Sime RS 10 Скачать руководство пользователя страница 12

4.2

GAS VALVE ADJUSTMENT

The 

“RS”

boilers  have  the  gas  valve

equipped  with  a  coil  assembly,  which
enables, via the double-contact regula-
ting  thermostat,  a  reduction  in  output
corresponding to approx. 60% of nomi-
nal output before the burner goes out
completely. Calibration of the gas pres-
sures  at  the  maximum  and  reduced
values  is  done  by  SIME  in  the  factory.
Consequently  they  should  not  be  alte-
red.  Only  when  you  switch  to  another
type  of  gas  (butane  or  propane)  is  it
permitted  to  alter  the  operating  pres-
sures according to the value shown in
Table  3. 

It  is  essential  that  this  ope-

ration  be  carried  out  exclusively  by
authorized  technical  staff. 

When  the

gas  pressures  are  to  be  reset,  this
must  be  done  following  a  set  order:
first  the  maximum  pressure  and  then
the reduced.

4.2.1

Maximum and minimum 
pressure adjustment

To  set  the  maximum  pressure,  pro-
ceed as follows (fig. 19):
–connect  the  pressure  column  or  a

pressure  gauge  to  the  pressure
int ake  locat ed  on  t he  bur ner
manifold;

–unscrew the screw (4) completely;
–set  the  knob  of  the  thermostat  to

the maximum value;

–supply electric power to the boiler;
–loosen  the  locknut  (1)  and  turn  the

connection  (3):  to  reduce  the  pres-
sure,  turn  the  connection  counter-
clockwise; to increase the pressure,
turn the connection clockwise;

–tighten the locknut (1);
–operate  the  main  switch  a  number

of times, making sure that the pres-
sure  corresponds  to  the  values
given in 

Table 3.

After  having  adjusted  the  maximum
pressure,  calibrated  the  minimum
pressure as follows (fig. 19):
– always use the pressure column or

a  pressure  gauge  to  check  the
pressure;

– deactivate the  coil (2) electric supply;
–switch  on  the  boiler  and  af ter  a

short period of operation at nominal
output,  turn  the  thermostat  knob
slowly  towards  the  minimum  posi-
tion  until  you  hear  the  click  of  the
first contact of the thermostat;

–leave  the  knob  in  that  position  and,

turning  the  screw  (4),  seek  the
reduced  pressure  value  according
to 

Table 3 for the gas in question: to

r educe  t he  pr essur e,  tur n  t he
scr ew  (4)  count er clockwise;  t o
increase  the  pressure,  turn  the
screw clockwise;

–restore electric power to the coil;
–operate  the  main  switch  a  number

of times, making sure that the pres-
sure corresponds to the value given
in 

Table 3.

4.3

COIL

The components of the coil are shown
in fig. 20.

4.4

CONVERSION TO 
DIFFERENT GAS

A  kit  is  supplied  complete  with  neces-
sary  change-over  materials  for  opera-
tion with butane gas (G30) or propane
gas (G31). For changing over from one
gas  to  another  the  main  nozzles  and
the tapered spring (1 fig. 20) must be
replaced  with  another  supplied  in  the
boiler gas conversion kit. To adjust the
operating  pressures,  refer  to  section
4.2.1.  After  having  ultimated  the  con-
version  of  the  boiler,  please  stick  onto
the  casing  panel  to  the  plate  showing
the relevant freeding gas which is inclu-
ded into the kit.

NOTE:  After  assembling  all  the  gas
connections, a test for gas tightness
must  be  carried  out  using  soapy
water  or  special  products.  DO  NOT
USE NAKED FLAMES.

4.5

CLEANING AND 
MAINTENANCE

At the end of each heating season, it is
essential to have the boiler thoroughly
checked and cleaned out in compliance
with  the    national  legislation.  Proceed
as follows (fig. 21):
–cut off electric power to the control

panel;

–remove the door of the outer casing

(2), the front panel (3), and the bot-
tom base strip (1);

58

KEY
1 Locknut M13
2 Coil
3 Max. pressure 

adjust. connection

4 Reduced pressure 

adjust. screw

Fig. 19

TABLE 3

Type of gas

Minimum pressure

Maximum pressure

mbar

mbar

Methane - G20

6

9,7

Butane - G30

15

28

Propane - G31

15

35

Fig. 20

KEY
1 Tapered spring
2 Spring anchor
3 Locknut M13
4 Max. pressure 

adjust. connection

5 Coil
6 Spring
7 Clip
8 Reduced pressure

adjust. screw

Содержание RS 10

Страница 1: ...RS IT ES GB PT...

Страница 2: ...rge the system bleeding off the air present in the gas pipe by operating the pressure relief valve on the gas valve inlet Make sure that none of the regulation control and safety devices and appurtena...

Страница 3: ...II2H3 II2H3 II2H3 II2H3 II2H3 II2H3 II2H3 II2H3 II2H3 Type B11 B11 B11 B11 B11 B11 B11 B11 B11 Maximum temperature C 95 95 95 95 95 95 95 95 95 Mains gas nozzles Quantity n 5 6 7 8 9 10 11 12 13 Meth...

Страница 4: ...limiting pressure loss between the gas meter and any apparatus being used to not greater than 1 0 mbar for family II gases natu ral gas 2 0 mbar for family III gases butane or propane An adhesive data...

Страница 5: ...must be at least 500 mm Access to the chamber must be guaranteed by means of an opening provided with an air tight metal door have a circular square or rectangu lar internal cross section in the case...

Страница 6: ...pieces which are to be joined together using the screws provided fig 5 The smoke chamber is assembled by fastening the right hand side panel 2 to the top panel 1 using the nine hexagonal head self tap...

Страница 7: ...l 6 and the panels 7 and 8 to the panel 9 by means of the pressure pins making sure that they are joined together using the two self tapping flathead screws 7SP x 1 2 provided assemble the panels 4 an...

Страница 8: ...provided between the head and the intermediate section at the other end of the body NOTE Take the utmost care when assembling the two electrodes so as not to break the ceramic coating which otherwise...

Страница 9: ...rough the SM 191 1 programmer and the gas valve opens at the same time Burner ignition normally takes place within 1 or 2 seconds However it is possible for ignition failures to occur with consequent...

Страница 10: ...regu lating thermostat with a double con tact having differentiated setting This makes it possible to obtain a reduction of heat output before the burner goes out completely by means of the coil asse...

Страница 11: ...4085 is supplied by a rectified con nector code 6243600 which in the event of breakage must be replaced To replace it follow the instructions of fig 18 4 USE AND MAINTENANCE KEY 1 Electric operator 2...

Страница 12: ...e minimum posi tion until you hear the click of the first contact of the thermostat leave the knob in that position and turning the screw 4 seek the reduced pressure value according to Table 3 for the...

Страница 13: ...upon first ignition or after long periods of lay off Check whether the rectifier card on the connector that supplies the gas solenoid valve is working properly If necessary replace Valve coil has a b...

Страница 14: ...scharge cur rent to the ignition electrode and simul taneously opening the gas valve Ignition of the burner normally takes place within 1 or 2 seconds For various reasons the boiler may fail to start...

Страница 15: ...y to convert to a different gas from that for which the boiler has been arranged get in touch exclusively by authorized technical staff CLEANING AND MAINTENANCE At the end of each heating season it is...

Отзывы: