User manual - METER SRP-147 

Example 3: The linear characteristic

Let the input mode = 4-20 mA, and parameters 

“Lo C”

 and  

“Hi C”

 equal to -300 and 1200 

respectively. The calculations will be done for three different input currents from example 2.

a) I

in

 =10 mA  and  I

n

 = 0,375

Accordingly to expression on page 43 for linear characteristic:
 0,375 × [1200 -(- 300)] 

 562 and next, the 

“Lo C”

  value is added to the result , so the 

displayed value: 

 562 + (-300) = 262

b) I

in

 = 2,5 mA and

  

I

n

 = -0,0938.

 -441.

c) I

in

 = 20,5 mA and

 

I

n

 =  1,0313.

 1247.

Example 4: The square characteristic

Let the input mode = 4-20 mA, and  parameters 

“Lo C”

 and 

“Hi C”

 equal to  -300 and 1200 

respectively. The calculations will be done for there different input currents from example 2.

a) I

in

 =10 mA  and  I

n

 = 0,375

Accordingly to expression on page 43 for square characteristic:  (0,375)

2

 × [1200 -(- 300)] 

≅ 

211.
and next, the 

“Lo C”

  value is added to the result , so the displayed value:

 211 + (-300) = -89

b) I

in

 = 2,5 mA and 

 

I

n

 = -0,0938.

 -287.

c) I

in

 = 20,5 mA and

  

I

n

 =  1,0313.

 1295.

Example 5: The square root characteristic

Let the input mode = 4-20 mA, and  parameters 

“Lo C”

 and 

“Hi C”

 equal to  -300 and 1200 

respectively. The calculations will be done for there different input currents from example 2.

a) I

in

 =10 mA  and  I

n

 = 0,375

Accordingly to expression on page 44 for square root characteristic:   

0,375

× [1200 -(- 300)] 

 919.

and next, the 

“Lo C”

  value is added to the result , so the displayed value: 

 919 + (-300) = 619

b)  I

in

 = 2,5 mA and I

n

 = -0,0938 , normalized result is negative , so the displayed value is equal 

to 

“Lo C” 

parameter:  W 

  

“Lo C”

 = -300.

c) I

in

 = 20,5 mA and I

n

 =  1,0313.

 1223.

47

Содержание SRP-147

Страница 1: ...ETER SRP 147 Input type 0 4 20 mA 0 1 5V 0 2 10V Large 4 x 38 mm display Read the user s manual carefully before starting to use the unit or software Producer reserves the right to implement changes w...

Страница 2: ...e 26 7 3 MENU DESCRIPTION 26 7 3 1 rEL1 menu 27 7 3 2 bEEP menu 29 7 3 3 inPt menu 29 7 3 4 OutP menu 35 7 3 5 bri parameter 36 7 3 6 HOLd menu 37 7 3 7 SECu menu 37 7 3 8 rS menu 38 7 3 9 Edit parame...

Страница 3: ...g to this manual local safety and EMC regulations If the device is equipped with PE connector it should be connected to PE wire Otherwise PE wire should be connected to GND connector The unit must be...

Страница 4: ...0 10 2 10V Current input has additionally overcurrent protection circuit which protects standard resistor The selection of active input is realised by software and selected input can be changed at any...

Страница 5: ...65 typical 55 Accepted prolonged input overload 20 Voltage input 0 5 V 1 5 V 0 10 V 2 10 V Voltage measurement accuracy 0 1 25 C one digit for 0 10 V range Voltage input resistance 50 k Accepted prol...

Страница 6: ...g type Housing material Housing dimensions Mounting hole Assembly depth Panel thickness panel NORYL GFN2S E1 144 x 72 x 100 mm 138 5 x 67 mm 102 mm max 5 mm Operating temperature depending on version...

Страница 7: ...be taken into consideration 4 1 UNPACKING After removing the unit from the protective packaging check for transportation damage Any transportation damage must be immediately reported to the carrier Al...

Страница 8: ...een the centre points of multiple units due to the thermal and mechanical conditions of operation are 163 mm x 91mm Figure 4 3 a b Figure 4 1 Mounting hole dimensions a recommended b allowable 8 138 5...

Страница 9: ...er manual METER SRP 147 Figure 4 2 Installing of brackets and dimensions of connectors Figure 4 3 Minimum distances when assembly of a number of units 9 163 mm 91 mm 82 mm 5 mm 12 mm 10 mm 8 5 mm 16 m...

Страница 10: ...ver tightening can lead to damaging the connections inside the units and breaking the thread In the case of the unit being fitted with separable clamps they should be inserted into appropriate connect...

Страница 11: ...ection between the filter and the unit should be as short as possible and the metal housing of the filter must be connected to the earth with the largest possible surface The cables connected to the f...

Страница 12: ...OC1 optional OC2 optional OC3 optional OC4 optional Power supply depending on version 1 2 11 12 13 14 15 16 17 18 19 3 4 5 6 7 8 9 10 optional R1 optional R2 Uo 24V 5 10 Imax 100mA RS 485 DATA DATA G...

Страница 13: ...ND 0 1 5V 0 2 10V 0 4 20mA n c n c Passive isolated current output 4 20mA optional 1 2 11 12 13 14 15 16 17 18 19 3 4 5 6 7 8 9 10 optional R1 optional R2 Uo 24V 5 10 Imax 100mA RS 485 DATA DATA GND n...

Страница 14: ...14 15 16 17 18 19 15 16 17 18 19 24V DC internally connected 11 12 internally connected 15 16 17 18 19 15 16 17 18 19 24V DC 11 12 1 2 11 12 13 14 15 16 17 18 19 3 4 5 6 7 8 9 10 Uo 24V 5 10 Imax 100m...

Страница 15: ...s coils contactors power relays electromagnets motors etc it is required to use additional suppression circuit typically capacitor 47nF min 250VAC in series with 100R 5W resistor connected in parallel...

Страница 16: ...Examples of suppression circuit connection a to relay terminals b to the inductive load Figure 4 18 Example of OC type outputs connection 16 N 3 4 3 4 L L N 5 6 10 11 voltage input 24 V Logic controll...

Страница 17: ...connection for device with passive current output only Figure 4 21 Example of active voltage outputs connection for device with active voltage output only 17 current input 0 20 mA Logic controller 3 4...

Страница 18: ...arked with this symbol should not be placed in municipal waste Please check local regulations for disposal of electronic products 5 FRONT PANEL DESCRIPTION Symbols and functions of push buttons Symbol...

Страница 19: ...description of Lo r i Hi r parameters paragraph inPt menu Figure 6 2 Definitions of measurement ranges in mode 0 20mA If the measurement value does not exceed permissible measurement range but displa...

Страница 20: ...d menu The detection of the peak can be done if the measured signal raises and drops of value at least equal to parameter PEA Detected peaks are displayed during the time defined by parameter timE If...

Страница 21: ...esholds values If one threshold is used Figure 6 4 the relay can be turned on modE on or off modE oFF when the input signal value is contained in zone A If two thresholds are used Figure 6 5 the relay...

Страница 22: ...ysteresis and threshold hysteresis respectively If t on and toFF parameters are set to 0 then the relay state will be changed as soon as input value exceeds any of the border values see points A and C...

Страница 23: ...connected with relay outputs are described in paragraph rEL1 menu 6 3 2 Two thresholds mode Obja nienie A B C D E points where measured signal exceeds border values expected value allowed deviation BO...

Страница 24: ...lar parameters is described in paragraph MENU DESCRIPTION Some of the parameters can be accessed without menu entering quick view mode After pressing or v button name of the threshold e g rEL1 and his...

Страница 25: ...e of current position flashing digit or the sign Short pressing of the ENTER button causes change of the position digit Press ENTER at least 2 seconds to accept the changes after that question SEt is...

Страница 26: ...change of value acceleration deceleration direction change While editing switch parameter selection of switch parameter If numerical parameter is being edited a short press of ENTER button change edit...

Страница 27: ...or out value Threshold is the medium value of relay hysteresis HYSt hysteresis of relay range 0 999 Full hysteresis of the relay is equal to 2x HYSt parameter The relay state can change when an input...

Страница 28: ...ameter is set by unit parameter toFF turn off delay time the relay is turned off with delay equal toFF if the input value exceeds appropriate border value defined with threshold and hysteresis at leas...

Страница 29: ...n be turned off by pressing of any button 7 3 3 inPt menu This menu presets the measurement input tYPE type of the input sensor This parameter can be set to values 0 20 4 20 current inputs 0 10 2 10 0...

Страница 30: ...h2 t h3 t d the parameters defining shape of cylindrical tank Figure 7 1 and Figure 7 2 a for the cylindrical tank in the vertical position t h1 the height of the bottom part of a tank in the ellipti...

Страница 31: ...t parameters of tank in m unit t Sn parameter takes cm unit respectively see above than displays the result the volume of the tank in m3 unit if we set parameters of tank in cm unit t Sn parameter tak...

Страница 32: ...TER SRP 147 Figure 7 1 Parameters of cylindrical tank in vertical position Figure 7 2 Parameters of cylindrical tank in horizontal position 32 t h1 t h2 t h3 t Sh t Sn h I mA t d t Sh t d t h2 t h1 t...

Страница 33: ...prox 1 5 sec After that device waits for selection of point being deleted by v buttons The short pressing of ENTER button causes by switching between X and Y value of the displayed point The long pres...

Страница 34: ...issible range accordingly to the expression for all modes For example if input is set to 4 20 mode then upper border is calculated due to expression Imax 20 mA 20 mA Hi r The value of Hi r can be set...

Страница 35: ...via RS 485 interface For active voltage output oFF voltage output disabled 0 5 voltage output enabled with 0 5V mode 1 5 voltage output enabled with 1 5V mode 0 10 voltage output enabled with 0 10V mo...

Страница 36: ...on page 50 of the DISPLAY VALUES CALCULATION paragraph the procedure of the analogue outputs determining is presented in details AL this parameter determines the behaviour of analogue output if any cr...

Страница 37: ...uts R1 R4 operation mode rEAL relay LED operates depend on the current value HOLd relay LED operates depend on the peak drop value HOUt current output operation mode rEAL current output operates depen...

Страница 38: ...he device If the delay will be greater than the value of mbtO parameter the relays and analogue outputs which are controlled via RS 485 interface will set to alert state see OUtP menu and rEL1 menu de...

Страница 39: ...e the factory settings of the device To get the access to this option special password is required 5465 next the device displays acknowledge question SEt Press ENTER to acknowledge the restoring of fa...

Страница 40: ...R MENU ESC ENTER MENU ESC rEL3 MENU ESC MENU ESC bEEP MENU ESC inPt MENU ESC AL r1 r2 r3 r4 Parameter edition ENTER MENU ESC ENTER ENTER MENU ESC tYPE CHAr FiLt Pnt Lo C Hi C AddP dELP Parameter editi...

Страница 41: ...meter edition ENTER MENU ESC ENTER ENTER MENU ESC Addr bAud mbAc mbtO rESP Parameter edition ENTER MENU ESC ENTER ENTER MENU ESC Scod A r1 A r2 A r3 A r4 ENTER MENU ESC ENTER ENTER MENU ESC modE PEA t...

Страница 42: ...and units The first step to compute the result of measure is the calculation of the normalized result it means result of 0 1 range To do it the begin of the input range 0 mA for 0 20mA range and 4mA f...

Страница 43: ...r In such a case for an increasing value of input current the displayed value decreases Figure 10 1 Normal Lo C Hi C and inverted Lo C Hi C characteristic 10 1 2 Square characteristic The normalized r...

Страница 44: ...he normalized result In the device computes specific segment e g for characteristic from figure below and In 0 65 the segment between points X 50 0 and X 70 0 will be chosen Let s mark those points as...

Страница 45: ...ut value equal 1 displays value t Sh t Sn Figure 10 5 The linear scaling can be expressed as follow h In t Sh t Sn where h is level of liquids gases or solids in the tank see Figure 7 1 7 2 Figure 10...

Страница 46: ...0 then permissible input currents range will be equal 3 2 mA 22 mA Lower border of the range is the result of calculations 4 mA 4 mA 20 and the higher 20 mA 20 mA 10 Example 2 The normalized In resul...

Страница 47: ...fferent input currents from example 2 a Iin 10 mA and In 0 375 Accordingly to expression on page 43 for square characteristic 0 375 2 1200 300 211 and next the Lo C value is added to the result so the...

Страница 48: ...nd Ip 0 3 the displayed value W In I p Y PH Y PL X PH X PL 100 Y PL 0 375 0 3 80 30 40 30 100 30 67 b Iin 2 5 mA and In 0 0938 because of the normalized In value is lower than 0 the segment defined by...

Страница 49: ...of the cylinder located in horizontal position The tank has dimension height in first part is 2m height in second part is 8 05m diameter 3 26m and length of the sensor 10m The output of signal of the...

Страница 50: ...age 35 Iout 17 5 10 0 20 0 10 0 16 mA 4 mA 0 75 16 4 16 mA Calculated Iout do not exceeds the output working range 3 8 21 mA b D 20 5 According to formula from page 35 Iout 20 5 10 0 20 0 10 0 16 mA 4...

Страница 51: ...0 0 1 0 0 2 0 00 3 0 000 04h Yes see descr State of the relays and alarm LED binary format 1 on 0 off 00000000 000edcba a relay R1 b relay R2 c relay R3 d relay R2 e alarm LED If written only a b c d...

Страница 52: ...1200 baud 1 2400 baud 2 4800 baud 3 9600 baud 4 19200 baud 5 38400 baud 6 57600 baud 7 115200 baud 23h4 Yes 0 1 mbAc parameter in rS menu permission to write registers via RS 485 interface 0 write de...

Страница 53: ...pressed in tenth of seconds or tenth of minutes depend on unit parameter register no 3Dh 3Ch Yes 0 999 toFF parameter in rEL2 menu expressed in tenth of seconds or tenth of minutes depend on unit para...

Страница 54: ...al point included 52h Yes 0 199 timE parameter in HOLd menu maximum peaks or drops display time expressed in seconds 53h Yes 0 1 HdiS parameter in HOLd menu 0 rEAL mode 1 HOLd mode 54h Yes 0 1 H r1 pa...

Страница 55: ...meter in OUtP menu for active and passive current output expressed in 0 1 Yes 0 99 Hi r parameter in OUtP menu for active voltage output expressed in 0 1 A5h1 Yes 0 3 AL parameter in OUtP menu active...

Страница 56: ...EXAMPLES OF QUERY ANSWER FRAMES Examples apply for device with address 1 All values are represent hexadecimal Field description ADDR Device address on modbus network FUNC Function code REG H L Starti...

Страница 57: ...C3 DATA identification code 20F5h 3 Change of the device address from 1 to 2 write to reg 20h ADDR FUNC REG H L DATA H L CRC L H 01 06 00 20 00 02 09 C1 DATA H 0 DATA L new device address 2 The answe...

Страница 58: ...UNT L the count of being read registers max 16 The answer ADDR FUNC BYTE C DATA H1 L1 DATA H2 L2 DATA H3 L3 CRC L H 01 03 06 00 0A 00 00 00 01 78 B4 DATA H1 L1 reg 01h 10 displayed value 1 0 DATA H2 L...

Страница 59: ...ysteresis of relay R2 0 0 27 modE Operation mode of relay R2 on 27 t on Turn on delay of relay R2 0 0 28 toFF Turn off delay of relay R2 0 0 28 unit Unit of t on toFF parameters of relay R2 SEC 28 AL...

Страница 60: ...imal point position 0 0 30 Lo C Minimum displayed value for nominal range 000 0 30 Hi C Maximum displayed value for nominal range 100 0 30 t h1 Height length first part of the tank 00 00 30 t h2 Heigh...

Страница 61: ...e top of the nominal output range 5 0 36 AL Voltage output value on critical exception 11 0 V 36 Display parameters bri Display brightness bri6 36 Configuration of peaks detection function HOLd menu m...

Страница 62: ...ord knowledge on 37 RS 485 interface configuration menu rS Addr Device address 0 38 bAud Baud rate 9 6 38 mbAc Permission to changes of configuration registers on 38 mbtO Maximum delay between receive...

Страница 63: ...User manual METER SRP 147 63...

Страница 64: ...SIMEX Sp z o o ul Wielopole 11 80 556 Gda sk Poland tel 48 58 762 07 77 fax 48 58 762 07 70 http www simex pl e mail info simex pl...

Отзывы: