The system pump
Check if the summer function is active.
doesn’t work
Check the right plug-in.
The pump can be blocked, burned-off or air into the
system.
Enabling from ambient thermostat missing (or the
bridging on the plug - in case the termostat is not
available - is missing - in this case the pump led is
flashing).
The burner get dirty
Low quality pellet (too dusty pellet or excess of
very quickly
bark and of mineral residuals, hampring the,
automatic removal during the cleaning).
Underpressure is not eneugh.
Pellet’s diameter <> 6mm.
Smokes loss
Check the right closing of the front doors and of
(pellet mode)
the top cover.
Check the burner’s seal is well fastened to the door.
Check the right connection between boiler’s
smokes outlet and the chimney.
Pellet stops into the
Check the right position
flexible tube
Too much sawdust. Clean it.
Low quality pellet which tends to stick to the coilholder
slide thus hampering the descent.
Primari fan stop
Set boiler’s temperature is reached (MAnt).
Boiler’s OFF.
The fan is blocked or broken: contact the nearest
service center.
Door open (Por) (only on boiler’s prepared
for this.
The pellet descent
Action of the safety system (melting of the pipe)
self-extinguishing
to physically separate the pellet storing chamber
pipe has melted.
from the burner in case of back-fire.
Always replace the pipe with a self-extinguishing pipe to
avoid affecting the safety device described above.
Underpressure is not enought into the chimeny.
Low quality pellet obstructing the burner.
Содержание SOLIDA 8 PL