EM330D User Manual
A Special Purpose Inverter for Hoisting
78
No.
Function
Range
Unit
Default
Type
F3-30
Open Loop Slip Compensation
0.00
~
200.00
%
100.00
●
The speed of motor rotor decreases as load increases. In order to ensure that the speed of
rotor is close to synchronous speed, motor could start slip frequency when motor is on rated
load. When the speed of motor is far lower than the objective value, increase the setting
value of F3-30.
★
F3-30
=
0 Slip compensation is disabled.
No.
Function
Range
Unit
Default
Type
F3-31
Parameter Copy
0: No Copy
1:Upload Parameter (From Inverter to Keypad)
2:Download Parameter (From Keypad to
Inverter, F3-31=0 upon completion)
0
〇
F3-31=0
No copy.
F3-31=1
Upload the parameters from the control panel of inverter to the EEPROM on
keypad. Upon the completion of uploading, F3-31=0 set automatically.
F3-31=2
Download the parameters from the EEPROM on keypad to the control panel of
inverter. Upon the completion of downloading, F3-31=0 set automatically.
The function may be applied to the setting parameter copy between different
inverters, and to save the initial parameters defined by user. When the parameters
are edited by mistake, the inverter cannot work normally, please download the
parameter to reset
User Parameters.
7.5
Group F4: Application Marcos and Display Options
No.
Function
Range
Unit
Default
Type
F4-15
Monitor
Reference
Selection
*
Iq
Est.Slip
Est.
Speed
*
Sync-
Freq.
Inp.
Freq.
Outp.
Freq.
11111111
〇
1
1
1
1
1
1
1
1
0: Absolute Value
,
1: +/- *: Not used
Bit setting value=0
Monitoring frequency shows absolute value when motor
forwards/reverses.
Bit setting value=1
Monitoring frequency shows positive/negative value when motor
forwards/ reverses.
F4-15 is bit operation, only setting corresponding bit of monitoring frequency = 0 or 1. For
instance: when motor forwards/reverses, the monitoring output frequency and estimated
slip frequency shows positive/negative value respectively, but monitoring the other
frequency shows absolute value, only set the 0
th
bit=1 (corresponding to the output
frequency) and the 5
th
bit=1 (corresponding to the estimated slip), and set other bits = 0, i.e.
F4-15=XX10X001.