User manual - CONTROLLER PUR-49D
Figure 7.4. Change in the fuzzy setpoint depending on the setting of the
SLOP
parameter
7.3.8.
”bri”
parameter
This parameter allows the user to set brightness of the LED display, brightness can be
set to conventional values from 1 to 8.
7.3.9.
”HOLd” menu
This menu contains parameters connected with peak detection function. See also full
description of the peak detection function in paragraph:
DETECTION OF THE PEAK
VALUES
.
“modE”
- the type of detected changes of the input signal, can be set to values:
”norm”
- peaks:
peak and next drop of the input signal of value equal at least
“PEA”
,
”inv”
- drops: drop and next peak of the input signal of value equal at least
“PEA”
,
“PEA”
- minimal detected signal change classified as peak or drop (see
Figure 6.4
),
“timE”
- maximum time of displaying of the peak (drop) value, can be set from 0.0 to 19.9
sec, with 0.1 sec. resolution. If „
HdiS
”=”
HOLD
” then setting parameter
"timE"
=
0.0
causes holding peak value until
[ESC]
button is pressed.
If „
HdiS
”=”
rEAL
” then
value
"timE"
=
0.0
means no holding,
“HdiS”
- type of displayed values.
”rEAL”
- current value is displayed,
”HOLd”
- peak (drop) value is displayed,
48
0
20
40
60
80
100
120
140
0
20
40
60
80
100
120
SLOP = 0
SLOP = 1
SLOP = 5
SLOP = 10
unit
fu
zz
y
va
lu
e