32

– disassemble  the  right  side  (10)  fol-

lowing the same operations.

3.3.4 Fault finding

Herefater  we  outline  a  number  of
potential  problems  that  may  occur  on
the  appliance  and  the  relevant  list  of
actions  required.  A  working  fault,  in
most cases, provocates the “lock out”
signal  onto  the  control  panel  of  the
control  box.  When  this  light  turns  on,
the  burner  can  operate  again  only
af t er  t he  r ese t  butt on  has  been
pressed;  if  this  has  been  done  and  a
regular  ignition  occurs,  it  means  the
failure can be defined momentary and
not dangerous. On the contrary, if the
“lock out” stays, the cause of the fault,
as well as the relevant action must be
made according to the following chart:

The burner does not ignite 

– Check the electric connections.
– Check  the  regular  fuel  flow,  the

cleanness of the filters, of the nozzle
and air vent from the tube.

– Check the regular spark ignition and

the proper function of the burner.

The  burner  ignites  regularly  but  the
flame goes out immediately

– Check  the  flame  detection,  the  air

calibration  and  the  function  of  the
appliance. 

Difficulty  in  regulating  the  burner
and/or lack of yield

– Check:  the  regular  flow  of  fuel,  the

cleanness  of  the  boiler,  the  non
obstruction  of  the  smoke  duct,  the
real  input  supplied  by  the  burner
and its cleanness (dust). 

The boiler gets dirty easily

– Check  the  burner  regulator  (smoke

analysis),  the  fuel  quantity,  the  flue
obstruction  and  the  cleanness  of
the air duct of the burner (dust).

The boiler does not heat up

– Control  the  cleanness  of  the  shell,

the  matching,  the  adjustment,  the
burner  per formances,  t he  pr e-
adjusted  temperature,  the  correct
function  and  position  of  the  regula-
tion stat.

– Make  sure  that  the  boiler  is  suffi-

ciently powerful for the appliance.

Smell of unburnt products

– Control  the  cleanness  of  the  boiler

shell and the flue, the airtightness of
the boiler and of the flue ducts (door,
combustion  chamber,  smoke  ducts,
flue, washers).

– Control the quality of the fuel.

Frequent  intervention  of  the  boiler
shutoff valve

– Control  the  presence  of  air  in  the

system,  the  function  of  the  circula-
tion pumps.

– Check the load pressure of the appli-

ance, the efficiency of the expansion
tanks and the valve calibration.

3.4 

FROST PROTECTION

In  the  event  of  frost,  ensure  that  the
central  heating  plant  is  functional  and
effective  frost  protection  interlocks
are  in  place  to  protect  against  frost
damage

3.5 

USER WARNINGS

When  faults  occur  and/or  the  equip-
ment does not operate correctly, turn
the  boiler  off  and contact  the  autho-
rised service engineer.

1

10

2

3

8

6

5

7

4

9

Fig. 10

Содержание estelle

Страница 1: ...Rondò Estelle ...

Страница 2: ...CHNICAL FEATURES 25 1 4 FUNCTIONAL DIAGRAM 26 1 5 COMBUSTION CHAMBER 1 6 COMPATIBLE BURNERS 2 INSTALLATION 2 1 BOILER ROOM 27 2 2 BOILER ROOM DIMENSIONS 2 3 CONNECTING UP SYSTEM 2 4 CONNECTING UP FLUE 2 5 FITTING THE CASING RONDÒ 2 6 ELECTRICAL CONNECTION 28 3 USE AND MAINTENANCE 3 1 COMMISSIONING THE BOILER 30 3 2 LIGHTING AND OPERATION 3 3 REGULAR CLEANING 3 4 FROST POTECTION 32 3 5 USER WARNING...

Страница 3: ...e boiler unit BA100 BA150 BA200 ESTELLE for central heating only with combustion hinged door mat chable with a separate boiler unit BA100 BA150 BA200 The components for RONDÒ installa tion are supplied in three separate packages boiler body casing with enclosed documents and control panel 1 BOILER DESCRIPTION 460 850 280 P 55 95 505 625 ø 130 S M R 1 2 DIMENSIONAL DETAILS Fig 1 Rondò Estelle 3 4 5...

Страница 4: ...0 32 0 43 Water loss of head mbar 5 10 15 20 25 Combustion chamber pressure mbar 0 02 0 02 0 02 0 02 0 02 Suggested chimney depression mbar 0 07 0 13 0 14 0 18 0 17 0 23 0 32 0 37 0 34 0 45 Smokes temperature Minimum Maximum C 160 185 160 185 160 185 160 170 160 170 Smokes flow Minimum Maximum m3n h 24 0 31 6 32 4 41 4 42 9 52 8 54 8 63 3 65 5 73 8 Smokes volume dm3 9 12 15 18 21 CO2 12 5 12 5 12 ...

Страница 5: ... 1 4 FUNCTIONAL DIAGRAM L 270 280 Fig 3 Fig 2 L Volume mm dm3 Rondò Estelle 3 305 17 5 Rondò Estelle 4 405 24 0 Rondò Estelle 5 505 30 5 Rondò Estelle 6 605 37 0 Rondò Estelle 7 705 43 5 R 75 ø 110 M8 Fig 4 KEY 1 Burner 2 Boiler 3 Boiler thermometer 4 Boiler drain 5 Non return valve 6 Automatic air vent 7 D H W pump 8 Magnesium anode 9 D H W tank drain 10 D H W storage tank 11 D H W tank expansion...

Страница 6: ... with the standards starting the boiler will be difficult and there will be a consequent formation of soot condensate and encrustation The flue used to expel combustion products into the atmosphere must meet the following requirements be constructed with waterproof materials and resistant to smoke temperature and condensate be of adequate mechanical resilience and of low heat conductivity be perfe...

Страница 7: ...ted by fuses The room thermostat required for enhanced room temperature control should be installed as shown in fig 6 Connect the burner with the cable supplied NOTE SIME declines all responsibility for injury caused to persons due to failure to earth the boiler 2 6 1 Electrical connection to the BA boiler unit To connect the boiler to the boiler unit proceed with the following operations 28 KEY T...

Страница 8: ... of the boiler unit fig 7 connect the cables as shown in the diagram fig 6 a 29 L N 1 2 3 4 5 6 L N 1 2 3 4 5 6 B TS TC 1 2 C IG 1 2 C TB PB PI C NA NC C NA NC R KEY B Burner IG Main switch TS Safety stat TC Boiler stat R Relais PI C H pump PB D H W pump TB D H W stat NOTE When a room stat is to be fitted remove the link between terminal 1 and 5 on the connector plug Fig 6 a RONDÒ ESTELLE BA100 BA...

Страница 9: ...d range between 1 and 1 2 bar If the pressure is less than 1 bar reset the system 3 2 4 Turnig OFF boiler fig 7 To temporarily turn off the boiler turn off the electricity supply by pressing the main switch 1 The following operations must be car ried out if the plant will not be in use for a lengthy period of time position the main switch of the plant on off turn the fuel and water taps of the cen...

Страница 10: ...1 fixed with pin clutches remove the control panel 2 whose sides are fixed by two self tapping screws remove the right back panel 3 which is fixed to the side by two screws remove the left back panel 4 which is fixed to the sides by three screws remove the back panels 5 and 6 which are fixed to the sides by ten self tapping screws disassemble the left side 7 unscrewing the screws fixing it to the ...

Страница 11: ...iler the non obstruction of the smoke duct the real input supplied by the burner and its cleanness dust The boiler gets dirty easily Check the burner regulator smoke analysis the fuel quantity the flue obstruction and the cleanness of the air duct of the burner dust The boiler does not heat up Control the cleanness of the shell the matching the adjustment the burner performances the pre adjusted t...

Отзывы: