![Sime RS 10 Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/sime/rs-10/rs-10_installers-instructions_1275105012.webp)
4.2
GAS VALVE ADJUSTMENT
The
“RS”
boilers have the gas valve
equipped with a coil assembly, which
enables, via the double-contact regula-
ting thermostat, a reduction in output
corresponding to approx. 60% of nomi-
nal output before the burner goes out
completely. Calibration of the gas pres-
sures at the maximum and reduced
values is done by SIME in the factory.
Consequently they should not be alte-
red. Only when you switch to another
type of gas (butane or propane) is it
permitted to alter the operating pres-
sures according to the value shown in
Table 3.
It is essential that this ope-
ration be carried out exclusively by
authorized technical staff.
When the
gas pressures are to be reset, this
must be done following a set order:
first the maximum pressure and then
the reduced.
4.2.1
Maximum and minimum
pressure adjustment
To set the maximum pressure, pro-
ceed as follows (fig. 19):
–connect the pressure column or a
pressure gauge to the pressure
int ake locat ed on t he bur ner
manifold;
–unscrew the screw (4) completely;
–set the knob of the thermostat to
the maximum value;
–supply electric power to the boiler;
–loosen the locknut (1) and turn the
connection (3): to reduce the pres-
sure, turn the connection counter-
clockwise; to increase the pressure,
turn the connection clockwise;
–tighten the locknut (1);
–operate the main switch a number
of times, making sure that the pres-
sure corresponds to the values
given in
Table 3.
After having adjusted the maximum
pressure, calibrated the minimum
pressure as follows (fig. 19):
– always use the pressure column or
a pressure gauge to check the
pressure;
– deactivate the coil (2) electric supply;
–switch on the boiler and af ter a
short period of operation at nominal
output, turn the thermostat knob
slowly towards the minimum posi-
tion until you hear the click of the
first contact of the thermostat;
–leave the knob in that position and,
turning the screw (4), seek the
reduced pressure value according
to
Table 3 for the gas in question: to
r educe t he pr essur e, tur n t he
scr ew (4) count er clockwise; t o
increase the pressure, turn the
screw clockwise;
–restore electric power to the coil;
–operate the main switch a number
of times, making sure that the pres-
sure corresponds to the value given
in
Table 3.
4.3
COIL
The components of the coil are shown
in fig. 20.
4.4
CONVERSION TO
DIFFERENT GAS
A kit is supplied complete with neces-
sary change-over materials for opera-
tion with butane gas (G30) or propane
gas (G31). For changing over from one
gas to another the main nozzles and
the tapered spring (1 fig. 20) must be
replaced with another supplied in the
boiler gas conversion kit. To adjust the
operating pressures, refer to section
4.2.1. After having ultimated the con-
version of the boiler, please stick onto
the casing panel to the plate showing
the relevant freeding gas which is inclu-
ded into the kit.
NOTE: After assembling all the gas
connections, a test for gas tightness
must be carried out using soapy
water or special products. DO NOT
USE NAKED FLAMES.
4.5
CLEANING AND
MAINTENANCE
At the end of each heating season, it is
essential to have the boiler thoroughly
checked and cleaned out in compliance
with the national legislation. Proceed
as follows (fig. 21):
–cut off electric power to the control
panel;
–remove the door of the outer casing
(2), the front panel (3), and the bot-
tom base strip (1);
58
KEY
1 Locknut M13
2 Coil
3 Max. pressure
adjust. connection
4 Reduced pressure
adjust. screw
Fig. 19
TABLE 3
Type of gas
Minimum pressure
Maximum pressure
mbar
mbar
Methane - G20
6
9,7
Butane - G30
15
28
Propane - G31
15
35
Fig. 20
KEY
1 Tapered spring
2 Spring anchor
3 Locknut M13
4 Max. pressure
adjust. connection
5 Coil
6 Spring
7 Clip
8 Reduced pressure
adjust. screw
Содержание RS 10
Страница 1: ...RS IT ES GB PT...