Suppression Release Peripheral Application and Installation Instructions 

 

9

 

 

For systems intended for Halon 1301 (NFPA 12A), Halon 1211 (NFPA 12B), or clean 
agents (NFPA 2001) release, a pre-discharge NAC must be configured to warn building 
occupants of the impending discharge. Refer to the applicable control panel programming 
manual (574-849 for 4100U/4100ES/4010ES, 579-1167 for 4007ES and 574-052 for 
4010) for programming details. Compliance with ADA requires audible and visible 
notification. 
 
 
Use of abort switches in a pre-action or deluge water type releasing service will void UL 
864 Listing for this product and for the associated fire alarm control panel. 
 
Program an addressable monitor point for abort operation by following the programming 
details in the applicable manual.  When the abort switch is activated, the control panel 
halts the release or discharge of extinguishing agent. Pressing and holding the abort switch 
will prevent agent release/discharge unless the manual release switch is activated.  Manual 
release overrides abort. 
 

 

Activation of a manual release switch is indicated with a programmed red manual release 
LED on the FACP. Upon activation of the manual release switch, the system will activate 
the applicable releasing circuits upon expiration of the manual release timer or upon 
expiration of a previously active automatic release timer if the remaining time on the 
automatic release timer is less than the programmed manual release timer.  

Note:

 Setting the manual release timer to 

zero 

will result  in immediate release. 

 

Suppression 
Release 
Application 
Requirements  

Abort Switches 

Содержание 4090-9005

Страница 1: ...E and earlier SRPs sensed only normal 10 k EOL and trouble open circuit conditions and revision F and later SRPs sense normal 10 k EOL trouble open circuits and supervisory 16 2 k disconnect switch c...

Страница 2: ...226 242 1100 3 19 35 51 67 83 99 115 131 147 163 179 195 211 227 243 0010 4 20 36 52 68 84 100 116 132 148 164 180 196 212 228 244 1010 5 21 37 53 69 85 101 117 133 149 165 181 197 213 229 245 0110 6...

Страница 3: ...ur supplied nuts do not over tighten 2 The SRP has an optional communications LED option kit 4090 9812 that mounts to the cover If using the LED option kit remove the plastic snap in plug on the enclo...

Страница 4: ...0 6 V minimum SRP output coil supervision module minimum actuator voltage 21 7 7 20 4 at the rated actuator operating current including the coil supervision module See Table 3 for maximum RAC wiring...

Страница 5: ...on modules Yell Black is not power limited Refer to the 2081 9046 Coil Supervision Module Wiring Instructions 574 437 Connect 24 V DC actuator as shown only one 24 V DC actuator per RAC output Connect...

Страница 6: ...A107 097617 005D coil in NPS 5 8 in orifice T8210A107 097617 005D coil in NPS 5 8 in orifice Hygood TSP Model 304 205 010 Electrical Actuator Suppression diode Model 304 209 001 Electrical Actuator Br...

Страница 7: ...B YEL COIL SUPERVISION MODULE 2081 9046 LOCATED IN VALVE JUNCTION BOX RAC RAC IDNET IDNET TB3 TB1 TB2 RAC RAC TB1 TB3 TB2 IDNET IDNET P1 Red Black P1 Red Black Notes 1 Refer to Table 3 for maximum RA...

Страница 8: ...luding supervision module 0 6 V Drop per Releasing Appliance Circuit RAC Output Interface description is on page 5 and Table 3 RAC wiring is class B only 3 When connecting two IDNet wires to one termi...

Страница 9: ...ort operation by following the programming details in the applicable manual When the abort switch is activated the control panel halts the release or discharge of extinguishing agent Pressing and hold...

Страница 10: ...pliances The RAC is compatible for use with any FM approved electric release deluge pre action and refrigerated area sprinkler solenoid valve rated 22 watts or less Refer to the solenoid valve manufac...