TECHNICAL DATA

2.1 TECHNICAL DATA 

 

”

Light oil is not permitted on low level discharge of flue gas products.

2.2 OVERALL DIMENSIONS

2.3 FIRING RATE,

(as EN 267)

TYPE

744T3R

Output   –   Thermal power

(with air at 20 °C)

1.8 – 3.5 kg/h    -    21.3 – 41.5 kW

Fuel

Light oil, viscosity 4 – 6 mm

2

/s at 20 °C 

”

 

(Hi = 11.86 kWh/kg)

Electrical supply

Single phase,

~

 50Hz  230 V 

±

 10% 

Motor

Run current 0.85 A – 2700 rpm – 283 rad/s

Capacitor

4.5 

F

Ignition transformer

Secondary 8 kV – 25 mA

Pump

Light oil, maximum pressure 15 bar (218 psi)

Absorbed electrical power

0.215 kW

Flange

Burner

77

202

130

20

45

°

ø

 

85

223

.5

11

168

D4087

72

72

150

45

°

ø

 

75

23

0

180

136

150

D7149

Pr

ess

ure

 in th

e combu

s

ti

on

ch

amber

 –

 mb

ar

Fuel output - kg/h

Thermal power - kW

Содержание 20096000

Страница 1: ...2903126 5 12 2014 Installation use and maintenance instructions Light oil burners One stage operation CODE MODEL TYPE 3513687 SIME FUEL 30 DT BFX 744T3R 20096000 SIME FUEL 30 DT BFX 744T3R GB...

Страница 2: ......

Страница 3: ...ems 5 3 5 Electrical wiring 6 4 WORKING 7 4 1 Combustion adjustment 7 4 2 Nozzles recommended 7 4 3 Pump pressure 7 4 4 Electrodes setting 7 4 5 Air damper adjustment 8 4 6 Fuel heating 8 4 7 Burner s...

Страница 4: ...ght oil viscosity 4 6 mm2 s at 20 C Hi 11 86 kWh kg Electrical supply Single phase 50Hz 230V 10 Motor Run current 0 85A 2700 rpm 283 rad s Capacitor 4 5 F Ignition transformer Secondary 8 kV 25 mA Pum...

Страница 5: ...ould compromise the correct working of the appliance Installations 4 and 5 are forbidden for safety reasons 3 1 BOILER FIXING Put on the flange 1 the screw and two nuts see fig 2 Fix the flange 1 to t...

Страница 6: ...e requirements will be met if you use flues for pressure exhaust of flue gases the condensation kind Make sure the air intake tube s inlet is positioned so that it is not likely to be obstructed by fo...

Страница 7: ...mm 0 5 1 1 5 2 10 20 40 60 20 40 80 100 On the systems in fig 6 and 7 start the burner and wait for the priming Should lock out occur prior to the arrival of the fuel await at least 20 seconds before...

Страница 8: ...nd remove all components Remove the coil 3 Loosen the two screws 4 Move a little the control box and remove the high voltage leads E9151 4 4 3 1 2 Fig 8 Burner earth Safety thermostat ATTENTION Do not...

Страница 9: ...RIED OUT IN THE FACTORY 4 2 NOZZLES RECOMMENDED Delavan type W Steinen type Q Danfoss type S Angle 60 In most cases 80 In case of flame detachment during ignitions at low temperatures 4 3 PUMP PRESSUR...

Страница 10: ...k the second ary air damper B SECONDARY AIR DAMPER B fig 11 The purpose of this damper is to perform a fine tun ing of the inlet air Tuning of this device is possible acting of the screw 3 4 6 FUEL HE...

Страница 11: ...heck that there are not obstructions or dents in the supply or return oil pipes Clean the filter in the oil suction line and in the pump Clean the photoresistance 9 fig 1 page 1 Check for correct fuel...

Страница 12: ...or due to the intervention of unqualified personnel FAULTS POSSIBLE CAUSES SOLUTION The burner will not start when the limit thermostat closes Lack of electrical supply Check presence of voltage in th...

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ...Fonderie Sime S p A via Garbo 27 37045 Legnago Vr Italy Tel 39 0442 631111 Export Division fax number 39 0442 631293 Sime Service fax number 39 0442 631292...

Отзывы: