C type (Coaxial exaust ø 80/125)
NOTE:
- The condense recovery (12) should be connected to
a waste water drain.
- Before fitting the accessories, it is always advisable
to lubricate the internal section of the gaskets with
silicon products, avoid the use of oils and greases.
- Insertion of additional 90 degree bends, will reduce
the available flue length by 1 metre each.
- Insertion of additional 45 degree bends, will reduce
the available flue length by 0.5 metre each.
Fig. 8
VERTICAL EXHAUST
To ensure correct operation of the appliance, do as
follows:
- set the installer parameter PAR 9 as indicated in
TABLE 3 (see point 3.3 to access the installer para-
meters).
- proceed with calibrating CO2 at the maximum and
minimum capacity as specified in point 4.2.2.
TABLE 3
Maximum length
PAR 9
exhaust (m)
(long chimneys)
0 - 1,0
6
1,0 - 2,0
7
2,0 - 3,0
8
3,0 - 4,0
9
4,0 - 5,0
10
HORIZONTAL EXHAUST
To ensure correct operation of the appliance, do as
follows:
- set the installer parameter PAR 9 as indicated in
TABLE 3/a (see point 3.3 to access the installer
parameters).
- proceed with calibrating CO2 at the maximum and
minimum capacity as specified in point 4.2.2.
TABLE 3/a
Maximum length
PAR 9
exhaust (m)
(long chimneys)
0 - 1,0
7
1,0 - 2,0
8
2,0 - 3,0
9
3,0 - 4,0
10
600
Model
Gas H (m) L (m)
Murelle Green Planet 110 HE i/e G20
5
4
Murelle Green Planet 110 HE i/e G31
4
3
Flue kits
8091280 8091281
Key
Code
Description
Include
Include
2a
8096171
1000mm extension 80/125
2b
8096170
500mm extension 80/125
3
8091300
Articulated tile
4 / 4a 8091205
Coaxial roof terminal
9
10
8091401
Inlet/exhaust fi tting
9
9
11
Gasket(supplied with boiler)
12
8092800
Condensate recovery
9
9
13
8091210
Coaxial terminal 80/125
9
14a
8095870
90° bend 80/125
9
14b
8095970
45° bend 80/125