The following procedure shall be adhered to:
• remove
refrigerant.
•
purge the circuit with inert gas.
• Evacuate
vacuum.
•
purge with inert gas.
•
open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders.
For appliances containing
fl
ammable refrigerants the system shall be purged
with oxygen-free nitrogen to render the appliance safe for
fl
ammable refriger-
ants. This process may need to be repeated several times. Compressed air or
oxygen shall not be used for purging refrigerant systems.
For appliances containing
fl
ammable refrigerants, refrigerants purging shall be
achieved by breaking the vacuum in the system with oxygen-free nitrogen and
continuing to
fi
ll until the working pressure is achieved, then venting to atmos-
phere, and
fi
nally pulling down to a vacuum. This process shall be repeated
until no refrigerant is within the system. When the
fi
nal oxygen-free nitrogen
charge is used, the system shall be vented down to atmospheric pressure to
enable work to take place. This operation is absolutely vital if brazing opera-
tions on the pipe-work are to take place.
Ensure that the outlet for the vacuum pump is not close to any potential ignition
sources and that ventilation is available.
16. Charging procedures
In addition to conventional charging procedures, the following requirements
shall be followed.
•
Ensure that contamination of different refrigerants does not occur when
using charging equipment. Hoses or lines shall be as short as possible to
minimize the amount of refrigerant contained in them.
•
Cylinders shall be kept in an appropriate position according to the instruc-
tions.
•
Ensure that the refrigerating system is earthed prior to charging the sys-
tem with refrigerant.
•
Label the system when charging is complete (if not already).
•
Extreme care shall be taken not to over
fi
ll the refrigerating system.
Prior to recharging the system, it shall be pressure-tested with the appropriate
purging gas. The system shall be leak-tested on completion of charging but
prior to commissioning. A follow up leak test shall be carried out prior to leav-
ing the site.
Содержание Dry Up SDHM-20L ECO
Страница 1: ...SDHM 20L ECO DRY UP Dehumidifier GB INSTRUCTION MANUAL GR R290...
Страница 2: ...GB ENGLISH 3 GR E 30...
Страница 30: ...30 T R290 R290 ODP GWP R290 R290...
Страница 31: ...31 R290 4 m2...
Страница 32: ...32...
Страница 33: ...33 SINGER...
Страница 34: ...34...
Страница 35: ...35 1 service 2 SINGER SINGER SINGER...
Страница 36: ...36 3 Singer 4 24...
Страница 37: ...37 3 1...
Страница 39: ...39 POWER POWER TIMER POWE R HUMIDITY LOCK 3 SEC MODE 3 SEC TIMER POWE R HUMIDITY LOCK MODE 3 SEC 3 SEC...
Страница 40: ...40 LOCK LOCK 2 LOCK 2 MODE MODE AUTO Auto 50 Humidity 5 High Speed 5 Low Speed 5 HIGH DEHUMIDIFYING MODE...
Страница 41: ...41 LOW DEHUMIDIFYING ECONOMY mode MODE FAN ONLY MODE HUMIDITY INTERNAL DRYING MODE 2 MODE 2 Drying Power...
Страница 43: ...43 LED AUTO Auto Humidity AUTO...
Страница 44: ...44 1 2 Power 3 4 Auto 50 5 Mode 6 Humidity 7 Timer 8 Mode Drying 9 Lock LED...
Страница 45: ...45 5 3 15...
Страница 46: ...46 12 mm 2...
Страница 47: ...47 1 2 3 4 Drying 40 C 3 1 3...
Страница 48: ...48 2 C 2 C 30...
Страница 49: ...49 drying 30 R290 0 236ohm 0 236 ohm...
Страница 50: ...50 100m3 h...
Страница 51: ...51 1 2 3 4...
Страница 52: ...52 5 6 7 8...
Страница 53: ...53 9...
Страница 54: ...54 10 11...
Страница 55: ...55 12 13 14 25 OFN...
Страница 56: ...56 15 16...
Страница 57: ...57 17 H...
Страница 58: ...58 80 18 19...
Страница 59: ...59...
Страница 60: ...60 SSM EMC Directive 2014 30 EU LVC Low Voltage Directive 2014 35 EU ROHS Directive 2011 65 EU...
Страница 61: ...61 NOTES...
Страница 62: ...62 NOTES...
Страница 63: ...63 NOTES...