Operator Interaction

The illustration below identifies the LCD readout and
the primary operator indicators and switch functions.
When the internal access door is lowered, the additional
keypad shown is available for extended operator
functions. Some of the features include:

 

Bright LED indicators and LCD alphanumeric
information for accurate status presentation

 

Nomenclature that is provided by insert, allowing the
terminology to be revised to suit local language
needs

 

Four site-specific programmable LEDs and switch
keys for use as required by the individual location

 

Typical LCD information is displayed in sequence:

Line 1:

  

First zone in alarm/Menu

Line 2:

  Menu information

Line 3:

  Most recent zone in alarm

Line 4:

  Total event counts

Password Access

Four levels of password protection are available.
Typical access divisions are per the following:

Operation

Level

View software revision, test indicators

Access alarmed zones not shown

Display suppressed faults or disablements

1

Silence local sounder

Reset latching fault conditions

Silence fire alarm sounders

Resound fire alarm sounders

Initiate reset process

Disable/enable points, zones, or outputs

Set time and date, View historical logs

2

Clear historical logs, Manually control points and lists

3

Disconnect or adjust main or standby power

Modify program contents (EXEC)

Alter site-specific data (CFIG)

4

Simplex Time Recorder Co.

2

S4100-0025 (EN54)  5/99

SYSTEM

FAULT

POWER

ZN

1

SIG

2

AUX

3

FB

4

IO

5

MAP

6

P

7

A

8

ZONE

9

NET

-

FUNC

0

DEL

ENTER

CLR

MENU

SITE SPECIFIC PROGRAMMABLE KEYS/LEDS

RESET

PANEL SILENCE

REVIEW

ALARMS

FIRE

ALARM

REVIEW
FAULTS

FAULT

DISABLE/ENABLE

SOUNDERS

SOUNDER

FAULT/DISABLED

SOUNDER

SILENCE/RESOUND

SOUNDERS

SILENCED

REVIEW

DISABLED

ZONES

DISABLEMENT

NEXT

PREV

***   System is Normal   ***

 

09:36:24                                 MON   05-APR-1999

4 X 40 LCD READOUT, LED 

backlighted during

normal conditions and abnormal operating

conditions, provides up to 40 characters for custom

label information

EXTENDED FUNCTION KEYPAD

 (accessible

with door open) select and scroll through display

prompts for locating additional system information,

performing maintenance functions

YELLOW FAULT LED 

flashes

when a new fault event is received,

REVIEW FAULTS KEY 

steps

through fault events

YELLOW DISABLEMENT LED

flashes when a new disablement

event is received, 

REVIEW

DISABLED ZONES KEY

 steps

through disabled zones

YELLOW SOUNDER FAULT LED 

flashes when there is a fault

on a sounder circuit and turns on steady when a sounder circuit

is disabled, 

DISABLE/ENABLE SOUNDERS KEY 

allows all

sounders to be disabled simultaneously

YELLOW SOUNDERS SILENCED LED 

turns

on to indicate that the sounder points have been

turned off,  

SOUNDER SILENCE/RESOUND

KEY 

silences the sounders when on and will

resound them when pressed again

RESET KEY 

initiates system reset process

PANEL SILENCE KEY

 turns off the local sounder

YELLOW SYSTEM FAULT LED

 turns on to indicate a system fault

GREEN POWER LED

 turns on whenever the c.i.e. is powered,

either mains or battery

FOUR PROGRAMMABLE

SWITCHES WITH YELLOW

LEDs

 provide custom operations

labeling (labels insert into a

pocket)

RED FIRE ALARM LED 

flashes when a

new alarm event is received and

 REVIEW

ALARMS KEY  

steps through alarm events

STATUS INDICATOR LEDs 

provide system status indications

in addition to LCD information, LEDs flash to indicate the

condition and change to steady on after one minute

 Operator Control Panel Functions

Содержание TrueAlarm 4100 Series

Страница 1: ...MAL PRESS RESET KEY SYSTEM FAULT POWER SITE SPECIFIC PROGRAMMABLE KEYS LEDS RESET PANEL SILENCE FIRE ALARM REVIEW ALARMS FAULT REVIEW FAULTS SOUNDER FAULT DISABLED DISABLE ENABLE SOUNDERS SOUNDERS SILENCED DISABLEMENT REVIEW DISABLED ZONES SOUNDER SILENCE RESOUND System is Normal 09 36 24 MON 05 APR 1999 4100 FIRE ALARM CONTROL 4100 4120 Series Control and Indicating Equipment shown as a 6 unit pa...

Страница 2: ...AULTS FAULT DISABLE ENABLE SOUNDERS SOUNDER FAULT DISABLED SOUNDER SILENCE RESOUND SOUNDERS SILENCED REVIEW DISABLED ZONES DISABLEMENT NEXT PREV System is Normal 09 36 24 MON 05 APR 1999 4 X 40 LCD READOUT LED backlighted during normal conditions and abnormal operating conditions provides up to 40 characters for custom label information EXTENDED FUNCTION KEYPAD accessible with door open select and...

Страница 3: ...rammed for temporal code or march time code RS 232 Dual Port Communication Module Up to four additional RS 232 modules total Each port can be vectored by event category Auxiliary Control Relays Built in fuse protection per contact Feedback tracks on off status of remote devices 4100 3001 four CPU controlled relays DPDT contacts rated for 2 A 24 VDC 4100 3002 four CPU controlled relays DPDT contact...

Страница 4: ... to 830 Hz in 2 5 seconds recommended for fire alarm and no other purpose High Low Free running signal with a high frequency of 750 Hz for 100 msec and a low frequency of 500 Hz for 400 msec Horn Continuous 500 Hz tone primarily used for coded systems Chime 600 Hz fundamental tone with a 1 5 sec duration used as a free running tone or for coded operation Beep 500 Hz tone of 0 7 sec on 0 7 sec off ...

Страница 5: ...des routing and pre amplification of digitized alarm tones and voice messages Actual tones and voice messages are digitally recorded and stored in the audio control board s message memory When called upon an integral Voice Tone Generator VTG recreates the audio waveforms of the prerecorded voice tone messages with completely natural sound The Audio Control board receives instructions from the Mast...

Страница 6: ...e 3001 Four Relays 2A with Feedback 15 mA 75 mA 2 Internal 3002 Four Relays 10A with Feedback N A 15 mA 175 mA 4 Internal 3003 Eight Relays 3A with Feedback 2 As Required 25 mA 280 mA 2 Internal Power Supply Options 4100 4120 Description LPC Status Quantity Standby Alarm Module Size 0157 8 A Intelligent Power Supply with Charger 230 VAC 6 Internal 0158 8 A Power Supply 230 VAC 0164 Temperature Com...

Страница 7: ...antity Standby Alarm Module Size 4120 6014 Modular Network Interface Board 35 mA 35 mA 2 Internal 4120 0142 Wired Media Card 40 mA 40 mA 4120 0143 Fiber Optic Media Card N A As Required 25 mA 25 mA N A Cabinets and Accessories 4100 4120 Description LPC Status Quantity Standby Alarm Module Size 2052 Four Unit 2053 Six Unit with Glass Door 2062 Four Unit 2063 Six Unit with Solid Door Choose One Per ...

Страница 8: ... 4 654 mm 6 3 4 171 mm 26 3 8 670 mm 7 3 4 197 mm 3 3 4 95 mm See chart 3 76 mm 2 1 4 57 mm Installation Detail Side View IMPORTANT Distance between close coupled dual cabinets must be no less than 3 inches 76 mm and no more than 24 inches 610 mm Input Power Requirements Mains Input 230 VAC base models 1 A maximum Mains Input with 230 VAC expansion power supply 2 A maximum Mains Input 4100 0263 10...

Отзывы: