User manual for flow meter with pulse input SPI-94
Register Write
Range
Register description
35h
Yes
0 ÷ 999
“t on”
parameter in
“rELAy1”
menu, expressed in tenth of seconds
or tenth of minutes depend on
“unit”
parameter
36h
Yes
0 ÷ 999
“t oFF”
parameter in
“rELAy1”
menu, expressed in tenth of seconds
or tenth of minutes depend on
“unit”
parameter
37h
Yes
0 ÷ 1
“unit”
parameter in
“rELAy1”
menu:
0
- seconds;
1
- minutes
38h
Yes
0 ÷ 2
“ALArmS”
parameter in
“rELAy1”
menu:
0
- no changes;
1
- on;
2
- off
39h
3Ah
Yes
Yes
0 ÷ 999999 “
SEt P2
” parameter in “
rELAy1
” menu, no decimal point included
3Bh
Yes
0 ÷ 1
“vALUE”
parameter in
“rELAy1”
menu (kind of value controlled
relay):
0
- “FLo”;
1
- “tot”;
3Ch
Yes
0 ÷ 3
“t PrEc”
parameter in
“rELAy1”
menu (precision of thresholds and
hysteresis while relay is controlled due to total flow counter value):
0
- “ 0”;
1
- “ 0.0”;
2
- “ 0.00”;
3
- “0.000”
3Dh
Yes
0 ÷ 1
“t unit”
parameter in
“rELAy1”
menu (the unit of thresholds and
hysteresis while relay is controlled due to total flow counter value):
0
- lit.;
1
- m
3
;
Parameters or relay R2 operation
40h
41h
Yes
Yes
0 ÷ 999999 “
SEt P
” parameter in “
rELAy2
” menu, no decimal point included
42h
43h
Yes
Yes
0 ÷ 99999
“
HySt
” parameter in “
rELAy2
” menu, no decimal point included
44h
Tak
0 ÷ 5
“
modE
” parameter in “
rELAy2
” menu:
0
- “
noACt
” mode;
1
- “
on
” mode;
2
- “
oFF
” mode;
3
- “
in
” mode;
4
- “
out
” mode;
5
- “
modbuS
” mode
45h
Yes
0 ÷ 999
“t on”
parameter in
“rELAy2”
menu, expressed in tenth of seconds
or tenth of minutes depend on
“unit”
parameter
46h
Yes
0 ÷ 999
“t oFF”
parameter in
“rELAy2”
menu, expressed in tenth of seconds
or tenth of minutes depend on
“unit”
parameter
47h
Yes
0 ÷ 1
“unit”
parameter in
“rELAy2”
menu:
0
- seconds;
1
- minutes
48h
Yes
0 ÷ 2
“ALArmS”
parameter in
“rELAy2”
menu:
0
- no changes;
1
- on;
2
- off
49h
4Ah
Yes
Yes
0 ÷ 999999 “
SEt P2
” parameter in “
rELAy2
” menu, no decimal point included
4Bh
Yes
0 ÷ 1
“vALUE”
parameter in
“rELAy2”
menu (kind of value controlled
relay):
0
- “FLo”;
1
- “tot”;
4Ch
Yes
0 ÷ 3
“t PrEc”
parameter in
“rELAy2”
menu (precision of thresholds and
hysteresis while relay is controlled due to total flow counter value):
0
- “ 0”;
1
- “ 0.0”;
2
- “ 0.00”;
3
- “0.000”
41