Troubleshooting
0 0 7 - 5 5 3 3 - 0 0 1
67
4.2.5
Thermal Alarm
Symptom
Cause
Action
1
. Enclosure system
FAULT LED is amber.
2
. An amber LED on
one or more power
cooling modules
3
. Air temperature
exiting the PSU is
above 55°C.
If the air temperature
through the enclosure
exceeds a pre-set
threshold, a thermal
alarm will sound.
1
. Ensure that the local ambient environment
temperature is below the upper 40°C
specification.
2
. Check the installation for any airflow
restrictions at the front and rear of the
enclosure. A minimum gap of 1" (25mm) at the
front and 2" (50mm) at the rear is
recommended.
3
. Check for restrictions due to dust build-up.
Clean as appropriate.
4
. Check for excessive re-circulation of heated
air from rear to the fron. Use in a fully enclosed
rack installation is not recommended.
5
. If possible, shut down the enclosure and
investigate the problem before continuing.
An enclosure will shut down when a critical temperature threshold is exceeded in
order to prevent permanent damage to the disk drives.
Warning
!
Содержание InfiniteStorage 6120
Страница 1: ...SGI InfiniteStorage 6120 RAID User s Guide 007 5533 001 ...
Страница 10: ......
Страница 11: ...SECTION 1 Introducing the InfiniteStorage 6120 ...
Страница 12: ......
Страница 23: ...SECTION 2 InfiniteStorage 6120 Installation ...
Страница 24: ......
Страница 32: ......
Страница 43: ...SECTION 3 InfiniteStorage 6120 Management ...
Страница 44: ......
Страница 66: ......
Страница 68: ......
Страница 69: ...SECTION 4 Supporting the InfiniteStorage 6120 ...
Страница 70: ......
Страница 85: ...SECTION 5 Appendices ...
Страница 86: ......
Страница 94: ......