User manual for universal counter with batching function SLIK-73
Register Write
Range
Register description
1Ah
6
Yes
see descr.
“oFFSEt”
parameter in
“PrESCA”
menu (high word)
1Bh
6
Yes
see descr.
“oFFSEt”
parameter in
“PrESCA”
menu (low word)
Cumulative value of registers 1Ah and 1Bh: from -99999 to 999999
1Ch
Yes
0÷5
“
Point
” parameter in “
Presca
” menu (decimal point position)
0
- “
0
”;
1
- “
0.0
”;
2
- “
0.00
”;
3
- “
0.000
”;
4
- “
0.0000
”;
5
- “
0.00000
”
20h
3
Yes
0 ÷ 199
Device address
21h
No
20C4h
Device identification code (ID)
22h
4
Yes
0 ÷ 7
“bAud”
parameter in
“rS-485”
menu (baud rate);
0
- 1200 baud;
1
- 2400 baud;
2
- 4800 baud;
3
- 9600 baud;
4
- 19200 baud;
5
- 38400 baud;
6
- 57600 baud;
7
- 115200 baud
23h
5
Yes
0 ÷ 1
“mbAccE”
parameter in
“rS-485”
menu (permission to write registers
via RS-485 interface);
0
- write denied ;
1
- write allowed
24h
Yes
see descr.
Parameters of “
SECU
” menu (binary format (0 - „
oFF
”, 1 - „
on
”):
bit 0
- “
A rEL
” parameter;
bit 4
- “
A oFFS
” parameter
25h
Yes
0 ÷ 5
“rESP”
parameter in
“rS-485”
menu (additional response delay);
0
- no additional delay;
1
- ”
10c
” option;
2
- ”
20c
” option;
3
- ”
50c
” option;
4
- ”
100c
” option;
5
- ”
200c
” option;
27h
Yes
0 ÷ 99
“mbtimE”
parameter in
“rS-485”
menu (maximum delay between
received frames);
0
- no delay checking;
1
÷
99
- maximum delay expressed in seconds
2Dh
Yes
1 ÷ 8
“
briGHt
” parameter (display brightness);
1
- the lowest brightness;
8
- the highest brightness
2Fh
Yes
0 ÷ 1
“
Edit
” parameter (numerical parameters edit mode);
0
- „
dig
” mode;
1
- „
SLid
” mode
30h
6
Yes
see descr.
“SEtP”
parameter in
“rELAy”
menu (high word).
31h
6
Yes
see descr.
“SEtP”
parameter in
“rELAy”
menu (low word).
Cumulative value of registers 30h and 31h: from -99999 to 999999
32h
Yes
0÷3
“
modE
” parameter in “
rELAy
” menu:
0
- “
noAct
” mode;
1
- “
on
” mode;
2
- “
oFF
” mode;
3
- “
modbuS
” mode
33h
Yes
0÷999
“timE”
parameter in
“rELAy”
menu (
the time period of the relay
active state
), expressed in tenth of seconds or tenth of minutes
(depending on
“unit”
parameter);
34h
Yes
0 ÷ 1
“unit”
parameter in
“rELAy”
menu:
0
- “
SEC
” option;
1
- “
min
” option
1
- if overflow or underflow occurs (
“-Hi-”
or
“-Lo-”
), read of registers 01h and 02h (single registers) it returns
recalculated number of pulses ( while the overload of display quantity is very big this value can be erroneous).
Register 03h returns according error code.
2
- Preset of 0000h to these registers ( 04h, 05h, 06h and 07h, ) causes by zeroing of main counter and precounter
content
3
- after writing to register no 20h the device responds with an “old” address in the message.
4
- after writing to register no 22h the device responds with the new baud rate.
5
- the value of the “
mbAccE
” parameter is also connected to write to this register, so it is possible to block a writes,
but impossible to unblock writes via RS-485 interface, The unblocking of the writes is possible from menu level only.
6
- n
umbers written to holding registers of relays thresholds are interrelated with each other auto-correction.
36