7
1.4
TECHNICAL SPECIFICATIONS MURELLE EQUIPE 660 ErP
MURELLE EQUIPE
660 ErP
Heat output
Nominal (80-60°C) (Pn max)
kW
633.6 (6 x 105.6)
Nominal (50-30°C) (Pn max)
kW
687.6 (6 x 114.6)
Minimum (80-60°C) (Pn min)
kW
21.1
Minimum (50-30°C) (Pn min)
kW
23.6
Heat input (*)
Nominal (Qn max - Qnw max)
kW
648.0 (6 x 108.0)
Minimum (Qn min - Qnw min)
kW
21.6
Min/max operating yield (80-60°C)
%
97.7/97.8
Min/max operating yield (50-30°C)
%
109.1/106.1
Operating yield at 30% (40-30°C)
%
105.6
Energy yield markings (CEE 92/42)
Losses after shutdown to 50°C (EN 15502)
W
1640
MURELLE HE 110 R ErP generators
n°
6
Feeding tension
V-Hz
230-50
Absorbed power consumption (Qn max)
W
1548 (6 x 258)
Absorbed power consumption (Qn min)
W
150
Absorbed power consumption modulating pump
W
780 (6 x 130)
Electrical protection grade
IPX4D
Energy efficiency
Seasonal energy efficiency class of the heating system
A
Seasonal energy efficiency of the heating system
%
91
Sound power of the heating system
dB (A)
---
Single module temperature regulation
°C
20/80
Water content modules
l
49.2 (6 x 8.2)
Max operating pressure (PMS)
bar
5
Max operating temperature (T max)
°C
85
Exhaust temperature at max flow rate (80-60°C)
°C
86.2
Exhaust temperature at min flow rate (80-60°C)
°C
74.6
Exhaust temperature at max flow rate (50-30°C)
°C
61.6
Exhaust temperature at min flow rate (50-30°C)
°C
49.2
Smokes flow min/max
g/s
10.28/310.00
CO
2
at min/max flow rate (G20)
%
9.0/9.0
CO
2
at min/max flow rate (G31)
%
10.2/10.2
NOx measured
mg/kWh
24
Max. output pressure fumes manifold
Pa
375
Max. pressure independent fumes
Pa
428
CE certification
n°
1312CM5614
Category
II2H3P
Type
B23-B53-B23P-B53P-C13-C33-C43-C53-C83
NOx class
5 (< 70 mg/kWh)
Nozzle
Number n°
1
Nozzle diameter (G20)
ø
12.4
Nozzle diameter (G31)
ø
8.2
Gas consumption at nominal/minimum output
Nominal (G20)
m
3
/h
68.52 (6 x 11.42)
Minimum (G20)
m
3
/h
2.28
Nominal (G31)
kg/h
50.28 (6 x 8.38)
Minimum (G31)
kg/h
1.68
Supply pressure (G20/G31)
mbar
20/37
(*) Heat input of the heating system measured using lower heating value (LHV)