26
NOTE: the inside of the upper door of
the boiler panel has a label with the
values that have to be set for PAR 1 and
PAR 2 (fig. 19).
3.3.2 Warning
If the boiler is functioning but not opti-
mally, and it is not showing any error,
press
until info 70 is displayed.
When the boiler is operating at its opti-
mum the display will show “--”.
Refer to the table below for description
of any warning displayed.
PARAMETERS INSTALLER
EXPANSION CARD
PAR DESCRIPTION
RANGE
UNIT OF
INC/DEC
DEFAULT
MEASUREMENT UNIT
SETTING
40 Number of expansion boards
0 ... 3
=
1
0
41 Mix valve stroke time
0 ... 199
10 sec.
1
12
42 Priority of D.H.W. over mixed zone
0 = Paralle
=
=
1
1 = Absolute
43 Floor drying
0 = No activated
=
=
0
1 = Curve A
2 = Curve B
3 = Curve A+B
44 Type of solar system
1 ... 7
=
1
1
45
∆
t solar collector pump 1
PAR 74 OEM - 1... 50
°C
1
8
46 Solar integration delay
“--”, 0 ... 199
Min.
1
0
47 Tmin solar collector
“--”, -30 ... 0
°C
1
- 10
48 Tmax solar collector
“--”, 80 ... 199
°C
1
120
PARAMETERS RESTORATION
PAR DESCRIPTION
RANGE
UNIT OF
INC/DEC
DEFAULT
MEASUREMENT UNIT
SETTING
49 * Reset default parameters
-- , 1
=
=
=
(par 01 - par 02 = “-“)
* Should the boiler not be operating correctly, the original default values can be reset by setting PAR 49
= 1 and the PAR 1 and PAR 2 as specified at point 3.3.1.
CODE
DESCRIPTION
E0
Operation in power reduction (
∆
t
between supply and return more
than 40 ° C)
E1
External sensor, SE , short circuit.
E2
TBD
E3
TBD
E4
TBD
E5
TBD
E6
TBD
E7
TBD
E8
TBD
E9
TBD
BOILER
PAR
2
Instantanious with diverter valve
1
and
flowmeter
Instantanious with diverter valve,
2
flowmeter and solar system
Remote control cylinder with
diverter valve and sensor
3
T version (LOW INERTIA)
Tank on board with
diverter valve and DHW sensor
4
(LOW
INERTIA)
Remote control cylinder with
diverter valve and tank thermometer
5
(LOW
INERTIA)
or heating only R version
Only
heating
antifreeze sensor
9
(LOW
INERTIA)
CASCADE CONNECTION PARAMETERS
When the appliance is installed in sequence/cascade (modular
system with several generators) it is necessary to set on all the
boilers the following INST PAR parameters:
PAR 15 =
0 for the first boiler (MASTER)
1 .... 7 for the other boilers (SLAVE)
(Avoid assigning the same number
to SLAVE boilers)
Boiler connected to a common(cascade) flue. whether working in
cascade or independently must have PAR1 reset
PAR 1 =
8 (for NATURAL GAS boilers)
16 (for PROPANE boilers)
In addition, when the number of boilers in cascade is more than
two, configure the parameters OEM A1 of the MASTER boiler.
(See 2.2.2)