Figure 6.2. Definitions of measurement ranges in mode 0 ÷ 150mV
If the measurement value do not exceeds
permissible measurement range
but
displayed value exceeds range -999 ÷ 9999, the warning ”
-Ov-
” is displayed rather
than the calculated result.
Figure 6.3. Definitions of measurement ranges in mode Pt100
In the measurement mode and PID mode user can check main thresholds values of
relays, the value of the analog output or the set point of the PID controller on the auxillary SV
display (see description of
”diSP” menu
). After pressing
[^]
or
[v]
button, name of the next
parameter (e.g.
”rEL1”
) and then its value will be displayed on the display. If
[^]
or
[v]
will be
pressed in 5 sec again, the next value will be displayed, else the device displays value of
parameter chosen in
”diSP” menu.
If a
free access
is enabled (see description of
”SECu”
menu
), user can change the value of particular parameter by pressing
[ENTER]
button (see:
PARAMETERS EDITION
).
All accessible parameters can be changed by entering the menu (see:
DEVICE
PROGRAMMING
). Use the local keyboard or the remote controller to do it. (Note: all
parameters can be remote changed via RS-485 interface).
Configuration of the device (via menu or RS-485 interface)
does not stop measures
.
6.1.1.
Detection OF THE PEAK VALUES
controller is equipped with peaks detection function. It can detect a peaks
of the input signal and display their values. Presets connected with this function are placed in
”HOLd”
menu (see description of
”HOLd” menu
). The detection of the peak can be done if
the measured signal raises and drops of value at least equal to parameter
”PEA”
. Detected
peaks are displayed during the time defined by parameter
”timE”
. If a new peak will be
detected while one is displayed, this new peak will be displayed and display time counter will
be cleared
(
Figure 6.4
22
i
”
Hi r
” parameter
0 mV
150 mV
permissible measurement range
nominal measurement range
i
permissible measurement range
”-Lo-” message
displayed
”-Hi-” message
displayed
-100°C
+600°C