The design level current for these fuses must be multiplied by a factor
of 1.25 times the Isc of the photovoltaic module measured under standard
test conditions (92.94 W/ft
2
and 77 ºC) / (1,000 W/m
2
and 25°C). The
fuses must be suitable for direct current systems, with a breaking
capacity greater than the sum of the intensities of the series of connected
modules, using the method indicated in the National Electrical Code.
Failure to install this type of protection, in the event of an incorrect
positive and negative polarity connection, will cause the reversed series
to act as an electricity receiver causing severe damage to both the
diodes and the other electrical components of the modules.
WARNING: Failure to comply with the provisions of this section will
lead to the loss of guarantee and the exoneration of Siliken from any
type of responsibility for damage to property or injury to people.