This occurs when the position of live
and neutral has not been respected
on the terminal block. There is a
break in the wire of the sensing
electrode or the electrode itself is
earthed: the electrode is worn out
and needs replacing.
NOTE:
Should the equipment “lock out”,
first wait at least 20 seconds from
when the warning lamp lights up,
before pressing the push-button
with built-in light; otherwise, the
appliance will not be deblocked.
3.1.2
Ionization circuit
The ionization circuit is to be checked
using a dial-type micro-ammeter, or
preferably a digital micro-ammeter
with a 0 to 50 µA scale.
The micro-ammeter terminals must be
series-connected to the wire of the
sensing electrode.
Under normal operating conditions,
the value oscillates between 6÷12 µA.
The minimum value of the ionization
current for which the equipment can
“lock out” is about 1 µA.
In this case, make sure that there is a
good electrical contact and check the
degree of wear of the end part of the
electrode and the corresponding cera-
mic protection.
3.2
REGULATION THERMOSTAT
“RS”
boilers are equipped with a regu-
lating thermostat with a double con-
tact having differentiated setting. This
makes it possible to obtain a reduction
of heat output before the burner goes
out completely, by means of the coil
assembly (fig. 20) installed on the gas
valve regulator.
This step-modulation system affords
the following advantages:
–higher overall boiler efficiency;
–cont ainment wit hin accep t able
values of the increase in temperatu-
re that takes place in the cast-iron
body (heat inertia) when the burner
goes out.
3.3
LAYOUT WITH TWO
OPPOSED BOILERS
Accessories are available on request
to permit an opposed layout of two boi-
lers which will reduce overall dimen-
sions and facilitate connection with the
flue through a single flue gas duct (figu-
res 14 - 15).
Table 2 gives the dimensions of the
two boilers combined and the diameter
of the chimney.
Fig. 14
TABLE 2
D (ø mm)
L (mm)
A (mm)
RS 6
400
2360
600
RS 7
400
2360
600
RS 8
400
2360
600
RS 9
400
2360
600
RS 10
450
2360
600
RS 11
450
2360
600
RS 12
500
2380
620
RS 13
500
2380
620
RS 14
500
2380
620
Connecting cover
Connecting panel
RS 6
6136208
6136251
RS 7
6136209
6136251
RS 8
6136210
6136251
RS 9
6136211
6136251
RS 10
6136212
6136252
RS 11
6136213
6136252
RS 12
6136205
–
RS 13
6136206
–
RS 14
6136207
–
Fig. 15
KEY
1 Connecting cover
2 Connecting panel
Содержание RS 10
Страница 1: ...RS IT ES GB PT...