background image

 

 

S4906-0004-3  5/2013

15

110 75 30

F

ACP

Strobe intensity viewing slot
Intensity selection plug, 
accessible only from rear of lens 
housing; factory setting is FACP, 
controlled by panel

4905-9910 Adapter Plate, required for surface 
mount with handy box unless using the 4905-9926 
wire guard

Handy box, 1-1/2" ( 38 mm) deep (RACO 650 or 
equal) or single gang box, 2-1/2" (64 mm) deep 
(RACO 519 or equal) supplied by others

Also can be attached to boxes mounted to drop 
ceiling T-bar with clips (ERICO No. 512 or equal)

Ceiling mount strobe

Optional 4905-9926 wire 
guard with mounting plate

Magnetic 

test location

Bottom view

LED indicator

Address setting DIPswitch is behind strobe 

assembly, select address and strobe 

candela setting before inserting into housing

Single gang box (Wiremold V5744S) 

2-1/4" (57 mm) deep, supplied by others

 

 

Compatible Controller 

Data Sheet 

Reference 

Controller Output 

Available Strobe 

Intensity 

Appliance Voltage 

Minimum  

4100ES or 4100U with TrueAlert Power Supply 

S4100-0031 

TrueAlert 

Addressable SLC 

15, 30, 75, and 

110 cd 

17 VRMS 

4009 TPS, Remote TrueAlert Power Supply 

S4100-0037 

TrueAlert Addressable Controller (4009T) 

S4009-0003 

Electrical Ratings Difference for Retrofit Applications 

Voltage Range  17 VRMS to 31 VRMS, Special Application 

Candela Setting 

15 cd 

30 cd 

75 cd 

110 cd 

17 VRMS

 Current Ratings, use when connected 

to TrueAlert Addressable SLCs per above 

76 mA 

128 mA 

242 mA 

328 mA 

General Specifications

 

(see page 2 for dimensions)

 

Environmental 

32° to 122° F (0° to 50° C); 10% to 93%, non-condensing at 100° F (38° C) 

Connections 

Terminal blocks for 18 AWG to 12 AWG (0.82 mm

2

 to 3.31 mm

2

); two wires per 

terminal for in/out wiring 

Installation Instructions 

579-808 

Strobe Specifications 

Typical Operating Voltage Range 

23 VRMS to 31 VRMS, Special Application (see below for 17 VRMS rating) 

Supervisory Requirements 

1 unit load 

Flash Rate and Synchronized SLC Loading 

1 Hz; with up to 46 synchronized strobes maximum per NAC; maximum 30 

 

resistance between appliances 

Candela Setting 

15 cd 

30 cd 

75 cd 

110 cd 

23 VRMS

 Current Ratings, for connection to 

IDNAC Addressable SLCs 

60 mA

 

92 mA

 

180 mA

 

240 mA

 

Compatible Controller 

Data Sheet 

Reference 

Controller 

Output 

IDNAC SLC  

Output Voltage  

Appliance Voltage 

Design Reference 

4100ES with EPS+ or EPS Power Supply 

S4100-0100 

IDNAC SLC 

29 VRMS 

(regulated) 

23 VRMS 

(with 6 VRMS drop)

4009 IDNAC Repeater 

S4009-0004 

 Ceiling Mount V/O and Guard Installation Reference 

 TrueAlert Strobe LEGACY Compatibility Reference 

 Specifications

 

 

 TrueAlert Strobe and IDNAC SLC Controller Compatibility Reference 

Содержание TrueAlert 4906-9202

Страница 1: ...nt of Buildings MEA35 93E Additional listings may be applicable contact your local Simplex product supplier for the latest status Listings and approvals under Simplex Time Recorder Co are the property of Tyco Safety Products Westminster Ceiling Mount Addressable V Os Description Multi Candela TrueAlert addressable strobes provide convenient installation to standard electrical boxes The strobe is i...

Страница 2: ...after the address is indicated by pulsing the appliance LED the strobe will briefly flash to indicate proper operation TrueStart Instrument Two TSIT The 2nd generation of the Simplex TrueStart Test Instrument adds testing of IDNAC SLC wiring and TrueAlert and TrueAlert ES appliances to its ability to test IDCs NACs and IDNet communications before connection to the control panel Please contact your...

Страница 3: ...e for Retrofit Applications Voltage Range 17 VRMS to 31 VRMS Special Application Candela Setting 15 cd 30 cd 75 cd 110 cd 17 VRMS Current Ratings use when connected to TrueAlert Addressable SLCs per above 76 mA 128 mA 242 mA 328 mA General Specifications see page 2 for dimensions Environmental 32 to 122 F 0 to 50 C 10 to 93 non condensing at 100 F 38 C Connections Terminal blocks for 18 AWG to 12 ...

Страница 4: ...aling Code are registered trademarks of the National Fire Protection Association NFPA Tyco Fire Protection Products Westminster MA 01441 0001 USA S4906 0004 3 5 2013 www simplexgrinnell com 2013 Tyco Fire Protection Products All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice ...

Отзывы: