background image

97

p air” ADJUSTMENT

To measure “

p air” simply con-

nect  a  differential  pressure
gauge with a decimal or Pascal
scale  to  the  positive  and  nega-
tive  tap,  observing  the  symbols
(

Drawing 1

).

Sequence of operations:
1)

Turn the heating power con-
trol  trimmer  clockwise  as
far as it will go (

B – Drawing

2

)  with  the  fan  at  its  top

speed.

2)

Attempt  to  achieve  the  “

p

air” values given in the table
by  adjusting  the  MAX  trim-
mer  on  the  fan  board
(

Drawing 3

):

p air max.

3)

Turn the heating power con-
trol  trimmer  anti-clockwise
as  far  as  it  will  go  (

B  –

Drawing  2

)  with  the  fan  at

its top speed.

4)

Attempt  to  achieve  the  “

p

air”  values  shown  in  the
table  using  the  “MIN”  trim-
mer  on  the  fan  board
(

Drawing 3

):

p air min.

p air-gas” ADJUSTMENT

To measure “

p air-gas”, simply

connect  the  positive  tap  of  the
differential  pressure  gauge  to
the  gas  tap  and  the  negative
tap to the corresponding tap on
the boiler (

Drawing 4

)

Always  adjust  gas  pressure
with the fan at its top speed.

Sequence of operations: 
1)

Turn the heating power con-
trol  trimmer  anti-clockwise
as  far  as  it  will  go  (

B  –

Drawing  5

)  with  the  fan  at

its top speed.

2)

Open  the  gas  capacity  step
(

1  –  Drawing  6

)  all  the  way

so that the notch is in a hori-
zontal position. 

The boiler must always be calibrated while set on heating.

ATTENTION:

–  On PROPANE – G31 boilers

it  is  a  good  idea  to  check
that the position of the GPL
bridge  on  the  control  board
is correct.

–  Diaphragm code 6028640

(

Drawing  7

)  is  assembled

on  the 

“Dewy  25”

model

functioning  on  PROPANE  –
G31 only.

–  If the fan control board code

8260501  is  replaced  on

“Dewy”

models  running  on

PROPANE  –  G31  it  is  very
important  to  remember  to
cut the specified resistance
(

Drawing 8

).

B

2

1

Upon completion of the calibration procedure, check CO

2

values using a combustion analyser. If a difference which is more than 0.2 above

or below the values indicated in the table is found, it will be necessary to correct it:

– Use the OFFSET screw (

2 – Drawing 6

) to correct CO

2

at “MIN” output.

– Use the capacity step to correct CO

2

at “MAX” output (

1 – Drawing 6

).

Drawing 1

Drawing 2

Drawing 4

Drawing 6

Drawing 7

Drawing 8

Dewy 

25

30

Natural gas (G20) 49,5

63,8

Propane (G31)

49,5

68,4

Dewy 

25

30

Natural gas (G20)

7,1

8,4

Propane (G31)

7,1

9,2

B

Drawing 5

3)

Adjust the gas valve OFFSET regulation (

2 – Drawing 6

), aiming

to achieve the “

p air- gas” shown in the table:

Capacity step open

4)

Using the capacity step (

1 – Drawing 6

), attempt to achieve the

p air-gas” shown in the table:

Capacity step regulated

Dewy 

25

30

Natural gas (G20)

7,3

7,0

Propane (G31)

8,1

10,1

Dewy 

25

30

Natural gas (G20)

5,3

6,3

Propane (G31)

4,4

9,0

“Dewy 25”

“Dewy 30”

CO

2

(Natural gas)

CO

2

(Propane)

CO

2

(Natural gas)

CO

2

(Propane)

“MIN” output

9,3

10,2

9,0

10,1

“MAX” output

8,9

10,0

9,1

10,3

Drawing 3

MIN. MAX

“∆p air”

adjustment

4.3

BOILER CALIBRATION

Fig. 26

Содержание PLANET DEWY 30 BFR

Страница 1: ...is unobstructed and has been pro perly installed Make sure that any shutoff valves are open Make sure that the system is charged with water and is thoroughly vented Check that the circulating pump is...

Страница 2: ...H return 3 4 M C H flow 3 4 G Gas connection 3 4 C1 System filling optional 1 2 S3 Condensation outlet 25 1 3 TECHNICAL FEATURES 30 BFR Heat output Nominal 80 60 C kW kcal h 28 3 24 300 Minimum 80 60...

Страница 3: ...ixing jig 19 90 C limit stat 20 Condensation water trap 21 Gas rate adjuster 22 System filling optional 23 Aqua Guard 24 Non return valve 1 5 MAIN COMPONENTS Fig 3 KEY 1 Control panel 2 Gas rate adjus...

Страница 4: ...e data plate is sticked inside the front panel it contains all the technical data identifying the boiler and the type of gas for which the boiler is arranged 2 3 1 Connection of condensation water tra...

Страница 5: ...ow eaves 300 D below balcony 1 300 E from adjacent window 400 F from adjacent ventilation opening 600 G from horizontal or vertical soil or drain pipes 2 300 H from corner of building 300 I from reces...

Страница 6: ...on calculation in that the sum of the head losses of the single fittings is less than 15 5 mm H2O Inlet Outlet 7 m horizontal pipe 80 x 0 20 1 40 7 m horizontal pipe 80 x 0 30 2 10 n 2 90 elbows 80 x...

Страница 7: ...eed 15 5 mm H2O When calculating the lengths of pipe take into account the parameters given in the Table 2 2 8 60 PIPING SYSTEM A special kit allows to separate smoke outlet and air intake pipes The 8...

Страница 8: ...cables of section 0 5 mm2 First of all assemble and wire the socket 2 then insert the equipment which will start up as soon as it receives current To gain access to connector 3 remove the control pan...

Страница 9: ...electrode ER Sensing electrode TS 100 C safety stat V Fan TPA Water pressure transducer P Pump SE External sensor optional TA Room stat SM C H sensor blue TR Transformer 230 24V FL Flowmeter CR Logic...

Страница 10: ...rough a window contact Anti bacterial 2 10 1 Installation The unit must be installed in the main living room For installation follow the assembly instructions inserted in the package At this point wit...

Страница 11: ...nute of the prescribed delivery temperature value sent in C is limited to the imposed value With the activation of the adaptation the pre set value transmitted to the boiler regulator is adapted to th...

Страница 12: ...o par metro 64 1 0 activa s a sonda interna 0 externa 100 interna 50 valor m dio da sonda externa interna 100 activa s a sonda externa Para a regula o ambiente e a visualiza o utilizada a mistura pro...

Страница 13: ...egulated so as to obtain a pressure of approx 3 mbar at the burner for methane gas and 7 mbar for propane gas G31 To increase pressure turn the trimmer clockwise to reduce pres sure turn the trimmer c...

Страница 14: ...up There could have a break in the wire of the sensing electrode or the electrode itself is touching earth the electrode is worn out and needs replacing The con trol box is defective When there is a...

Страница 15: ...function of the flow in graph in fig 21 3 7 MAINS ELECTRICITY CONNECTION Use a separate electricity supply to con nect the room stats and relative zone val ves or pumps The micro or relay contact con...

Страница 16: ...2 Gas valve 3 Mixer intake 4 Ventilator intake 5 Nozzle 6 Fan 7 Air gas mixer 8 Air pressure switch 9 Digital pressure gauge Fig 24 0 30 20 10 p aria mm H2O Potenza termica kW 25 20 10 15 50 40 60 5 3...

Страница 17: ...G31 boilers it is a good idea to check that the position of the GPL bridge on the control board is correct Diaphragm code 6028640 Drawing 7 is assembled on the Dewy 25 model functioning on PROPANE G3...

Страница 18: ...sliding them out of their slots 4 6 CLEANING AND MAINTENANCE Preventive maintenance and checking of efficient operation of equipment and safety devices must be carried out exclusively by authorized te...

Страница 19: ...ing of the water C H TEMPERATURE ADJUSTMENT fig 2 The C H temperature can be adjusted by turning the knob of the C H potentiometer The set temperature is indicated on the red led scale from 35 80 C an...

Страница 20: ...out occurs again call local authorised Service Centre for technical assistance Other anomalies fig 6 When one of the red 40 80 C leds start flashing switch off the boiler and then try to ignite again...

Страница 21: ...utton automatic operation 4 Operating mode button manual operation 5 Operating mode button availability 6 Cover with instruction compartment 7 Temperature knob 8 Presence button Fig 8 KEY 1 Display ti...

Страница 22: ...l lowing list of items one after the other are displayed The thermo feeler continues to function independently of the display Day hour room temperature External temperature Hot water service temperatu...

Страница 23: ...ity boiler unit temperature desired for hot water service at reduced level To have access to the reduced hot water service temperature parameter press the and keys at the same time for at least 5 seco...

Страница 24: ...rature set in parameter 3 1 standard Hot water according to the daily heating programme In the comfort periods of the heating the temperature of the boiler unit is regulated at the value set via para...

Страница 25: ...of the heating characteristics curve When the room temperature set is not reached choose the gradient indicated in point 2 9 3 Display of the current boiler temperature Display of the current power of...

Страница 26: ...fficient water pressure Reset operation using the boiler charge valve fig 4 Plant overpressure Call an authorised Service Centre Safety thermostat trips Call an authorised Service Centre Fan air press...

Отзывы: