4. WORKING

4.1 COMBUSTION ADJUSTMENT

In conformity with Efficiency Directive 92/42/EEC the
application of the burner on the boiler, adjustment and
testing must be carried out observing the instruction
manual of the boiler, including verification of the CO
and CO

2

 concentration in the flue gases, their temper-

atures and the average temperature of the water in
the boiler.

WARNING 

Combustion air is drawn in from outside, meaning
there may be notable changes in temperature, which
can affect the percentage of CO

2

. You are advised to

adjust CO

2

 in accordance with the graph featured. 

Exemple: Outside air temperature 25 °C, adjust CO

2

to 12.25% (± 0.2%).

SETTINGS CARRIED OUT IN THE FACTORY

4.2

NOZZLES RECOMMENDED :

Delavan type W;   Steinen type Q;   Danfoss type S.

Angle : 60° -

In most cases.

80° -

In case of flame detachment, during ignitions at low 
temperatures.

4.3 PUMP PRESSURE 

12 bar:  

pressure suitable for light oil in most cases.

14 bar: 

 improves flame retention; it is therefore suitable for ignitions at low temperatures.

4.4 ELECTRODES SETTING 

   

Before removing or assembling the noz-
zle, loosen the screw (

A

, fig. 9) and

move the electrodes ahead.

Burner

Nozzle

Pump

pressure

Output

Comb. head 

adjustment

Air damper 
adjustment

Main air 

damper

Code

Model

GPH Angle

bar

kg/h ± 4%

Set-point

Set-point

Set-point

3513687

SIME FUEL 30 DT BFX 0.65 60° W

14

2.6

Fixed

4

D

20096000 SIME FUEL 30 DT BFX 0.65 60° W

14

2.6

Fixed

4

D

Outside air temperature (°C)

% C

O

2

D7052

4

± 

0.3 mm

IMPORTANT:
THESE  DIMENSIONS
MUST BE OBSERVED

D5230

A

Fig. 9

2 - 2.5 mm

ATTENTION

Содержание 20096000

Страница 1: ...2903126 5 12 2014 Installation use and maintenance instructions Light oil burners One stage operation CODE MODEL TYPE 3513687 SIME FUEL 30 DT BFX 744T3R 20096000 SIME FUEL 30 DT BFX 744T3R GB...

Страница 2: ......

Страница 3: ...ems 5 3 5 Electrical wiring 6 4 WORKING 7 4 1 Combustion adjustment 7 4 2 Nozzles recommended 7 4 3 Pump pressure 7 4 4 Electrodes setting 7 4 5 Air damper adjustment 8 4 6 Fuel heating 8 4 7 Burner s...

Страница 4: ...ght oil viscosity 4 6 mm2 s at 20 C Hi 11 86 kWh kg Electrical supply Single phase 50Hz 230V 10 Motor Run current 0 85A 2700 rpm 283 rad s Capacitor 4 5 F Ignition transformer Secondary 8 kV 25 mA Pum...

Страница 5: ...ould compromise the correct working of the appliance Installations 4 and 5 are forbidden for safety reasons 3 1 BOILER FIXING Put on the flange 1 the screw and two nuts see fig 2 Fix the flange 1 to t...

Страница 6: ...e requirements will be met if you use flues for pressure exhaust of flue gases the condensation kind Make sure the air intake tube s inlet is positioned so that it is not likely to be obstructed by fo...

Страница 7: ...mm 0 5 1 1 5 2 10 20 40 60 20 40 80 100 On the systems in fig 6 and 7 start the burner and wait for the priming Should lock out occur prior to the arrival of the fuel await at least 20 seconds before...

Страница 8: ...nd remove all components Remove the coil 3 Loosen the two screws 4 Move a little the control box and remove the high voltage leads E9151 4 4 3 1 2 Fig 8 Burner earth Safety thermostat ATTENTION Do not...

Страница 9: ...RIED OUT IN THE FACTORY 4 2 NOZZLES RECOMMENDED Delavan type W Steinen type Q Danfoss type S Angle 60 In most cases 80 In case of flame detachment during ignitions at low temperatures 4 3 PUMP PRESSUR...

Страница 10: ...k the second ary air damper B SECONDARY AIR DAMPER B fig 11 The purpose of this damper is to perform a fine tun ing of the inlet air Tuning of this device is possible acting of the screw 3 4 6 FUEL HE...

Страница 11: ...heck that there are not obstructions or dents in the supply or return oil pipes Clean the filter in the oil suction line and in the pump Clean the photoresistance 9 fig 1 page 1 Check for correct fuel...

Страница 12: ...or due to the intervention of unqualified personnel FAULTS POSSIBLE CAUSES SOLUTION The burner will not start when the limit thermostat closes Lack of electrical supply Check presence of voltage in th...

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ...Fonderie Sime S p A via Garbo 27 37045 Legnago Vr Italy Tel 39 0442 631111 Export Division fax number 39 0442 631293 Sime Service fax number 39 0442 631292...

Отзывы: