Page 3
579-1019 Rev M
4009 IDNAC Repeater Installation Instructions
Mounting
The 4009 IDNAC Repeater card arrives pre-installed in a stand-alone cabinet. The cabinet measures W 16.5 inches x H 13.75 inches x D 4.5 inches. It is
available in red, and platinum.
Preparing the cabinet
To prepare the Repeater cabinet for mounting, do the following:
1. Carefully remove the Repeater cabinet and contents from the shipping box and lay the cabinet on a flat and solid surface.
2. Prepare the cabinet in order to be able to safely pierce the conduit/service entrances required.
a. Disconnect the AC harness.
b. Use a screw driver to loosen the 4 screws retaining the Repeater assembly.
c. Set the Repeater assembly aside in a safe dry place.
3. Pierce the required conduit and service entrances. It is recommended that the conduit entrance for the AC power be placed at the bottom right
side of the cabinet.
4. Return the Repeater assembly to the cabinet and tighten the hardware.
5. Reconnect the AC harness.
Mounting the repeater
Danger - High Electrocution Risk.
Do not remove the protective casings that are pre-installed on the card. They cover
High Voltage zones that present a high electrocution risk.
To mount the Repeater, complete the following steps:
1. Locate the place the Repeater will be installed. To do this, consult the following guidelines:
1. - There must be a clear space of at least 1000 mm in front of the Repeater to provide access for maintenance and testing.
- The top of the cabinet must not be more than 2400 mm above the finished floor level.
- The Repeater must be located in an area that is compatible with it’s operation conditions.
2. Using the Repeater as a template, mark the wall through the tear drop knock out at the top of the Repeater cabinet and through the two holes at
the base of the cabinet.
3. Pierce the four holes.
4. Insert the appropriate hardware, into the top two holes, leaving a 1/8 inch (3.175 mm) gap between the screw head and the wall.
5. Align the tear drop hole in the back of the Repeater with the protruding screws.
6. Hang the repeater on the protruding screws.
7. Insert the appropriate hardware into the two holes at the base of the Repeater.
8. Install the batteries, see Installing the batteries for instructions.
Adaptor Card
Optional Class A
Protective
Casing
Batteries
4009 IDNAC
Repeater Card
AC Harness
Insert Hardware
100%