background image

For parts or assistance, call Simer Customer Service at 

1-800-468-7867 / 1-800-546-7867

Installation

3

Fire and explosion hazard.

Do not use this

pump to pump flammable or explosive liquids. Use pump
only with liquids compatible with pump component
materials. Do not use pump in explosive atmospheres. 

Risk of flooding.

If for any reason property

damage or personal injury can result from an inoperative
or leaking pump, an auxiliary switch backup system
and/or an alarm should be installed with pump.

INSTALLATION

Electrical shock and carbon monoxide

hazards. When mounting the pump on the side of the
furnace, make sure that the mounting holes clear the
heat exchanger and all wiring. 

The mounting screw for

the pump should touch only the pump reservoir flange
and the exterior sheet metal on the furnace. If in doubt or
if this is confusing, consult a qualified HVAC serviceman
or the furnace manufacturer.

Make sure that the tubing to the pump intake is fastened
securely so that it cannot come out of the pump intake
port. Check for local code requirements. You must com-
ply with codes.

Check local codes for discharge water requirements.
Run the discharge line to a point outside the house if
possible. To do this easily, you may be able to run the
condensate discharge line out through the wall along
the AC freon line. Use the existing line if possible (when
replacing an existing pump). 
Clamping the plastic discharge line to the check valve
with a 1/2" hose clamp (purchase separately) will help
to keep it in place, especially with older tubing (plastic
tubing tends to harden as it gets older).
Common locations for the end of the discharge line are:
A. Out a window or along the air conditioner freon line

to the outdoors.

B. To a floor drain (leave an air gap between the end of

the tube and the drain).

C. To a laundry tub or sink (leave an air gap above the

tub drain).

Gas 
Condensing
Furnace

Mount Pump 
below all Heater 
and A.C. Drains

From A.C.
Unit

Pump must be level!

5490 0906

Pump can also be installed 
on wall or floor. Allow at least 
6-1/2” vertical clearance to 
allow tank removal.

At lea

st 6-1/2”

Mount pump on side of furnace (or on floor or
wall).

1

Furnace 
Condensate
Drain

AC Unit
Condensate
Drain

Plastic
Tubing

5491 0906

1-1

1 2

" above

bottom of
reservoir

Cut tubing at an angle 
so that bottom of 
reservoir doesn't close it. 
Be sure tubing does not 
interfere with float.

Run plastic tubing as shown  into pump’s drain inlet
hole(s).

2

3/8" ID Tubing
To Floor Drain
or Laundry Tub.

Do not kink tube!

Ceiling and Joists

Discharge tube should
slope down toward 
outlet if possible

5492 0906

1/2" Hose 
Clamp

Run tubing as shown from hose barb on pump 
discharge to floor drain or laundry tub.

3

Содержание 2520ULST5499

Страница 1: ...8 7867 English Pages 2 6 Installation Fonctionnement Pi ces Pour plus de renseignements concernant l utilisation l installation ou l entretien Composer le 1 800 468 7867 Fran ais Pages 7 11 Instalaci...

Страница 2: ...ree from defects in material or workmanship If within twelve 12 months from the date of the original consumer purchase any such product shall prove to be defective it shall be repaired or replaced at...

Страница 3: ...n the condensate discharge line out through the wall along the AC freon line Use the existing line if possible when replacing an existing pump Clamping the plastic discharge line to the check valve wi...

Страница 4: ...about 1 2 from the top of the reservoir thereby stopping the production of condensate and preventing flooding but it will not allow the furnace AC unit to restart until the condensate pump reservoir...

Страница 5: ...lding the impeller cover to the motor 6 Remove the impeller cover The rotor impeller assembly may come out with it If not pull it out of the rotor chamber in the motor You may have to pull it hard to...

Страница 6: ...ree of algae build up Be sure to dump the cleaner and rinse the reservoir with water before starting the pump Be sure you do not clog the impeller discharge port or the check valve when starting the p...

Страница 7: ...sur une surface humide ou recouverte d eau Avant d intervenir sur la pompe pour la r parer ou l entretenir la d brancher de la prise de courant ATTACHER LE RE U D ORIGINE ICI DES FINS DE GARANTIE SIME...

Страница 8: ...sser un espace entre l extr mit du tube et le drain C Un bac laver ou un vier laisser un espace au dessus du drain du bac laver ATTENTION Pour obtenir des pi ces ou de l aide appeler le Service la cli...

Страница 9: ...le appareil de chauffage central et climatiseur de red marrer tant que le r servoir de r cup ration des eaux condens es ne sera pas vide Si le niveau de l eau dans le r servoir devait monter trop haut...

Страница 10: ...dans le moteur Il faudra peut tre tirer fermement dessus car le magn tisme des enroulements du moteur le retiendra 7 Nettoyer l impulseur le rotor la cavit du rotor et le joint torique l aide d un ch...

Страница 11: ...ricant Verser environ quatre litres de solution algicide dans le r servoir puis faire fonctionner la pompe sur plusieurs cycles pour d bar rasser le r servoir et la conduite de refoulement des algues...

Страница 12: ...mantenimiento en la misma ADH ERA AQU EL RECIBO ORIGINAL PARA VALIDACION DE GARANT A SIMER garantiza al comprador consumidor original Comprador de sus productos que stos se encuentran libres de defect...

Страница 13: ...on tubos m s viejos las tuber as de pl stico tienden a endurecerse con el tiempo Los lugares comunes para el extremo de la l nea de descarga son A Fuera de una ventana o a lo largo de la l nea fre n d...

Страница 14: ...car hasta que se haya vaciado el tanque de la bomba de condensado Se deber controlar para que en case de que el agua est alta en el tanque se pueda tomar una medida correctiva antes de que ocurra un c...

Страница 15: ...uera de la c mara del rotor en el motor Es posible que deba jalar fuerte mente para sacarla contra el magnetismo en los devanados del motor 7 Limpie el impulsor el rotor la cavidad del rotor y el aro...

Страница 16: ...l tanque y la l nea de descarga libres de acumu laci n de algas Aseg rese de verter todo el producto de limpieza y enjuagar el tanque con agua antes de arrancar la bomba Aseg rese de no tapar la abert...

Отзывы: