14
UL-LISTED
CONTROL PANEL
SIMPLEX 2120, 4001, 4002,
4004, 4005, 4020, 4100+ OR 4120
PRIMARY 1
BACKUP 2
SEE NOTE 2
RESETTABLE
POWER CIRCUIT
24 VDC
INITIATING
DEVICE
CIRCUIT
WHT
BLUE
YELLOW
ORANGE
C
N.C.
N.O.
WHT
4098-9686
4-WIRE DUCT DETECTOR
1
TB1
2
3
4
5
6
7
8
-IDC
SEE NOTE 5
CIRCLE INDICATES WIRE PAIR BUT
MULTICONDUCTOR CABLE MAY BE USED
+24
-24
TEST
SPV
+ZN
-ZN
+A -A
LED
+P -P
LED
+
-
ALM
+24
-24
TEST
SPV
+ZN
-ZN
+A -A
LED
+P -P
LED
+
-
ALM
+24
-24
TEST
SPV
+ZN
-ZN
+A -A
LED
+P -P
LED
+
-
ALM
9
10
11
12
13
14
15
16
17
18
4098-9686
4-WIRE DUCT DETECTOR
1
TB1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
4098-9686
4-WIRE DUCT DETECTOR
1
TB1
2
3
4
5
6
7
8
+
-
9
10
11
12
13
14
15
16
17
18
4098-9843
PAM-SD
RELAY
4098-9843
PAM-SD
RELAY
+
-
+
-
+
-
+
-
WHT
BLUE
YELLOW
ORANGE
C
N.C.
N.O.
WHT
RED
RED
RED
RED
ALARM
LED
BLK
RED
POWER
ON LED
4098-9835
(OPTIONAL SEE ACCESSORIES)
OPTIONAL LED 4098-9830
IS WIRED SAME AS 4098-9834
LESS "TEST" CONNECTIONS
TEST
-
+
ALARM
LED
4098-9834
(OPTIONAL SEE ACCESSORIES)
BLK
RED
EOL RESISTOR
IF USED, SEE
NOTE 1
TEST
+IDC
-IDC
SEE
NOTE 5
OPTIONAL
1/2 W 10K
EOL RESISTOR
4081-9008
SEE
NOTES
3, 4
SEE
NOTES
3, 4
SEE
NOTE 4
Notes:
1.
For Style D initiating device circuit, wire per dotted lines and do not use EOL resistor. If Style B initiating device circuit, refer to
drawings provided with the system panel for proper EOL resistor value.
2.
It is recommended that the primary 1 and backup 2 lines be in separate wire runs and in compliance with local requirements. Duct
Detector wiring is 12 to 18 AWG. For additional wiring information, refer to wiring diagrams supplied with the system panel.
3.
The 4098-9830, 4098-9834, and 4098-9835 are polarized; observe color coded wiring.
4.
Maximum wire length to test terminals and remote LED is 250 feet.
5.
4098-9843 PAM-SD Relay (Air Products & Controls Limited) are rated at 7 amps 28VDC/10 amps @ 115VAC. Maximum wire
length to PAM-SD Relays is 500 feet (Fifteen PAM-SD Relays maximum). Wiring from the relay to the device it is controlling
should be no more than 3 feet (per NFPA 72).
Figure 8. 4098-9686 Four-Wire Duct Detector DC Operation with Remote Relay Control
Continued on next page
Technical Manuals Online! - http://www.tech-man.com
Содержание 4098-9685
Страница 2: ...Blank Page Technical Manuals Online http www tech man com...
Страница 4: ...Blank Page Technical Manuals Online http www tech man com...
Страница 6: ...BLANK PAGE Technical Manuals Online http www tech man com...
Страница 32: ...BLANK PAGE Technical Manuals Online http www tech man com...
Страница 33: ...BLANK PAGE Technical Manuals Online http www tech man com...
Страница 34: ...BLANK PAGE Technical Manuals Online http www tech man com...
Страница 35: ...BLANK PAGE Technical Manuals Online http www tech man com...