Simplex Time Recorder Co.

6

S4100-0025 (EN54)  5/99

System Type 

(select 4100 prefix for stand-alone systems, 4120 prefix for networked systems)

4100/4120-

Description

LPC Status

Quantity

Standby

Alarm

Module Size

8001

Basic Fire Control Panel

8010

Miniplex Control Panel

8201

Control Panel with Audio

8210

Miniplex Control Panel with Audio

8019

Miniplex Transponder

(1)

Choose

One

See below

Master Controller Option

4100/4120-

Description

LPC Status

Quantity

Standby

Alarm

Module Size

4100-7014

Standard

(2)

8” Internal

16” Retainer

4120-7014

EN54 Master

Controller

Assembly with

Display

For 4120 Network

N.A.

Choose

One

625 mA

675 mA

10” Internal

16” Retainer

System Requirements

4100/4120-

Description

LPC Status

Quantity

Standby

Alarm

Module Size

6027

CE Mark Option

6081

Version 8 Software

6051

Non Power-limited

(2)

Required

Not applicable

Conventional Zone Circuits

4100/4120-

Description

LPC Status

Quantity

Standby

Alarm

Module Size

5004

8 Zone Class B

(2)

As Required

75 mA

195 mA

2” Internal

Sounder and Speaker Circuits

4100/4120-

Description

LPC Status

Quantity

Standby

Alarm

Module Size

4001

Two Circuit Class B

16 mA

33 mA

4205

Dual Circuit, Triple Channel Class B

25 mA

80 mA

4321

Six Circuit Class B

(2)

As Required

25 mA

70 mA

2” Internal

Auxiliary Relay Control

4100/4120-

Description

LPC Status

Quantity

Standby

Alarm

Module Size

3001

Four Relays, 2A with Feedback

15 mA

75 mA

2” Internal

3002

Four Relays, 10A with Feedback

N.A.

15 mA

175 mA

4” Internal

3003

Eight Relays, 3A with Feedback

(2)

As Required

25 mA

280 mA

2” Internal

Power Supply Options

4100/4120-

Description

LPC Status

Quantity

Standby

Alarm

Module Size

0157

8 A Intelligent Power Supply with
Charger, 230 VAC

––

––

6” Internal

0158

8 A Power Supply, 230 VAC

––

––

0164

Temperature Compensated Battery
Charger, 230 VAC

(2)

As Required

––

––

4” Internal

Interface Options

4100/4120-

Description

LPC Status

Quantity

Standby

Alarm

Module Size

0110

MAPNET II Addressable Zone Module

470 mA

490 mA

4” Internal

0113

Dual RS232 Module

132 mA

132 mA

0304

Remote Unit Interface (RUI)

(2)

As Required

85 mA

85 mA

2” Internal

Audio Controller Board Options

4100/4120-

Description

LPC Status

Quantity

Standby

Alarm

Module Size

0210

Single Channel Operation

185 mA

185 mA

0211

Dual Channel Operation

220 mA

220 mA

0212

Triple Channel Operation

(3)

Choose One as

Required

220 mA

220 mA

12” Internal

(1)

 LPC (Loss Prevention Council) Approval pending for 4100 model series (PIDs) only.   

(2)

 LPC Approval pending.

(3)

 Tested by LPC to verify that no detrimental effect occurred to mandatory EN54 functions.

Module size:

 “Internal” = only occupies space behind retainer panel.

“Retainer” = only occupies space at retainer panel level and internal modules can be located behind.

Module Size Reference:

 Each unit of space has 16” (406 mm) of panel width available.  (8” = 203 mm, 4” = 102 mm, 2” = 51 mm)

 Product Selection 

(LPC approval status designated per model number, see legend below)

Содержание TrueAlarm 4100 Series

Страница 1: ...MAL PRESS RESET KEY SYSTEM FAULT POWER SITE SPECIFIC PROGRAMMABLE KEYS LEDS RESET PANEL SILENCE FIRE ALARM REVIEW ALARMS FAULT REVIEW FAULTS SOUNDER FAULT DISABLED DISABLE ENABLE SOUNDERS SOUNDERS SILENCED DISABLEMENT REVIEW DISABLED ZONES SOUNDER SILENCE RESOUND System is Normal 09 36 24 MON 05 APR 1999 4100 FIRE ALARM CONTROL 4100 4120 Series Control and Indicating Equipment shown as a 6 unit pa...

Страница 2: ...AULTS FAULT DISABLE ENABLE SOUNDERS SOUNDER FAULT DISABLED SOUNDER SILENCE RESOUND SOUNDERS SILENCED REVIEW DISABLED ZONES DISABLEMENT NEXT PREV System is Normal 09 36 24 MON 05 APR 1999 4 X 40 LCD READOUT LED backlighted during normal conditions and abnormal operating conditions provides up to 40 characters for custom label information EXTENDED FUNCTION KEYPAD accessible with door open select and...

Страница 3: ...rammed for temporal code or march time code RS 232 Dual Port Communication Module Up to four additional RS 232 modules total Each port can be vectored by event category Auxiliary Control Relays Built in fuse protection per contact Feedback tracks on off status of remote devices 4100 3001 four CPU controlled relays DPDT contacts rated for 2 A 24 VDC 4100 3002 four CPU controlled relays DPDT contact...

Страница 4: ... to 830 Hz in 2 5 seconds recommended for fire alarm and no other purpose High Low Free running signal with a high frequency of 750 Hz for 100 msec and a low frequency of 500 Hz for 400 msec Horn Continuous 500 Hz tone primarily used for coded systems Chime 600 Hz fundamental tone with a 1 5 sec duration used as a free running tone or for coded operation Beep 500 Hz tone of 0 7 sec on 0 7 sec off ...

Страница 5: ...des routing and pre amplification of digitized alarm tones and voice messages Actual tones and voice messages are digitally recorded and stored in the audio control board s message memory When called upon an integral Voice Tone Generator VTG recreates the audio waveforms of the prerecorded voice tone messages with completely natural sound The Audio Control board receives instructions from the Mast...

Страница 6: ...e 3001 Four Relays 2A with Feedback 15 mA 75 mA 2 Internal 3002 Four Relays 10A with Feedback N A 15 mA 175 mA 4 Internal 3003 Eight Relays 3A with Feedback 2 As Required 25 mA 280 mA 2 Internal Power Supply Options 4100 4120 Description LPC Status Quantity Standby Alarm Module Size 0157 8 A Intelligent Power Supply with Charger 230 VAC 6 Internal 0158 8 A Power Supply 230 VAC 0164 Temperature Com...

Страница 7: ...antity Standby Alarm Module Size 4120 6014 Modular Network Interface Board 35 mA 35 mA 2 Internal 4120 0142 Wired Media Card 40 mA 40 mA 4120 0143 Fiber Optic Media Card N A As Required 25 mA 25 mA N A Cabinets and Accessories 4100 4120 Description LPC Status Quantity Standby Alarm Module Size 2052 Four Unit 2053 Six Unit with Glass Door 2062 Four Unit 2063 Six Unit with Solid Door Choose One Per ...

Страница 8: ... 4 654 mm 6 3 4 171 mm 26 3 8 670 mm 7 3 4 197 mm 3 3 4 95 mm See chart 3 76 mm 2 1 4 57 mm Installation Detail Side View IMPORTANT Distance between close coupled dual cabinets must be no less than 3 inches 76 mm and no more than 24 inches 610 mm Input Power Requirements Mains Input 230 VAC base models 1 A maximum Mains Input with 230 VAC expansion power supply 2 A maximum Mains Input 4100 0263 10...

Отзывы: