Appendix IX Advanced Output Control (optional)
Operating modes
In this mode the high voltage that is set depends on an analogue control signal, e.g. speed
control of the machine.
Operation in Advanced Output Control (AdvOutC) mode.
In the Advanced Output Control mode the generator is engaged in
voltage controlled charging (see VC mode). However, in this control
mode the emitted high voltage depends on a control voltage. This
will usually be related to the speed of a machine. In this mode a
minimum and maximum voltage are specified in combination with a
threshold and a maximum for the control voltage. As soon as the
analogue control voltage is higher than the threshold voltage, the
minimum set high voltage is supplied to the output of the generator.
This will be increased linearly until the maximum set output voltage, as the control voltage,
reaches the maximum level.