3.4 ELECTRICAL WIRING

TESTING:

Check the shut-down of the burner by
opening the thermostats and the lock-out
by 

darkening

 the photoresistance.

White

Capacitor

Limit

Oil valve

D4645

CONTROL BOX

Photoresistance

535RSE/LD

thermostat

Motor

Remote lock-out signal

(230V - 0.5A max.)

Main switch

T6A

Blue

White

Black

Resistance

Ignition

electrodes

CONTROL BOX  (see fig. 8)

To remove the control box from the burner follow of the istruction: 

Loosen the screw (1), open the protection (2) and remove all
components.

Remove the coil (3).

Loosen the two screws (4).

Move a little the control box and remove the high voltage leads.

E9151

4

4

3

1

2

Fig.  8     

Burner-earth 

Safety

thermostat

ATTENTION: 

Do not swap neutral and phase over, follow the diagram
shown carefully and carry out a good earth connection.

The section of the conductors must be at least 1mm². 

(Unless

requested otherwise by local standards and legislation).

The electrical wiring carried out by the installer must be in com-
pliance with the rules in force in the country.

All the installation, maintenance and disassembly operations
must be carried out with the electricity supply disconnected.

DANGER

N

L

~

50Hz - 230V

PE

Содержание 20096000

Страница 1: ...2903126 5 12 2014 Installation use and maintenance instructions Light oil burners One stage operation CODE MODEL TYPE 3513687 SIME FUEL 30 DT BFX 744T3R 20096000 SIME FUEL 30 DT BFX 744T3R GB...

Страница 2: ......

Страница 3: ...ems 5 3 5 Electrical wiring 6 4 WORKING 7 4 1 Combustion adjustment 7 4 2 Nozzles recommended 7 4 3 Pump pressure 7 4 4 Electrodes setting 7 4 5 Air damper adjustment 8 4 6 Fuel heating 8 4 7 Burner s...

Страница 4: ...ght oil viscosity 4 6 mm2 s at 20 C Hi 11 86 kWh kg Electrical supply Single phase 50Hz 230V 10 Motor Run current 0 85A 2700 rpm 283 rad s Capacitor 4 5 F Ignition transformer Secondary 8 kV 25 mA Pum...

Страница 5: ...ould compromise the correct working of the appliance Installations 4 and 5 are forbidden for safety reasons 3 1 BOILER FIXING Put on the flange 1 the screw and two nuts see fig 2 Fix the flange 1 to t...

Страница 6: ...e requirements will be met if you use flues for pressure exhaust of flue gases the condensation kind Make sure the air intake tube s inlet is positioned so that it is not likely to be obstructed by fo...

Страница 7: ...mm 0 5 1 1 5 2 10 20 40 60 20 40 80 100 On the systems in fig 6 and 7 start the burner and wait for the priming Should lock out occur prior to the arrival of the fuel await at least 20 seconds before...

Страница 8: ...nd remove all components Remove the coil 3 Loosen the two screws 4 Move a little the control box and remove the high voltage leads E9151 4 4 3 1 2 Fig 8 Burner earth Safety thermostat ATTENTION Do not...

Страница 9: ...RIED OUT IN THE FACTORY 4 2 NOZZLES RECOMMENDED Delavan type W Steinen type Q Danfoss type S Angle 60 In most cases 80 In case of flame detachment during ignitions at low temperatures 4 3 PUMP PRESSUR...

Страница 10: ...k the second ary air damper B SECONDARY AIR DAMPER B fig 11 The purpose of this damper is to perform a fine tun ing of the inlet air Tuning of this device is possible acting of the screw 3 4 6 FUEL HE...

Страница 11: ...heck that there are not obstructions or dents in the supply or return oil pipes Clean the filter in the oil suction line and in the pump Clean the photoresistance 9 fig 1 page 1 Check for correct fuel...

Страница 12: ...or due to the intervention of unqualified personnel FAULTS POSSIBLE CAUSES SOLUTION The burner will not start when the limit thermostat closes Lack of electrical supply Check presence of voltage in th...

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ...Fonderie Sime S p A via Garbo 27 37045 Legnago Vr Italy Tel 39 0442 631111 Export Division fax number 39 0442 631293 Sime Service fax number 39 0442 631292...