Setting DIP switch SW1
Dual Inline Package (DIP) Switch SW1 is used to set the BNIC eSlave address as identified in the ES Panel Programmer job. The address is set with the
card in its normal orientation (connectors up) as shown in the mounting instructions (see Figure 6).
Table 2: BNIC DIP switch functions
Switch
Position
Function
Figure
ON
Sets the card to “online” and allows the card to operate
normally.
SW1-1
OFF
Sets the card “offline” which stops all communication to
the FACP.
ON
SW1-2
through SW1-8
OFF
Set the BNIC eSlave address. Refer to Figure 4 for a
complete list of switch settings for all possible card
addresses.
Figure 3: BNIC DIP switch
page 4
579-949 Rev. D
4100-6047 and 4010-9914 Building Network Interface Card Installation and Programming Manual