Suppression Release Peripheral Application and Installation Instructions
6
Table 5. UL/ ULC Compatible Releasing Devices
MFG
NOTES
ANSUL
AUTOMAN II-C Assembly (uses solenoid 17728; coil 25924)
AUTOMAN II-C Explosion-Proof Releasing Device
(uses solenoid 31492; coil 31438)
AUTOMAN II-C Assembly (uses solenoid 68739; coil 25924)
Solenoid Electric Actuator (uses solenoid 73111; coil 73097)
CV90 HF Electric Actuator 73327 (may use 73606 in-line resistor)
LP CO2 w/ASCO solenoid 422934
LP CO2 double action 24 V solenoid 430948
LP CO2 3-way selector valve solenoid 433419
Electric Actuator
– 24 VDC solenoid 570537
LPG
Solenoid Electric Actuator (uses solenoid: Flow Control 609500/671S)
Solenoid Coupling Assembly 21006401 (uses solenoid: Flow Control 609500/671S)
Solenoid Coupling Assembly 21006402 (uses solenoid: Flow Control 609500/671S)
LPG128/145/190/230-50/55 FM-200 valves (uses solenoid: Flow Control 609500/671S)
LPG128-90UL iFLOW and FM-200 valve (uses solenoid: Flow Control 609500/671S)
ASCO
Model 8210A107 (097617-005D coil) ½ in. NPS, 5/8 in. orifice. 24 VDC
Model 8210G207 (238310 coil) ½ in. NPS, ½ in. orifice.
Model 8211A107 (097617-005D coil) 24 VDC
Model 8262H182
Model EF8210G001MBMO
Model HV2628571 (23810 coil) N.C. ½ in. NPS, ½ in. orifice.
Model HV2648581 (23810 coil) N.O. ½ in. NPS, 1.2 in. orifice.
R8210A107 (097617-005D coil) ½ in. NPS, 5/8 in. orifice.
T8210A107 (097617-005D coil) ½ in. NPS, 5/8 in. orifice.
Hygood
(TSP)
Model 304.205.010
– Electrical Actuator Suppression diode
Model 304.209.001
– Electrical Actuator Bridge Rectifier
PyroChem
ECH Electrical Control Head (551201)
Explosion-Proof Electric Actuator (570147)
Removable Electric Actuator (570209) 0.2 A
Skinner
Model 71395SN2ENJ1NOH111C2 (Skinner coil H111C2) 1/4 in. NPS, 1/16 in.
Model 73212BN4TN00NOC111C2 (Skinner coil C111C2) ½ in., 5-300 psi
Model 73212BN4TNLVNOC322C2 (Skinner coil C322C2) ½ in. NPS, 0.92 A, 250 psi
Model 73218BN4UNLVNOH111C2 (Skinner coil H111C2)
Model 73218BN4UNLVNOC111C2 (Skinner coil C111C2) ½ in. NPW, 5/8 in. orifice.
Burkert
Model 5282 2/2
– Way Solenoid Valve
Minimax
Model MX1230 without diode, 24V DC, ½ in. NPT
Versa
Model CGS-4292-NB3-S20000
Table 6. Battery Calculation Guidelines
Condition
Current
Standby
0 mA*
Alarm
Refer to Table 6 Below
*= The SRP and coil supervision module looks like a 10k EOL resistor, which is
already figured into FACP standby current requirements. No additional standby
calculations are required when connecting an SRP to a FACP.
To use the table, first refer to actuator’s current rating. Then, determine the amount of
alarm current required from the NAC to supply the actuator. Use this figure to determine
alarm current battery requirements. For example, a 1.0 A actuator would require 1.71 A
alarm current from the FACP.
Continued on next page
Wiring Guidelines
(continued)
Standby Battery
Calculations