Installation • Operation 

4

For parts or assistance, call Simer Customer Service at 

800-468-7867

Installation

1.  This unit can be installed in sump pit with 

minimum diameter of 12”(30cm) and depth 

of 12” (30cm). Sump pit may be constructed 

of tile, concrete, steel or plastic. Check local 

codes for approved materials.

2.  Install pump on solid, level foundation, as near 

as possible to center of sump pit. Do not hang 

pump from discharge pipe or power cord.

 

 Risk of burns. Pump must be level 

(column must be vertical) when operating. If 

motor is tilted, internal start/run switch may 

overheat and damage motor.

3.  Pump should not be installed on clay, earth or 

sand surfaces. Clean sump pit of small stones 

and gravel which could clog the pump. Keep 

pump inlet screen clear.

4.  Thread discharge pipe into pump body 

carefully to avoid stripping or crossing threads.

 

NOTICE Do not use ordinary pipe joint 

compound on plastic pipe or pump. Pipe joint 

compound can attack plastics and damage pump.

5.  To reduce motor noise and vibrations, a short 

length of rubber hose (1-5/8”(41mm) I.D., e.g. 

radiator hose) can be connected into discharge 

line near pump using suitable clamps.

  

 Risk of electric shock. Can shock, 

burn or kill. Pump is designed for 115V., 60 

HZ operation and requires an individual branch 

circuit of 15 amperes capacity. It is supplied 

with a 3-wire cord set with grounding-type plug 

for use in a 3-wire, grounded outlet. Do not 

cut off the round grounding prong. For safety, 

outlet must always be electrically grounded to 

a suitable electrical ground such as a grounded 

water pipe or a properly grounded metallic 

raceway or ground wire system.

6.  Locate Float Rod Guide (Key No. 6) about 6” 

(16cm) below motor. Clamp guide to column 

with screw provided.

 

 Risk of flooding. Can cause 

personal injury and/or property damage. Be 

sure that guide is securely clamped so that float 

rod is vertical and can move up and down 

freely. If float is angled or binds, pump may not 

start, allowing flooding to occur.

7.  Screw float onto threaded end of rod. 

Threads on rod will cut threads into corrosion 

resistant afloat.

8.  Insert plain end of float rod up through eye of 

rod guide.

9.  Slide one rod stop on float rod before passing 

rod through eye of pump switch. Slide 2nd rod 

stop on rod after passing through eye of switch. 

Position 2nd rod stop flush with top of rod.

10.  Position lower rod stop to within 8”(20cm) of 

switch lever arm. With lower rod stop in this 

position, pump will automatically cycle at 

approximately 2-1/2”(6cm) off and 10-12”(25-

30cm) on. For faster cycling, move lower rod 

stop closer to switch lever arm.

11.  If pump discharge line is exposed to outside 

subfreezing atmosphere, then portion of 

line exposed must be installed so any water 

remaining in pipe will drain to outfall by 

gravity. Failure to do this can cause water 

trapped in discharge to freeze which could 

result in damage to pump.

12.  Install an in-line check valve to prevent flow 

backwards through pump after pump shuts off.

 

NOTICE Simer check valves are equipped 

with an air bleed hole to prevent airlocking the 

pump. If using a check valve that is not a Simer 

valve, drill a 1/8” (3.2mm) hole in discharge 

pipe just above pump body but below the 

check valve to prevent air locks.

13.  After all piping and controls have been 

installed, unit is ready for operation.

14.  Run pump through one cycle to check float 

switch operation.

 

 Risk of sudden starts. Can 

cause electrical shock and personal 

injury.

 

The pump motor is equipped with 

automatic resetting thermal protector and 

may restart unexpectedly. Protector tripping 

is an indication of motor overloading as a 

result of operating pump at low heads (low 

discharge restriction), excessively high or low 

voltage, inadequate wiring, incorrect motor 

connections, or a defective motor.

 5098 0705

Discharge

About 6"

About 8"

Check 
Valve
(Purchase
Separately)

Содержание 5020B-04

Страница 1: ...468 7867 English Pages 2 6 Installation Fonctionnement Pi ces Pour plus de renseignements concernant l utilisation l installation ou l entretien Composer le 800 468 7867 Fran ais Pages 7 11 Instalaci...

Страница 2: ...rn a sewage pump that has been installed to your retail store Contact SIMER Customer Service Sewage pumps that have seen service and been removed carry a contamination hazard with them If your sewage...

Страница 3: ...tion before each use making certain all connections are secure 7 Inspect sump pump and system components monthly Keep free of debris and foreign objects Perform routine maintenance as required Risk of...

Страница 4: ...is securely clamped so that float rod is vertical and can move up and down freely If float is angled or binds pump may not start allowing flooding to occur 7 Screw float onto threaded end of rod Threa...

Страница 5: ...utlet Low line voltage If voltage wiring under recommended minimum check size of wiring from main source If OK contact Electric Company or local Hydro cuthority Faulty automatic switch Operate switch...

Страница 6: ...ch model number below Switch FP0020 Switch FP0018 7D Ref Description Qty 5020B 04 1 Motor 1 2 Switch 1 3 Volute Pump Body 1 PS1 25P 4 Impeller 1 PS5 269P 5 Base Plate 1 PS4 17P 6 Screws Base Plate 8 U...

Страница 7: ...ice la client le de SIMER Les pompes d eaux d gout qui ont t utilis es puis retir es pr sentent un risque de contamination En cas de d faillance de la pompe d eaux d gout Porter des gants en caoutchou...

Страница 8: ...lisation non cal e peut donner des coups de fouet qui risquent de provoquer des blessures corporelles et des dommages mat riels 6 Avant chaque utilisation v rifier l tat des tuyaux et s assurer que to...

Страница 9: ...e flotteur sur l extr mit filet e de la tige Le filetage de la tige taraudera un trou dans le flotteur r sistant la corrosion 8 Ins rer l extr mit sans filetage de la tige du flotteur dans l illet du...

Страница 10: ...lage depuis sa souce S il n y a pas de probl me contacter la Compagnie d lectricit ou les services hydro lectriques locaux Interrupteur automatique d fectueux Faire fonctionner l interrupteur manuelle...

Страница 11: ...n se reportant ci dessous Interrupteur FP0020 Interrupteur FP0018 7D R f D signation Qt No de pi ce 1 Moteur 1 2 Interrupteur 1 3 Volute Corps de la pompe 1 PS1 25P 4 Impulseur 1 PS5 269P 5 Plaque du...

Страница 12: ...vuelva una bomba cloacal que se haya instalado a su tienda minorista Comun quese con el Departamento de Atenci n al Cliente de SIMER Las bombas cloacales que hayan estado en servicio y se hayan removi...

Страница 13: ...mangueras antes de usar la bomba para asegurarse de que est n en buen estado y verifique que las conexiones est n firmes 7 Inspeccione mensualmente el sumidero la bomba y los componentes del sistema...

Страница 14: ...Si el flotador est inclinado o se dobla la bomba puede no arrancar y provocar inundaciones 7 Enrosque el flotador al extremo con rosca de la varilla La rosca de la varilla cortar la rosca en el flotad...

Страница 15: ...s desde la fuente de alimentaci n Si el cableado est bien comun quese con la compa a el ctrica o la autoridad de recursos hidrol gicos Interruptor autom tico defectuoso Accione el interruptor manualme...

Страница 16: ...nterruptor FP0020 Interruptor FP0018 7D Ref Descripci n Cant No de piezas 1 Motor 1 2 Interruptor 1 3 Voluta Cuerpo de la bomba 1 PS1 25P 4 Impulsor 1 PS5 269P 5 Placa de base 1 PS4 17P 6 Tornillos Pl...

Отзывы: