24
4
CASCADE FLUE
1
Assemble the cascade flue as shown. use silicone grease to
ease connection of the components.
The flue can be orientated to the left or the right, but always
must fall to the condensate drain.
CAUTION: The boiler becomes a C-type appliance
when the intake terminal is removed from the flange
and the intake is connected.
In these cases, use ø 80 polypropylene accessories,
authorised and customised by SIME (refer to the
instruction manual provided with the boiler).
When boilers are used with a cascade flue PAR
1 on each boiler must be reset.
On natural gas PAR 1 = 8
On LPG PAR 1 = 16
To access the INST parameters and configure
PAR 9, press the INSTALLER BUTTONS (
and
) simultaneously for 2 seconds.
Parameter 1 will be displayed. Change the
values use the buttons (
and
).
After 60 seconds, the INST parameters will be
exited automatically or by pressing one of the
command buttons (2), except the RESET.
2
INSTALLER
BUTTONS
Provided with each
boiler there is a ø 80
rubber gasket to be
placed inside t he
fume exhaust unit, as
shown in the figure.