sisel ENDA ET4430 Скачать руководство пользователя страница 4

 pfa
 400

 400

____
 400

----

No communication with sensor.

(Sensor and/or cable broken or 

not connected)

ERROR MESSAGES

Temperature value is higher 

than scale.

Temperature value is lower 

than scale.

C h a n g e s   t o   t h i s  
parameter  may  cause 
s o m e   p a r a m e t e r  
values to change.

inp.t.

  =  Input Type selection. 

 

Pt.0

    

=

  PT100 - Decimal, 

Pt.

       

=

  PT100   Non-decimal, 

J.0

       

=

  J  Type - Decimal, 

j

          

=

  J  Non-decimal,  

k.0

       

=

  K  Type - Decimal, 

k

          

=

  K  Non-decimal, 

L.0

       

=

  L  Type - Decimal, 

L

          

=

  L  Non-decimal, 

t.0

       

=

  T  Type - Decimal,

Input Type Selection Chart

t

          

=

  T  Type, 

s

          

=

  S  Type , 

r

          =  

R  Type

C.s.Lo.
 -30

C.s.Hi.
 600 

C. pb
  4.0 

C. ti
  4.0 

C. td
 1.00

C.P.St.
   0

C.Hys
   2

C. Ct.
   1

C.typ
HEAt

s.s.t.s.
   0

C.E.p.s.
   0

C.EC.t.
 E.PS.

Con.o.

Co.sc.
p.yEs

a.1..sc.
p.yEs

a.2.sc.
p.yEs

Cn.sC.
p.yEs

S.t.sc.
p.yEs

inp.t.
   J

Unit
  °C

fltr.
  20

C.o.sE
C-A2

offs.
   0

d.Adr.
   1

baud
 9.60

d.in.C.
nonE

F.kE.C.
nonE

A2.S.L
 -30

A2.S.H
 600

A2.HY
   2

A2.tP
INDE.

A2.St.
  hi.

A2.Er.
  ON

S.Cod.
   0

s.t.us.
  

Pid.t.
  

25

s.tun.

s.t.us.
  

Al1.o.

Al2.o.

Conf..

s.tun.

SECU.

 4/4

A

A1

A2

A1

A2

A3

B

B3

B3

B2

A1.S.L
 -30

A1.S.H
 600

A1.HY
   2

A1.tP.
INDE.

A1.St.
  Hi.

A1.Er.
  ON

A1.PB
  0.0

A1.ti
  0.0

A1.td
   0

A1.Ct
  1

A1.ps
   0

A1.Ep
   0

B1

B1

B2

B3

B3

B1

B2

B3

C

D

D1

D1

D1

D2

E

F

A2

A2

A2

A2

A3

If 

co.SE

 parameter is 

different from 

C-A2

 , this 

menu can be displayed in 
SSR Out devices.

Alternatively, by pressing              key "Running Mode" is entered and by pressing  both               

   

keys at once, settings automatically 

saved and device returns to the "Running Mode" (to the home screen).

During in "Programming Mode", if no key is pressed for 20 sec, settings automatically saved and device returns to the "Running Mode" (to the home 

screen). 

RUNNING MODE

d.lth
  10

400
  

25

If          key is pressed while holding         key, the "Programming Mode" is entered.

ENTERING TO PROGRAMMING MODE

C.s.lo. 

=  Lower  limit  for  C/A1 

Output control, setpoint value. 

 

Can  be  adjusted  between

0

  and 

C.s.Hi.

C.s.Hi. 

=    Upper  limit  for  C/A1 

Output Control, setpoint value.

Can be adjusted between 

C.s.Lo.

 and 

Upper scale value. 

C. Pb

   = 

 

P

roportional band value

 

for C/A1 Output

.

Can  be  a

djust

ed

  between 

0

.0

%

 

and 

100

.0.% 

 

If   

C.Pb

   parameter set to 

0.0%

, On-Off control will be accepted.

C.Hys

 = H

ysteresis 

value for C/A1 

O

utput

.

Can  be  a

djust

ed  between

  between

 

1

 and 

 

50 °C.

°C

C. ti

    =   

Integral 

value  for  C/A1 

Output

.

Can  be  adjusted  between  0.0  and 
100.0 minutes. If   

C. ti

   parameter 

set to 

0.0

, integral will be disabled.

C.  td

  = 

C

/A1  Output 

Derivative 

value

.

Asjustable  between 

0.00

  and   

25.00

 

minutes.

 If   

C. td

 

 parameter set to 

0.0

 , derivative will be disabled.

C. Ct.

 = 

C/

A1 Output periodic time 

duration.

Adjustable  between 

1

  and 

 

250

 

seconds.

C.p.st

  = 

C/

A2  output  power 

percentage at  C/A1 set value.

Can  be  adjusted  be

tween 

0%

  and 

100%

.

C.E.C,t.

 = Control type selection for 

sensor failures.

If 

E.PS

  selected,  controlling  will  be 

performed  to  according  to 

C.E.P.S.

 

proportional control parameter.
If 

Auto

 is selected, controlling will be 

performed to last recorded set value 
percentage before probe failure.

C.E.P.s

.

  = 

C/

A1  Output  power 

percent selection on probe failure.

Can  be  adjusted  between   

%0

  and 

%100

.

  If 

C.Pb

  set  to 

0.0

  (On/Off 

Control) and 

C.E.P.S.

 set to 

0

 , output 

will be OFF, on failure. If 

C.E.P.S.

 set to 

different value from 

0

 , output will be 

ON, in case of failure.

S.S.t.S.

 = Soft start timer set value.

This parameter determines how many 
minutes will be reached to the setpoint 
value on power-up.
Can be adjusted between 0 and 250 
minutes.  If  set  to  0,  the  soft  start 
feature  will  be  canceled  and  the 
setpoint  value  will  be  reached 
maximum speed.

C.typ.

  =  Output  controlling  type 

selection

HEAt.

  =

 

Heating  control  can  be 

performed.

CooL

  =

 

Cooling  control  can  be 

performed.

a1.s.l

  = 

Can  be  adjusted  between 

and

 

Alarm1  set  value  lower 

limit.

 

A1.S.H

parameter value.

a1.s.H

 

=  Alarm1  set  value  upper 

limit.

Can be adjusted between 

A1.S,L

 and 

upper scale value.

a1.Hy

  =  Hysteresis  of  the  Alarm2 

output.

Can be adjusted between 1 and 50°C.

A1.tp

 

 =  Alarm1 

types

.

Six alarm types can be selected.

 

indE.

  =

 Independent

 alarm

dE.

        =

 Deviation 

alarm

bAnd

   =

 Band alarm

bAn.i

   =

 Band with inhibition 

in.Co. 

rE.Co

    =

 

A1  output  independent 

cooling control

A1  output  relative  cooling 

control

A1s

. t.

 

 

 

Status  selection  for 

Alarm1 Output

If  

Hi

 is selected,  A1 output is above 

the Alarm1 set value ; ON. If   

lo

   is 

selected,    A1  Output  is  above  the 
Alarm1 set value ; OFF.

A1.Er.

    =    Alarm1  condition 

selection on probe failure

on

         

A1 

Output is ON, in case of 

probe failure.

off

   = 

A1 Output is OFF, in case of 

probe failure.

A1.Pb

   =   A1 Output, proportional 

band value.

Can  be  adjusted  between 

0

%

 

and

 

100

%.

If  

A1.Pb

 

 Parameter set to  %0, On-

Off

 control will be accepted.

A1.ti

  =  

If   

A1.ti

  parameter  set  to  0.0, 

integral will be disabled.

A1 Output, integral value.

Can  be  adjusted  between  0.0  and 
100.0 minute.

A1.td

 

 

=

 

 

Can  be  adjusted  between  0.00  and 
25.00 minutes.

If   

A1.td

   

parameter  set  to  0.00, 

devirative will be disabled.

A1  output  derivative 

value.

A1.Ct

  =  

Can be adjusted between 

and

 250

 

seconds

.

A1 Output Period Time.

A 1 . P S

  =   A 1   o u t p u t   p o w e r  

percentage at A1 set value.

Can  be  adjusted  be

tween  0%

  and 

100%.

A1.EP

.

 = A1 Output power percent 

selection on probe failure.

Can  be  adjusted  between   

0

%

  and 

100

%

.

 

a2.s.l

 = 

Can be adjusted between 

and

 

Alarm2 set value lower 

limit.

 

A2.S.H

parameter value.

a2.s.H

 

= Alarm2 set value upper 

limit.

Can be adjusted between 

A2.S,L

 

and upper scale value.

a2.Hy

 = Hysteresis of the Alarm2 

output.

Can be adjusted between 1 and 50 

A2.tp

 

 =  Alarm

2

 

types

.

Four alarm types can be selected.

 

indE.

  =

 Independent

 alarm

dE.

        =

 Deviation 

alarm

bAnd

   =

 Band alarm

bAn.i 

Band with inhibition

A2s

. t.

 

 

 

Status selection for 

Alarm2 Output

If  

Hi

 is selected,  A2 output is 

above the Alarm2 set value ; ON. If  

lo

  is selected,  A2 Output is above 

the Alarm2 set value ; OFF.

A2.Er.

  =  Alarm2 condition 

selection on probe failure

on

     

A

2

 

Output is ON, in case of 

probe failure.

off

  = 

A2 Output is OFF, in case 

of probe failure.

inp.t.

 =  Input Type Selection.

             

Please see 

“Input Type      

                 Selection Table” 

for details at 

the right side  of this page.

Unit

  =

   Temperature   

                Unit Selection.

   

°C

 = °C   /  

°F

 = °F 

fLtr.

 = Coefficient of Digital Filter.

Provides to filter for displayed value.
Adjustable  between  1  and  200.  If  this 
parameter  set  to  1,  digital  filter  runs 
quickly. If the parameter is set to 200, 
filter runs slowly. This parameter value 
shouldbe  increased  in  interference 
environments. 

C.o.sE

  = 

C-A2

=

 

SSR

=

 

Control output selection.

 

C/A2 (Relay) output 

selection.

 

SSR output selection.

oFFS.

  =  

The  offset  value  is  added  to  the 
measurement  value.  This  feature  is 
used to eliminate errors that may occur 
due to the distance from the measuring 
probe to the measuring point.
Can  be  adjusted  between    -99  and 
100°C. Default value is 0.

Offset Value.

D.aDr.

 =RS485 Connection Address.

Can be adjusted between 1 and 247.

baud

 

=

 

Can be adjusted to off, 2.40, 4.80, 
9.60, 19.20 and 38.40.

ModBus Baud Rate for 

RS485

d.in.C.

    =  Digital  input  setting 

parameter.

nonE

    =

 Digital input is closed.

C2.S.A.

 =

 if digital input is activated, 2nd 

set value is used.

manu.

   =

 Manual mode start in case of 

digital  outputs  are  active  and  rational 
output  generated  according  to  period 
v a l u e   i n

 

C . C t

  p a r e m e t e r   a n d  

percentage value in 

m.SEt

parameter.

dSP.o.

  =

 If the digital input is activated, 

only temperature value will be indicated.

F.kE.C.

=

 

  Function  key  setting 

parameter.

nonE 

  =

  Function key is OFF.

C2.S.A. 

 =

 2nd. set value can be used 

by using function key.

manu.

  =

  Manual  mode  can  be 

accessed by using function key.

dSP.o.

  =

  Temperature  value  will  be 

indicated by using function key.

d

.

lth

 

 = Display Brightness

Can be adjusted between 1 and 20.

s.t.us.

  =  Self tune Control Parameter.

If                     keys are pressed together, main 
screen displayed and if the temperature is not 

high, 

pid.t.

 message flashes on display and 

the self tune process starts automatically. If the 
initial  temperature  is  higher  to  self-tune, 

tE.hi

. message appears and waits until the 

temperature  goes  down.  Then 

Pid.t.

 

message  appears  and  self  tune  procedure 
starts  automatically.  After  the  self  tune 

procedure, 

C.Pb

 , 

Ct

 , 

C.dt

 and 

C.Ct.

 values 

are  stored  in  memory  and  "Running  mode" 
(main screen) is entered.  After the successful 

self  tune  completion, 

S.tun.

  menu  will  be 

removed  automatically.  In  order  to  re-tune, 

s.t.sc.

 parameter should be set to 

p.yEs

 in 

SECU

 menu.

STOPPING SELF TUNE

When the self-tune operation needs to be 

terminated,

“Programming  Mode"

 

should be entered by using              keys 

and 

S.tun

 menu should be selected. 

By  using      key, 

S.t.uS

  parameter  is 

selected  and  self-tune  process  can  be 

terminated by pressing with together        
                  keys.

Cosc.

 = 

CoN.o
nonE

 

 

=

 

P.yEs

 

 =

 

P. no

 

 

=

 

Security Access Level for 

 Parameter.

Menu invisible.

Modification can be done.
Only visible.

a.1.sc.

 = Security Access Level for 

al1.o.

 Parameter.

nonE

 =

 

P.yEs

 =

 

P. no

 =

 Only visible.

Menu invisible.

Modification can be done.

a.2.sc.

 = Security Access Level for 

al2..o.

 Parameter.

nonE

 =

 

P.yEs

 =

 

P. no

 =

 Only visible.

Menu invisible.

Modification can be done.

Cn.sC.

 = Security Access Level for 

Conf.

 Parameter.

nonE

 =

 

P.yEs

 =

 

P. no

 =

 Only visible.

Pno

   =

 Menu visible only.

Menu invisible.

Modification can be done.

S.t.Sc..

 = Security Access Level for 

S.tun...

 Parameter.

nonE

 =

 

P.yEs

 =

 

Menu invisible.

Modification can be done.

S.Cod

 = Security menu access code.

To accessing security menu, 

430

 should 

be entered.

While 

  code 

0

 

(

,  by 

held down the        key and by pressing       

key  for  4  seconds, 

  message 

appears and default mode is entered.

S.Cod

S.Cod 

=

 0

  )

dEfP

A1.td
   0

I n f o r m a t i o n   t r a c k i n g  
m e t h o d   a b o u t   t h e  
parameters is as follows.

A B C D

A1

A2

A3

On  the  device  screens 
shown on this page ;
-  First  line  indicates  the 
parameter name,
-  Second line indicates the 
current parameter's value.
 At the same time, the value 
shown in the second line is 
the  default  value  of  the 
device.

Parameter name.

Parameter  value 
(default value).

ANNOTATIONS

Changes  to  this  parameter  may  cause 
some parameter values to change.

This  parameter  availble  in 
RS485-Modbus devices only.

Please  see  ET4430  Modbus 
Address  Map  and  Connection 
Diagram  Guide  for  Modbus 
feature.

C.HyS.

        6

C.HyS.

       5

C.HyS.

      6

 

C.HyS.

      6

 

If     

 

key is pressed and held 0.6 seconds, the value of the

 

selected

 

parameter changes rapidly. If   waited enough, the value increases 

 

100 at each step. After 1 second following the release of the key, 

 

 

initial condition   is returned. The same procedure is valid for the

 

 

 

decrement key.

When holding        key, selected parameter flashes and desired 

value can be adjusted by using               keys.

Parameter Setting Diagram

A1t.P

inC.o.

  or 

rEC.o.

  

 Parameter can not be displayed 

if

is selected.

A1t.P

inC.o.

  or 

rEC.o.

  

 Parameter will be activated 

if

is selected.

This parameter will be activated if the  

A1.tp

 parameter set to

 in.Co.

  or  

rE.Co.

  and if the 

A1.Pb

 parameter is 

different from “0”

This  parameter  will  be  activated  if  the 

C.Pb

 parameter set to  “0”.

This  parameter  will  be  activated  if  the 

C.Pb

 parameter different from “0”.

This  parameter  will  be  activated  if 
the 

C.Pb

  parameter  set  to  “0”  or 

C.E.Ct

 set to 

E.P.S.

ET4430-EN-01-190116

ENDA ET4430 PROGRAMMING DIAGRAM

SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş.

Şerifali Mah. 

 Y.Dudullu  34775

ÜMRANİYE/İSTANBUL-TURKEY
Tel : +90 216 499 46 64 Pbx.    Fax : +90 216 365 74 01
url : www.enda.com.tr

Barbaros Cad. No:18

D2

D2

Содержание ENDA ET4430

Страница 1: ...screw terminal connections 1 5mm EN 61326 1 2013 Performance criterion B satisfied for EN 61000 4 3 standard EEPROM minimum 10 years Max 100 Ohm EN 61010 1 2010 Pollution degree 2 overvoltage category...

Страница 2: ...pplement to cables Connect the thermocouple cables to the right places at the input terminal For resistance PT100 Sensor In order to using 2 wire resistance sensors PT100 8th and 9th terminals must be...

Страница 3: ...ent Alarm A1 tp indE Deviation Alarm A1 tp dE Band Alarm A1 tp bAnd SV CONT output set value ASV Alarm output set value ASV min 300 ASV maks 300 ASV min beginning of scale ASV max end of scale ASV min...

Страница 4: ...m bAnd Band alarm bAn i Band with inhibition A2s t Status selection for Alarm2 Output If Hi is selected A2 output is above the Alarm2 set value ON If lo is selected A2 Output is above the Alarm2 set v...

Страница 5: ...rm 2 Band alarm 3 Active alarm after in band time ModBus device address Adjustable between 1 and 247 Modbus communication speed Baudrate 0 Modbus cancel 1 2400 bps 2 4800 bps 3 9600 bps 4 19200 bps 5...

Страница 6: ...d 002Dh 0047d 002Fh 0048d 0030h 0049d 0031h 0050d 0032h 0051d 0033h 0052d 0034h 0041d 0029h 0042d 002Ah H41 H43 H44 H45 H47 H46 H48 H49 H50 H51 H52 H40 H42 R W R W R W R W R W R W R W R W R W R W R W...

Страница 7: ...the query is not an allowable action for the slave If a Poll Program Complete command was issued this code indicates that no program function preceded it The data address received in the query is not...

Отзывы: