IDNAC SLC Operation Advantage (Cont’d)
Reducing Installation and Testing Time.
With
separate controls on the same two-wire SLC, installation
time and expense for both retrofit and new construction
can be significantly reduced. When Class B wiring is
used,
wiring can be “T” tapped
, allowing more savings in
distance, wire, conduit (size and utilization), and overall
installation efficiency. Use of the magnet test feature
improves installation efficiency. TrueAlert device reports
conveniently identify information about each connected
appliance.
TrueAlert Addressable Wiring Isolator
Isolator Model
4905-9929
is available for remote
mounting on TrueAlert addressable circuits to isolate
short circuited wiring from functioning wiring. (Refer to
data sheet S4905-0001 for additional information.)
TrueAlert Addressable Diagnostics
Test Features.
Controllers can be selected to pulse each
appliance’s LED when it receives a supervision poll.
When the controller is selected for diagnostic mode, the
appliance magnet test feature provides a response at the
individual appliance being tested.
Silent Appliance Magnet Test.
In this test mode, in
response to the magnet test, the appliance LED pulses
sequentially to conveniently indicate the appliance’s
address.
Operational Appliance Testing.
In this test mode,
after the address is indicated by pulsing the appliance
LED, the strobe will briefly flash to indicate proper
operation.
TrueStart Instrument Two (TSIT).
The 2nd
generation of the Simplex TrueStart Test Instrument adds
testing of IDNAC SLC wiring and TrueAlert (and
TrueAlert ES) appliances to its ability to test IDCs,
NACs, and IDNet communications
before
connection to
the control panel
. Please contact your local Simplex
representative for additional information.
2
S4906-0004-3 5/2013
Multi-Candela Ceiling Mount Addressable Strobe
Model
Housing
Color
“FIRE” Lettering
Dimensions
Description
4906-9202 Red
White
4 ¾” x 2
5
⁄
16
” x 2
⅝
” D
(121 mm x 75 mm x 67 mm)
Multi-Candela Addressable Strobe;
intensity selectable as: 15, 30, 75, or
110 candela
4906-9204 White
Red
V/O Adapters
(see diagram on page 3)
Model
Description
Dimensions
4905-9910
Ceiling Mount, Surface Mount Adapter Plate, zinc plated;
required for
ceiling surface mount
4
⅞
” x 3
⅛
” (124 mm x 79 mm)
Wire Guards
(see diagram on page 3)
Model
Description
Dimensions
4905-9926*
Ceiling Mount Red wire guard with mounting plate, compatible with
semi-flush or surface mounted boxes
6
⅛
” x 4
⅜
” x 2
⅞
”
(156 mm x 111 mm x 73 mm)
* UL listed by Space Age Electronics Inc.
Service Port
Page 1
REPORT 5 : TrueAlert Device Report
12:34:56am MON 20-May-13
POINT ID
CUSTOM LABEL
DEVICE
TYPE
CANDELA
T14-1-1
Location Label . . . up to 40 characters
V/O
15
T14-1-2
Break Room 5
A/V
110
T14-1-3 Boiler
Room
A/V
75
T14-1-4
Elec. Room 7
A/V
30
Product Selection
TrueAlert Device Reports Reference