002Dh 0047d 002Fh 0048d 0030h 0049d 0031h 0050d 0032h 0051d 0033h 0052d 0034h 0041d 0029h 0042d 002Ah H41 H43 H44 H45 H47 H46 H48 H49 H50 H51 H52 H40 H42 R W R W R W R W R W R W R W R W R W R W R W...

Страница 7: ...the query is not an allowable action for the slave If a Poll Program Complete command was issued this code indicates that no program function preceded it The data address received in the query is not...

Отзывы: