4

 

 
2.  Using the example given in Step 1 as a guideline, set the duct sensor’s 

address using Figure 3.  Loosen the four screws securing the clear plastic 
cover to the housing base.  Locate the DIP switch on the duct sensor’s PCB 
assembly in the wiring compartment (see Figure 1). Use a small screwdriver 
or pen to set the switches. 

 

3.  Recheck the location of the sensor and its address before electrical 

connection.  Mark an address label with the appropriate address for your 
duct

 

sensor by shading a label box for each sensor DIP switch in the ON 

position.  Then apply the label to the sensor near the sensor’s DIP switch. 

 
4.  Secure the duct sensor’s clear plastic cover to the housing using the four screws 

(Torque screw to 8-10 inch-pounds). 

 

 

Continued on next page 

 

Setting the Duct Sensor’s Address, 

Continued

 

Address Setting for the 4010, 
4020, 4100+, or 4120 

(continued)

 

4020 System 

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

DOCUMENTATION 

      SYSTEM 

POINT 

SUMMARY 

        

Page 

4

 

9304100A 

 node: 

rev: 

             

 

 

 

 

10:50:20, 

 

WED, 

 

15-JAN-97 

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  
System Point Summary (ascending by zone name) :   

 

 

 

 

 

 

 

 

 

 

       Point Summary 

                       

 

 

 

Zone 

 

 

 

 

 

 

 

 

 

 

 

 

 

Device 

 

 

Point   

 

       PNIS 

Zone 

Name 

 Custom 

Label 

       Type 

   Type 

   

 

 

 

 

 

 

Code 

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  
IO1   

 

MULTI  IO  CARD  1  POINT  IO1   

 

 

 

PULL  

 

 

MONA 

IO2   

 

MULTI  IO  CARD  1  POINT  IO2   

 

 

 

PULL  

 

 

MONA 

IO3   

 

MULTI  IO  CARD  1  POINT  IO3   

 

 

 

SSIGNAL   

 

SIGA 

IO4   

 

MULTI  IO  CARD  1  POINT  IO4   

 

 

 

SSIGNAL   

 

SIGA 

M1-1 

  COMPUTER 

 

LAB 

 

BLDG 

 

21 

     VSMOKE 

  ION 

M1-2   

 

3RD  FLOOR  EAST  WING  ROOM  18   

 

 

SMOKE 

 

 

GENIAM 

M2-1   

 

2ND  FLOOR  WEST  WING  ROOM  12   

 

 

SMOKE 

 

 

ADRDET

 

IO9   

 

BASEMENT  EAST  WING  ROOM  3  IO9 

 

 

SFPUMP 

 

 

MONA 

 
 DEVICE 

ADDRESS 

 

4010, 4100+, or 4120 SYSTEM 

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  
DOCUMENTATION 

      SYSTEM 

POINT 

SUMMARY 

        

Page 

2

 

9304100A 

 node: 

rev: 

             

 

 

 

 

16:32:47, 

 

WED, 

 

15-JAN-98 

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  
System Point Summary (ascending by zone name) :   

 

 

 

 

 

 

 

 

 

 

       Point Summary 

                       

 

 

 

Zone 

 

 

 

 

 

 

 

 

 

 

 

 

 

Device 

 

 

Point   

 

       PNIS 

Zone 

Name 

 Custom 

Label 

       Type 

   Type 

   

 

 

 

 

 

 

Code 

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  
M1-1   

 

FIRST  FLOOR  MICROWAVE  ROOM 

 

M1-1   

ADRPUL 

 

 

PULL 

M1-2 

  FIRST 

 

FLOOR 

 

DINING 

 

ROOM 

  M1-2 

 ADRPUL 

  PULL 

M1-3 

  FIRST 

 

FLOOR 

 

LOBBY    M1- 

 ADRPUL 

  PULL 

M1-4   

 

FIRST  FLOOR  MECHANICAL  ROOM  2  

M1-4   

ADRPUL 

 

 

PULL 

M1-5 

  FIRST 

 

FLOOR 

 

LOADING 

 

DOCK 

  M1-5 

 ADRPUL 

  PULL 

M1-6   

 

1ST    FLR    MECH    RM    1 

 

 

 

M1-6   

PHOTO 

 

 

VSMOKE 

M1-7   

 

1ST  FLR  MECH  RM  1 

 

 

 

M1-7   

DUCT 

 

 

PHOTO 

 
 DEVICE 

ADDRESS 

 

Figure 2.  System Point Summaries with MAPNET II/IDNet Address 

Technical Manuals Online! - http://www.tech-man.com

Содержание 4098-9685

Страница 1: ...4098 9685 9686 9688 9755 9756 Duct Detector Sensor Installation Instructions 574 776 Rev C Technical Manuals Online http www tech man com...

Страница 2: ...Blank Page Technical Manuals Online http www tech man com...

Страница 3: ...ES SUCH AS SMOKE DILUTION AND STRATIFICATION OVER WHICH EVEN THE BEST DESIGNED SYSTEMS HAVE NO CONTROL AND PROPER PLACEMENT AND POSITIONING OF THE DUCT SMOKE DETECTOR SENSOR WHICH IS OFTEN COMPROMISED...

Страница 4: ...Blank Page Technical Manuals Online http www tech man com...

Страница 5: ...ng 20 Periodic Air Test 20 Magnetic Test for Detectors and Sensors 21 Preferred Method of Testing Smoke Detectors Sensors 22 DC Operation Detector Sensor Testing 23 Air Differential Pressure Test 24 M...

Страница 6: ...BLANK PAGE Technical Manuals Online http www tech man com...

Страница 7: ...indication red LED ON steady The 4098 9755 and 4098 9756 Duct Sensors have a red LED on the PCB assembly for POWER ON indication red LED flashing or for ALARM or TROUBLE indication red LED ON Steady...

Страница 8: ...ENDED BASE GASKET COVER GASKET HOUSING BASE CAP PLUG SHIP GROUP 748 518 SEE NOTE DIP SWITCH SW2 4098 9755 9756 ONLY Note Two 3 4 conduit entries are provided for field wiring connections 12 18 AWG to...

Страница 9: ...ta for the duct sensor you are installing set the duct sensor s address using Figure 3 Loosen the four screws securing the clear plastic cover to the housing base Locate the DIP switch on the duct sen...

Страница 10: ...97 System Point Summary ascending by zone name Point Summary Zone Device Point PNIS Zone Name Custom Label Type Type Code IO1 MULTI IO CARD 1 POINT IO1 PULL MONA IO2 MULTI IO CARD 1 POINT IO2 PULL MON...

Страница 11: ...216 232 248 1001 9 25 41 57 73 89 105 121 137 153 169 185 201 217 233 249 0101 10 26 42 58 74 90 106 122 138 154 170 186 202 218 234 250 1101 11 27 43 59 75 91 107 123 139 155 171 187 203 219 235 0011...

Страница 12: ...NET II IDNet Input Voltage 24 to 40VDC MAPNET II IDNet Current 400uA Typical 800uA when relay is activated in alarm 24VDC Power Input Voltage 18 to 32VDC Average Supervisory Current 3mA Alarm Current...

Страница 13: ...REMOTE ALARM INDICATOR KEYSWITCH RED ALARM LED TEST SEE NOTES 2 3 4098 9755 2 WIRE DUCT SENSOR RED BLK 1 ON 2 3 4 5 6 7 8 1 LED TB1 SW2 2 3 4 5 6 7 8 TEST MAP MAP Figure 4 4098 9755 Two Wire Duct Sens...

Страница 14: ...PNET II IDNet DEVICES SEE NOTE 2 BLK SHIELD SHIELD SEE NOTE 1 SHIELD OPTIONAL WHT BLUE YELLOW ORANGE C N C N O WHT RED RED RED RED 1 2 W 10K EOL RESISTOR 4081 9008 Figure 5 4098 9756 Four Wire Duct Se...

Страница 15: ...8 9686 Duct Detector Electrical Specifications Four Wire DC Operation with Remote Relay Control Figure 8 Page 14 The 4098 9686 Four Wire Duct Detector has a supervised zone to control up to fifteen 40...

Страница 16: ...0 UT 4004 4005 High Current 4098 9688 not used with 4004 4005 Low Current systems 1 1 1 1 Notes 1 Relay operation cannot be guaranteed unless it is the only device on that zone 2 Panel compatibility i...

Страница 17: ...ivates alarm relay 4098 9756 4098 9688 or 4098 9686 only remote LED and puts the detector sensor into alarm LED Alarm Current 1 2mA Nominal Remote Power Alarm Indicator Key Switch Model 4098 9835 Use...

Страница 18: ...Figure 6 4098 9685 Two Wire Duct Detector DC Operation Continued on next page Notes 1 For Style D initiating device circuit wire per dotted lines and do not use EOL resistor If Style B initiating dev...

Страница 19: ...es 1 For Style D initiating device circuit wire per dotted lines and do not use EOL resistor If Style B initiating circuit refer to drawings provided with the system panel for proper EOL resistor valu...

Страница 20: ...USED SEE NOTE 1 TEST IDC IDC SEE NOTE 5 OPTIONAL 1 2 W 10K EOL RESISTOR 4081 9008 SEE NOTES 3 4 SEE NOTES 3 4 SEE NOTE 4 Notes 1 For Style D initiating device circuit wire per dotted lines and do not...

Страница 21: ...low is non turbulent and that smoke is properly mixed with air in the duct for maximum detector sensor efficiency See Figures 9 and 10 Note Installation of a duct detector sensor to a round duct is th...

Страница 22: ...s in return air ducts ahead of mixing areas 8 Do not locate air duct detectors sensors next to outside air inlets unless you want to monitor smoke entry to the handling system from an adjacent area 9...

Страница 23: ...DIRECTION AIR FLOW DIRECTION 12 THIS END OF INLET TUBE Figure 13 Inlet Tube Orientation Mounting Position 2 See Figure 18 EXHAUST TUBE INLET TUBE RUBBER PLUG INLET TUBE HOLES FACE UPSTREAM OF AIR FLO...

Страница 24: ...ear of the duct housing The inlet tube must be installed through the hole in the housing corner next to the smoke port air flow test holes Place the tube retainer supplied over the inlet tube so that...

Страница 25: ...s Note Only one remote indicator may be connected to each 4098 9685 4098 9686 4098 9688 4098 9755 or 4098 9756 The 2098 9806 2098 9808 4098 9830 4098 9834 and 4098 9835 accessories are intended for in...

Страница 26: ...l operation to sensor by doing a system reset at the panel With the air handling unit turned on and all filters and dampers in place open one of the test port holes Figure 1 by removing one of the red...

Страница 27: ...gure 16 Use the Simplex Magnet Tester Part No 553 810 Table 4 and the following information to test detectors Figure 16 Magnet Test Location Table 4 describes the Detector LED reaction during Normal a...

Страница 28: ...flash the detector does NOT latch into alarm and the LED stops flashing and turns OFF If the detector is out of the normal operating range it should be cleaned If the detector still indicates as other...

Страница 29: ...tion of detector sensor and remote alarm indicator Restore normal operation to detector by doing a system reset at the panel or by momentarily removing power or by removing and replacing the detector...

Страница 30: ...inches 381 mm of water nor greater than 1 55 inches 39 370 mm of water After testing is completed secure the clear plastic cover to the housing using the four screws Torque screws to 8 10 inch pounds...

Страница 31: ...ES ARE 1 1 4 INCH 31 75mm A A POSITION 1 AND 2 TOP DETECTOR PCB DETECTOR PCB DETECTOR PCB DETECTOR PCB POSITION 1 POSITION 3 CUT NOT ALLOWED POSITION 2 BLANK PAGE Figure 18 Duct Detector Sensor Mounti...

Страница 32: ...BLANK PAGE Technical Manuals Online http www tech man com...

Страница 33: ...BLANK PAGE Technical Manuals Online http www tech man com...

Страница 34: ...BLANK PAGE Technical Manuals Online http www tech man com...

Страница 35: ...BLANK PAGE Technical Manuals Online http www tech man com...

Страница 36: ...implex Time Recorder Co Simplex Plaza Westminster Massachusetts 01441 0001 U S A 574 776 Simplex International Time Equipment Co LTD Mississauga Ontario Canada Technical Manuals Online http www tech m...

Отзывы: