background image

Page 2

579-1019 Rev M

4009 IDNAC Repeater Installation Instructions

Card layout and Specifications

Card layout

2 3

1

7

6

5

4

8

IDNAC OUT

+

+

  SHLD

-

-

IDNAC IN

AUX  OUTPUT

+

+

  SHLD

- -

+

-

TB1

+

-

TB2

AC POWER

BATTERY INPUT

TRBL A

TRBL B
TRBL C

COMM

TRBL D

IDNAC In AUX Output

IDNAC Out

Battery 

Input

Block

Address 

Wiring 

Mode 

LEDs

Jumpers 

Class A 

Adapter

Connectors

AC Connector

Fuse

Trouble

Scroll

Switch

Low Battery 

Disconnect

Jumper

J4

IDNAC IN line

termination Jumper

100%

Fig 2: Card Layout

Card specifications

Table 1: Card specifications

Operating conditions

32°F - 120°F (0°C-49°C)
Up to 93% relative humidity at 90°F (32°C), non-condensing

120 V, 50/60 HZ, 2.5 A

AC Input specifications

240 V, 50 HZ, 1.25 A
Standby: 70 mA plus 0.8 mA for an IDNAC device plus Aux Output current

DC Input specifications

(battery standby)

Alarm: 96 mA plus 1.37XSLC Load Current plus 1.37 X Aux Output Current. (4.5A maximum

with 3A IDNAC SLC load and 200mA Aux Output load)

IDNAC Input specification

1 address, 4 unit loads
Voltage: 29 V special application

IDNAC Output specification

Power: 3 A max.
Voltage: 29V DC Nominal with AC present or when powered from batteries with system

in Alarm or 24 V DC nominal when powered from batteries with system in Standby

mode. Special Application. Aux Loads include 4603-9101 Annunciator, 4100-96xx series

Annunciators, and 4090 series of IDNet ZAMs and IAMs

Electrical specifications

Aux Output specification

Power: 0.2 A max. @ 29 V

Earth fault

Earth fault detection is 10 k minimum to any circuit
Charges up to 25 Ah sealed lead-acid batteries connected to the power supply
High Voltage Internal battery charger Output: 27.6 V

Internal battery charger

Output Current Limit: 1.3 A

Содержание TrueAlert 4009 Series

Страница 1: ...Handle as follows Ground yourself before opening or installing components Prior to installation keep components wrapped in anti static material at all times SULFURIC ACID WARNING Battery contains sulfuric acid which can cause severe burns to the skin and eyes and can destroy fabric Replace any leaking or damaged battery while wearing appropriate protective gear If you come in contact with sulfuric...

Страница 2: ...s Aux Output current DC Input specifications battery standby Alarm 96 mA plus 1 37XSLC Load Current plus 1 37 X Aux Output Current 4 5A maximum with 3A IDNAC SLC load and 200mA Aux Output load IDNAC Input specification 1 address 4 unit loads Voltage 29 V special application IDNAC Output specification Power 3 A max Voltage 29V DC Nominal with AC present or when powered from batteries with system in...

Страница 3: ...e installed on the card They cover High Voltage zones that present a high electrocution risk To mount the Repeater complete the following steps 1 Locate the place the Repeater will be installed To do this consult the following guidelines 1 There must be a clear space of at least 1000 mm in front of the Repeater to provide access for maintenance and testing The top of the cabinet must not be more t...

Страница 4: ...ce both batteries to the left side on the bottom of the cabinet 2 Connect the positive terminal of the left battery to the positive battery input on the Repeater using the red cable 3 Connect the negative terminal of the right battery to the negative battery input on the Repeater using the black cable 4 Connect the two remaining battery terminals using the white jumper cable to join the two batter...

Страница 5: ...e off the cover 3 Bring the AC wiring in through the conduit entrance on the lower right side of the Repeater cabinet 4 Connect building AC to the terminal block The ground wire can be secured under the AC cover screws 5 Place the AC cover back over the terminal block and tighten the screws 1 2 Ground 100 Fig 5 Connecting the Repeater to the AC NOTE Wire the Non Power Limited wiring only in the sh...

Страница 6: ...7 53 6 22 38 54 7 23 39 55 8 24 40 56 9 25 41 57 10 26 42 58 11 27 43 59 12 28 44 60 13 29 45 61 14 30 46 62 15 31 47 63 DIP SWITCHES 5 THROUGH 7 100 Fig 7 Card addresses Battery Disconnect Jumper Use Jumper J3 to select Low Battery operation The Jumper operates as follows Jumper in the right position pins 2 3 causes panel shutdown when the batteries are depleted Jumper in the left position pins 1...

Страница 7: ...g T Tap connectors an SLC can support up to five wiring branches that each include a Repeater NOTE The Repeater does not increase the maximum number of devices supported on the IDNAC channel The total number of devices on a channel includes all devices present before and after the repeaters General wiring guidelines Ensure conductors test free of all grounds All wiring must be done using copper co...

Страница 8: ...he wire once though the ferrite bead close to the Repeater field wiring terminals for lowest radiated emissions before the wires leave the box Do not loop the ground wire on the AC wiring or the shield wire on shielded cables through the ferrite bead 2 Secure the ferrite bead with the provided cable ties Loop pattern Cable ties Ferrite Bead 100 Fig 11 Ferrite Bead Installation Wiring length tables...

Страница 9: ...t 1982 ft 3152 ft 5 24 55 462 ft 734 ft 1168 ft 1856 ft 2952 ft 4 92 60 434 ft 690 ft 1097 ft 1744 ft 2774 ft 4 75 63 419 ft 665 ft 1058 ft 1682 ft 2675 ft 4 64 65 409 ft 650 ft 1034 ft 1643 ft 2613 ft 4 38 70 386 ft 614 ft 976 ft 1552 ft 2468 ft 4 15 75 366 ft 581 ft 924 ft 1469 ft 2337 ft 3 94 80 347 ft 551 ft 877 ft 1394 ft 2217 ft 3 74 85 330 ft 524 ft 833 ft 1325 ft 2107 ft 3 56 90 314 ft 499...

Страница 10: ... 2726 ft 45 397 ft 631 ft 1002 ft 1593 ft 2534 ft 50 370 ft 588 ft 935 ft 1487 ft 2365 ft 55 347 ft 551 ft 876 ft 1393 ft 2215 ft 60 326 ft 518 ft 823 ft 1308 ft 2081 ft 63 314 ft 500 ft 794 ft 1262 ft 2007 ft 65 307 ft 488 ft 776 ft 1233 ft 1960 ft 70 290 ft 461 ft 733 ft 1165 ft 1852 ft 75 275 ft 436 ft 694 ft 1103 ft 1753 ft 80 261 ft 414 ft 658 ft 1046 ft 1663 ft 85 248 ft 394 ft 626 ft 994 ft...

Страница 11: ...Appliances IDNAC MTAA Appliances IDNAC MTAA Appliances IDNAC MTAA Appliances IDNAC IDNAC OUT IDNAC IN TB1 TB2 IDNAC OUT TB1 Devices Tap 1 Devices Tap 2 Devices Tap 3 Devices Tap 4 EPS T Tapping example Devices 100 Fig 12 Local Class B wiring diagram Local Class A Loop wiring To create a local Class A loop that stems from the Repeater complete the following steps NOTE For all Class A wiring the rep...

Страница 12: ... wiring Testing circuit supervision Use the following procedures to confirm that the IDNAC and Aux Power output are supervising for opens shorts and grounds The right column in this table shows the LEDs that illuminate when an open short or ground occurs on a specific circuit Table 6 Testing circuit supervision Condition Wiring configuration Action Corresponding LEDs Class B circuit Disconnect the...

Страница 13: ... voltage fluctuates with temperature variations At normal room temperature the battery voltage should be 27 27 6 V when the battery set is fully charged At higher temperatures the voltage is lower At lower temperatures the voltage is higher Table on page 13 shows the proper range of battery voltage across the specified operating range of the equipment Table 7 Voltage and temperature Temp F Temp C ...

Страница 14: ... fuse is a fast acting 8 A 32 V fuse and is located in the positive lead of the battery harness AC Input Fuse F1 208 195 The AC Input Fuse is in the line side of the AC input and is a time delay 4 A 250 VAC fuse It is located in the fuse holder FH1 under the High Voltage Cover Shut down AC power and remove the high voltage cover to replace the fuse CAUTION For continued protection against risk of ...

Страница 15: ... the Trouble LED codes Use the Trouble Scroll button see Figure 15 LED and trouble scroll location on page 15 to scroll through multiple troubles Only one trouble is displayed at a time AC POWER TRBL A TRBL B TRBL C TRBL D COMM 2 1 7 6 5 4 3 8 Indicator LEDs Trouble ScrollButton 100 Fig 15 LED and trouble scroll location COMM LED behavior Blinking The COMM LED blinks when communicating with the EP...

Страница 16: ...he front panel If the charger current is approximately 2 A the batteries are likely loading the charger Remove the battery connection and measure the output of the EPS If the output is 27 6 or close temperature dependent there is a possibility the batteries are depleted or are a bad set of batteries Charge the batteries or replace them if they do not take a charge Earth Fault Search This is displa...

Страница 17: ...he card function location or other information Alternate Label Enter an alternative description of the card Current Draw Amps This option specifies the current drawn by the device The current draw is based on the device PID To open the Power table and select the device press the F11 key When the correct device is selected and the quantity entered the correct power rating for this device is display...

Страница 18: ...ion appliances 49VO WRF 49VO WWF 49VO WRA A 49VO WWA A 49VO WRA BA 49VO WRF BA 49VO WRQ BA 49VO APPLC 49VOH APPLCB BA 49VOH APPLCB 49VOH APPLCA BA 49VOH APPLCA 49VOH APPLC BA 49VOH APPLC 49VO APPLC BA 49VO WRS BA 49VO WWA BA 49VO WWF BA 49VO WWS BA 49VO WRA A BA 49VO WWA A BA 49VO WWS A BA 4906 9201 4906 9202 4906 9203 4906 9204 Speaker Visible notification 4906 9251 4906 9253 4906 9254 Audible Vi...

Страница 19: ...le Visible Wall Mount High Candela Weatherproof 59AV APPLWRH O 59AV APPLWWH O Audible Only Wall Mount 59AO WRS 59AO WRS BA 59AO WWS 59AO WWS BA 59AO APPLWR 59AO APPLWW Audible Only Wall Mount Weatherproof 59AO WRSO 59AO WRSO BA 59AO WWSO BA 59AO APPLWR O 59AO APPLWW O Wall Mount Speaker and Speaker Visible and backplate 49SV APPLW BA 49HFV APPLW BA 49MP SVWR 49HF APPLW BA 49SO APPLW BA 49MP SVWW 4...

Страница 20: ...nal listings may be applicable contact your local Simplex product supplier for the latest status Listings and approvals under Simplex Time Recorder Co Simplex and the product names listed in this material are marks and or registered marks Unauthorized use is strictly prohibited NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association NFPA ...

Отзывы: