background image

Suppression Release Peripheral Application and Installation Instructions 

 

2

 

 

 

 

 

Figure 1.  Suppression Release Peripheral 

 

Note:

 

The IDNet channel supports address codes 1 through 250. 

 

Each SRP has a unique address.  The address of the SRP is set with an eight position dip 
switch (Figure 1), DIP switch position 1 is the least significant bit (LSB) and position 8 is 
the most significant bit (MSB). Set the address using Figure 2 as reference. Use a small 
screwdriver or pen to set the switches. Write the

 

device address for the SRP on the re-

sealable label, this information aids in troubleshooting the system. 

 

Note:

 

DIP switch in 

1

 position is 

ON

 while DIP switch in 

0

 position is 

OFF

FigureTag FD9-385-01  

0000 1000 0100 1100 0010 1010 0110 1110 0001 1001 0101 1101 0011 1011 0111 1111

0000

0

16

32

48

64

80

96

112

128

144

160

176

192

208

224

240

1000

1

17

33

49

65

81

97

113

129

145

161

177

193

209

225

241

0100

2

18

34

50

66

82

98

114

130

146

162

178

194

210

226

242

1100

3

19

35

51

67

83

99

115

131

147

163

179

195

211

227

243

0010

4

20

36

52

68

84

100

116

132

148

164

180

196

212

228

244

1010

5

21

37

53

69

85

101

117

133

149

165

181

197

213

229

245

0110

6

22

38

54

70

86

102

118

134

150

166

182

198

214

230

246

1110

7

23

39

55

71

87

103

119

135

151

167

183

199

215

231

247

0001

8

24

40

56

72

88

104

120

136

152

168

184

200

216

232

248

1001

9

25

41

57

73

89

105

121

137

153

169

185

201

217

233

249

0101

10

26

42

58

74

90

106

122

138

154

170

186

202

218

234

250

1101

11

27

43

59

75

91

107

123

139

155

171

187

203

219

235

0011

12

28

44

60

76

92

108

124

140

156

172

188

204

220

236

1011

13

29

45

61

77

93

109

125

141

157

173

189

205

221

237

0111

14

30

46

62

78

94

110

126

142

158

174

190

206

222

238

15

31

47

63

79

95

111

127

143

159

175

191

207

223

239

LSB

MSB

1

2

3

4

5

6

7

8

1111

DIP SWITCHES 5 THRU 8

ON

OFF

1 = ON

0 = OFF

251
252
253
254
255

DIPSWITCH IS SHOWN SET AT ADDRESS 7.

 

 

Figure 2.  Suppression Release Peripheral

 

Address Chart

Introduction 

Setting the SRP 
Address 

ADDRESS SWITCH 

(SW1) 

BRACKET 

ASSEMBLY 

SUPPRESSION 

RELEASE MODULE 

RAC OUTPUT 

(TB2) 

NAC INPUT 

(TB1) 

LED HARNESS 

PLUG (P1) 

IDNet INPUT 

(TB3) 

Содержание 4090-9005

Страница 1: ...E and earlier SRPs sensed only normal 10 k EOL and trouble open circuit conditions and revision F and later SRPs sense normal 10 k EOL trouble open circuits and supervisory 16 2 k disconnect switch c...

Страница 2: ...226 242 1100 3 19 35 51 67 83 99 115 131 147 163 179 195 211 227 243 0010 4 20 36 52 68 84 100 116 132 148 164 180 196 212 228 244 1010 5 21 37 53 69 85 101 117 133 149 165 181 197 213 229 245 0110 6...

Страница 3: ...ur supplied nuts do not over tighten 2 The SRP has an optional communications LED option kit 4090 9812 that mounts to the cover If using the LED option kit remove the plastic snap in plug on the enclo...

Страница 4: ...0 6 V minimum SRP output coil supervision module minimum actuator voltage 21 7 7 20 4 at the rated actuator operating current including the coil supervision module See Table 3 for maximum RAC wiring...

Страница 5: ...on modules Yell Black is not power limited Refer to the 2081 9046 Coil Supervision Module Wiring Instructions 574 437 Connect 24 V DC actuator as shown only one 24 V DC actuator per RAC output Connect...

Страница 6: ...A107 097617 005D coil in NPS 5 8 in orifice T8210A107 097617 005D coil in NPS 5 8 in orifice Hygood TSP Model 304 205 010 Electrical Actuator Suppression diode Model 304 209 001 Electrical Actuator Br...

Страница 7: ...B YEL COIL SUPERVISION MODULE 2081 9046 LOCATED IN VALVE JUNCTION BOX RAC RAC IDNET IDNET TB3 TB1 TB2 RAC RAC TB1 TB3 TB2 IDNET IDNET P1 Red Black P1 Red Black Notes 1 Refer to Table 3 for maximum RA...

Страница 8: ...luding supervision module 0 6 V Drop per Releasing Appliance Circuit RAC Output Interface description is on page 5 and Table 3 RAC wiring is class B only 3 When connecting two IDNet wires to one termi...

Страница 9: ...ort operation by following the programming details in the applicable manual When the abort switch is activated the control panel halts the release or discharge of extinguishing agent Pressing and hold...

Страница 10: ...pliances The RAC is compatible for use with any FM approved electric release deluge pre action and refrigerated area sprinkler solenoid valve rated 22 watts or less Refer to the solenoid valve manufac...

Отзывы: